(a)
Traps shall be placed as near the fixture as possible and in no case shall a trap be more than 2' (developed length) from the waste outlet of the fixture. All traps shall have at least a 1-1/2" and not more than a 4" seal. Traps placed below the floor shall have a brass trap screw for cleaning which shall be accessible. The interior walls of cast brass traps, unless machined, shall have been sand blasted so that there are no sharp points or obstructions in the trap. All traps shall be rigidly supported and set true with respect to their water level and shall be located to protect the trap seal. Traps which depend upon the action of movable parts to form a seal shall not be used. Traps which depend upon concealed interior partitions to form a seal or which have interior partitions, which in case of defect will permit the passage of sewer air shall not be used.
(b)
All closet, urinal, slop sink, floor drain and shower traps shall have a visible trap seal.
(1965 Code, sec. 15-160)