(a)
Cross connections.
Potable and nonpotable water supplies shall be distributed through systems entirely independent of each other, and any cross-connection between such supplies is prohibited.
(b)
Backflow.
Every potable water outlet shall be protected from backflow, preferably by having the outlet end from which the water flows, spaced a distance from the flood level rim of the receptacle into which the water flows, sufficient to provide a “minimum required air gap” as listed in the table below:
Fixtures | Minimum Air Gaps |
|---|---|
Lavatories with effective openings not greater than 1/2" in diameter | 1.0" |
Sinks, laundry trays, and gooseneck bath faucets with effective openings not greater than 3/4" in diameter | 1.5" |
Overrim bath fillers with effective openings not greater than 1" in diameter | 2.0" |
Effective openings greater than 1" | 2 x effective opening |
Where it is not possible to provide a minimum air gap, then the fixture shall be equipped with an accessibly located backflow preventer installed between the control valve and the fixture or outlet. Such backflow preventer shall be of a design approved by the chief plumbing inspector.
Where it is not possible to provide a minimum air gap or backflow preventer, as may be the case in connections to cooling jackets, condensers, or other industrial or special appliances, then the chief plumbing inspector shall require a separate tank supply or such other means of protection as may be practicable and desirable.
(c)
Water supply tanks.
All potable water supply tanks shall be properly covered to prevent entrance of foreign material into the water supply. Soil or waste lines shall not be permitted to pass directly over such tanks or over manholes in pressure tanks.
(1965 Code, sec. 15-107)