(a)
All backflow prevention assemblies shall be tested upon installation by a recognized backflow prevention assembly tester and certified to be operating within specifications. Backflow prevention assemblies which are installed to provide protection against health hazards must also be tested and certified to be operating within specifications at least annually by a recognized backflow prevention assembly tester. A test report must be completed by a recognized backflow prevention assembly tester for each assembly tested. The signed and dated original form must be submitted to the city within five (5) working days of the test.
(b)
Assemblies shall be repaired, overhauled or replaced at the expense of the customer whenever said assemblies are found to be defective. Original forms of such tests, repairs and overhauls shall be kept and submitted to the city within five (5) working days of the test, repair or overhaul of each backflow prevention assembly.
(c)
No backflow prevention assembly or device shall be removed from use, relocated, or other assembly or device substituted without the approval of the city. Whenever the existing assembly is moved from the present location or cannot be repaired, the backflow prevention assembly shall be replaced with a backflow prevention assembly or device that complies with this division, the American Water Works Association Manual M14, current edition, the University of Southern California Manual of Cross-Connection Control, current edition, or the current plumbing code of the city, whichever is more stringent.
(d)
All backflow prevention assemblies shall be installed in accordance with the manufacturer's instructions, the American Water Works Association Manual M14 or the University of Southern California Manual of Cross-Connection Control.
(e)
Test gauges used for backflow prevention assemblies testing shall be calibrated at least annually in accordance with the University of Southern California's Manual of Cross-Connection Control or the American Water Works Association's Recommended Practice for Backflow Prevention and Cross-Connection Control Manual M14. The original calibration form must be submitted to the city within five (5) working days after calibration.
(f)
A recognized backflow prevention assembly tester must hold a current endorsement from the state commission on environmental quality ("commission").
(Ordinance 145, sec. 5.131, adopted 12/20/2021)