These guidelines are to be followed when an aboveground storage tank is constructed, relocated, modified or otherwise installed within the city. All aboveground storage tank requirements for the purposes of this guideline and any other guidelines or requirements of the fire department shall conform to the latest version of the International Fire Code, as adopted and amended by the city, and the National Fire Protection association (NFPA) 30, Flammable and Combustible Liquids Code.
(1) 
The following regulations apply to aboveground storage tanks intended for the storage and dispensing of Class IIIB combustible liquids, as defined by international fire code (IFC), section 2306.2.3.
(A) 
The tank(s) shall be listed and labeled in accordance with underwriter laboratories as being protected above-ground tanks in accordance with UL 2085, and shall be installed in accordance with chapter 57.
(B) 
Tank(s) shall be constructed of steel. Poly-tanks are prohibited.
(C) 
When the installation location may be subject to vehicular impact, bollards must conform to IFC section 312.
(D) 
The tank must display the UL listing placard.
(E) 
Normal and emergency venting shall be provided. Emergency venting shall include the calculations to determine the minimum vent sizing in cubic feet per hour (cfh).
(F) 
Approved flame arrestors, when required by American Petroleum Institute (API) 2028, and venting devices shall be installed in all the vent lines.
(G) 
A spill container having a capacity of not less than 5 gallons shall be provided at each fill connection.
(H) 
Appropriate labeling and signs in accordance with the IFC, section 5003.5, must be provided.
(i) 
Smoking or open flames prohibited.
(ii) 
Emergency procedures.
(iii) 
NFPA 704 or equivalent placard specifically identifying the material therein.
(I) 
All piping and piping systems shall be designed in accordance with NFPA 31 and IFC, chapter 34.
(2) 
The following regulations apply to aboveground storage tanks intended for the storage and/dispensing of flammable liquids, as defined by IFC, section 2306.2.3 and in compliance with applicable requirements of section 5704.2.9.
(A) 
The tank(s) must be installed by a licensed or approved aboveground storage tank installer.
(B) 
Approved flame arrestors and venting devices shall be installed in the all vent lines per IFC, section 5704.2.7.3.1 through 5704.2.7.3.5.3.
(C) 
The tank(s) shall be listed and labeled as protected above-ground tanks in accordance with 2085 and shall be in accordance with chapter 57.
(D) 
When the installation location may be subject to vehicular impact, bollards must conform to IFC, section 312.
(E) 
The tank must display the UL listing placard.
(F) 
A leak detection system must be installed, equipped with on-site audible and/or visual warning devices, as approved by the latest version of the IFC and NFPA 30.
(G) 
A spill container having a capacity of not less than 5 gallons shall be provided at each fill connection.
(H) 
An overfill prevention system shall be provided for each tank to prevent being filled in excess of 95% capacity. The system must meet the requirements of IFC, section 5704.2.9.7.5:
(i) 
Provide an independent means of notifying the person filling that the fluid level has reached 90 percent of tank capacity by providing a tank level gauge marked at 90 percent of tank capacity, or other approved means;
(ii) 
Automatically shut off the flow of fuel to the tank when the quantity reaches 95 percent of tank capacity; and
(iii) 
Reduce the flow rate to not more than 15 gallons per minute so that at the reduced flow rate, the tank(s) will not overflow for 30 minutes and automatically shut-off flow into the tank(s) so that none of the fittings on the top of the tank(s) are exposed to product, because of overfilling.
(I) 
The tank fill connection shall be provided with a means for making a direct connection to the tank’s vehicle fuel delivery hose so that no fuel is exposed to the open air during the filing operation.
(J) 
Anti-siphon devices shall be installed in each pipe connected to the AST, where the piping extends below the level of the tank.
(K) 
Emergency shut offs shall be provided during filling and dispensing operations.
(L) 
Relief valves shall be provided.
(M) 
Pump dispensing devices shall be equipped with vapor-recovery connections.
(N) 
Appropriate labeling and signs in accordance with the latest version of the IFC, section 5704.2.9.7.5.1 must be provided; as follows:
(i) 
A permanent sign shall be placed at the fill point for the tank(s), documenting the filling procedure and tank calibration chart;
(ii) 
Smoking or open flames prohibited;
(iii) 
An approved emergency procedures sign in accordance with IFC 2304.3.5;
(iv) 
A permanent sign indicating that when filling the tank(s), parking is prohibited in the fire lane; and
(v) 
A placard specifically identifying the material therein. The placard shall be in accordance with NFPA 704.
(O) 
Dispensing locations shall limit fuel delivery to 25 gallons and require a manual action to resume, pursuant to IFC 2204.3.7.
(P) 
Any additional requirements of NFPA 30 and/or latest version of the IFC, must also be met.
(3) 
These regulations do not replace, nor supersede any codes and/or ordinances adopted by the city, or written determinations of the fire chief or fire marshal.
(Ordinance 2020-107 adopted 12/8/20)
(a) 
General.
(1) 
Any construction, modification, installation, or fabrication of the system is prohibited without approved plans and permit.
(2) 
Each submittal shall have a completed city fire department plan review/permit application.
(3) 
Plans approved by the fire marshal’s office give authorization for construction. Final approvals are subject to field verification. Any approval issued by the fire marshal’s office does not release the contractor or property owner from the responsibility of full compliance with all applicable codes and ordinances relating to the construction project.
(4) 
All installations and/or operations must concur with the approved plans. Any deviation from the approved plans requires a resubmittal to the fire marshal’s office.
(5) 
All fire department inspection forms and permits shall be kept in a permit packet on the jobsite until final inspection.
(b) 
To expedite the plan review and inspection processes, please refer to the submittal requirements listed below.
(1) 
Provide a written description of the operation to which the tank is to be installed.
(2) 
Site plan drawings of the installation location and layout, to include the following:
(A) 
All buildings and structures;
(B) 
Fire lanes and fire hydrants; and
(C) 
Location of tanks with regards to the above.
(3) 
A full listing of all tanks, piping, valves, and other equipment.
(4) 
Manufacturer documentation for all parts and materials used in the project.
(5) 
Drawings, to include the above requirements, shall be submitted for review and approval, prior to installation.
(6) 
Drawings shall be generated by the installing company specific to the installation, and shall not be copied and marked according to installation. Drawings shall show plan view and other pertinent information.
(7) 
Provide manufacturer’s documentation of tank testing and ability to hold a vacuum. This is in addition to any additional testing required by the fire department.
(Ordinance 2011-25 adopted 6/13/11)
The regulations as outlined in section 3.11.001(1) and (2) do not apply if all the following criteria are met:
(1) 
The contents of the storage tanks are for personal use only and not for resale or distribution;
(2) 
The property on which the storage tanks are located currently has an agriculture exemption as defined by the regulating authority;
(3) 
The total volume of each individual storage tank is 250 gallons or less; and
(4) 
The aggregate storage of all aboveground storage tanks located on the property is less than 1,000 gallons.
(Ordinance 2011-25 adopted 6/13/11)