(a)
Single-family dwellings.
Non-metallic sheathed cable may be used in installations of single-family dwellings and accessory buildings provided that the dwellings and accessory buildings are not located in restricted areas such as fire zones.
(b)
Buildings with four or less dwelling units.
Non-metallic sheathed cable may be used in installations of residential buildings of four or less dwelling units, two stories or less, provided that common walls and/or floor-ceiling assemblies of fire resistance ratings shall have all wiring encased in approved raceways and electrical outlets shall not be less than 18 inches apart horizontally or vertically.
(c)
Buildings with five or more dwelling units.
Residential buildings of five or more dwelling units shall have all wiring encased in approved raceways.
(Ordinance 84-464 adopted 2/28/84; 1994 Code, sec. 154.170)