That certain document entitled "California Green Building Standards
Code, 2022 Edition," as published by the California Building Standards
Commission, is hereby adopted as the Green Building Standards Code
of the City of Santa Monica.
(Added by Ord. No. 2328CCS §
30, adopted 11/9/10; amended by Ord. No. 2445CCS § 47, adopted 11/12/13; Ord. No. 2527CCS § 11,
adopted 11/22/16; Ord.
No. 2617CCS § 3, adopted 9/24/19; Ord. No. 2778CCS, 5/14/2024)
Notwithstanding any provisions of the 2022 California Green
Building Standards Code, 2022
California Energy Code, or other codes
adopted by any Chapter in Article VIII of the Municipal Code to the
contrary, the following local amendments shall apply.
(Added by Ord. No. 2328CCS §
30, adopted 11/9/10; amended by Ord. No. 2527CCS § 11, adopted 11/22/16; Ord. No. 2617CCS § 3,
adopted 9/24/19; Ord. No. 2778CCS, 5/14/2024)
In addition to definitions set forth in Section 202 of the 2019
California Green Building Standards Code, the following definitions
shall apply:
Major addition.
The addition to any building of either: (1) an additional
story; or (2) additional floor area equal to or greater than fifty
percent of the building's existing floor area prior to the addition.
Sustainability.
Consideration of present development and construction impacts
on the community, the economy, and the environment without compromising
the needs of the future.
Unshaded area.
Area(s) where light emittance from the sun is unobstructed
by fixed objects during the majority of daylight hours between March
21st and September 21st.
(Added by Ord. No. 2328CCS §
30, adopted 11/9/10; amended by Ord. No. 2390CCS § 2, adopted 2/28/12; Ord. No. 2445CCS § 50,
adopted 11/12/13; Ord.
No. 2513CCS § 1, adopted 4/26/16; Ord. No. 2527CCS § 11,
adopted 11/22/16; Ord.
No. 2617CCS § 3, adopted 9/24/19)
Section 301.1.1 of the 2019 California Green Building Standards
Code is amended to read as follows:
301.1.1 Additions and Alterations. With the exception
of Sections 4.201.4 and 4.201.5, which apply only to major additions
to one-, two-, and multi-family dwellings (three stories or less),
the mandatory provisions of Chapter 4 shall be applied to additions
or alterations of existing residential buildings. The requirements
shall apply only to and/or within the specific area of the addition
or alteration.
(Added by Ord. No. 2445CCS §
51, adopted 11/12/13; amended
by Ord. No. 2527CCS § 11, adopted 11/22/16; Ord. No. 2617CCS § 3, adopted 9/24/19)
Section 4.407.1 of the 2019 California Green Building Standards
Code is amended to read as follows:
4.407.1 Flashing Details. Provide flashing details
on the building plans which comply with accepted industry standards
or manufacturer's instructions. Details are shown on the house plans
at all of the following locations:
1. Around
windows and doors.
3. Deck
connections to the structure.
4. Roof-to-wall
intersections.
5. Chimneys
to roof intersections.
6. Drip
caps above windows and doors with architectural projections.
7. Other
locations as identified by the Building Officer.
(Added by Ord. No. 2328CCS §
30, adopted 11/9/10; amended by Ord. No. 2513CCS § 3, adopted 4/26/16; Ord. No. 2527CCS § 11,
adopted 11/22/16; Ord.
No. 2617CCS § 2, adopted 9/24/19)
Section 5.201 of the 2019 California Green Building Standards
Code is amended to read as follows:
5.201.3 Pool Heating—Non-Residential, High-Rise
Residential, and Hotel and Motel Buildings.
|
(a)
|
For new pool construction, if the pool is to be heated, an electric
heat pump water heater or a solar thermal system shall be used for
such heating.
|
5.201.4 Solar Photovoltaic Installation Requirements for
Major Additions to Non-Residential, High-Rise Residential, and Hotel
and Motel Buildings.
|
(a)
|
All major additions to non-residential, high-rise residential,
and hotel and motel buildings are required to install a solar electric
photovoltaic (PV) system. The PV system installed must have a minimum
total wattage 2.0 times the square footage of the footprint of the
addition (2.0 watts per square foot).
|
(b)
|
The requirements of this Section shall be waived or reduced,
by the minimum extent necessary, where: (i) production of electric
energy from solar panels is technically infeasible due to lack of
available and feasible unshaded areas; (ii) the PV system size required
is less than 1,200 watts DC; or (iii) the dwelling has an existing
functioning grid-tied PV system meeting the electrical utility's interconnection
requirements.
|
(c)
|
The requirements of this Section shall take priority if there
is a conflict between compliance with Section 5.201.3 through use
of a solar thermal system and compliance with this Section.
|
(Added by Ord. No. 2540CCS §
3, adopted 3/28/17; amended by Ord. No. 2617CCS § 2, adopted 9/24/19)
Electric vehicle charging for new residential and hotel and
motel buildings is governed by Sections 4.106.4 through 4.106.4.3.6
of the Green Building Standards Code. Electric vehicle charging for
new non-residential buildings is governed by Sections 5.106.5.3 through
5.106.5.3.5 of the Green Building Standards Code.
(Added by Ord. No. 2445CCS §
55, adopted 11/12/13; amended
by Ord. No. 2527CCS § 11, adopted 11/22/16; Ord. No. 2617CCS § 2, adopted 9/24/19)
Section 4.106.4 of the 2022 California Green Building Code and
its subsections are amended to read as follows:
A4.106.8 Electric vehicle (EV) charging for new construction. New construction shall comply with Section A4.106.8.1 or A4.106.8.2,
to facilitate the installation and use of EV ready spaces. Electric
vehicle supply equipment (EVSE) shall comply with the California Electrical
Code.
A4.106.8.1 New one- and two-family dwellings and townhouses
with attached private garages.
Tier 1 and Tier 2. For each dwelling unit, a dedicated
208/240-volt branch circuit shall be installed in the raceway required
by Section 4.106.4.1. The branch circuit and associated overcurrent
protective device shall be rated at 40 amperes minimum. Other electrical
components, including a receptacle or blank cover, related to this
Section shall be installed in accordance with the California Electrical
Code.
A4.106.8.1.1 Identification. The service panel
or subpanel circuit directory shall identify the overcurrent protective
device designated for future EV charging purposes as "EV READY" in
accordance with the California Electrical Code. The receptacle or
blank cover shall be identified as "EV READY."
A4.106.8.2 New multifamily dwellings, hotels and motels. New multifamily dwellings, hotels and motels shall meet the following
requirements:
A4.106.8.2.1 Multifamily dwellings, hotels and motels.
Tier 1. New multifamily projects shall comply with
Option A.
Option A for new multifamily dwellings, hotels and motels.
1. EV Ready parking spaces with receptacles.
a. Hotels and motels. Fifty percent of the total number of parking spaces
shall be equipped with low power Level 2 EV charging receptacles.
b. Multifamily parking facilities. Fifty percent of the total number
of parking spaces shall be equipped with low power Level 2 EV charging
receptacles.
EV charging receptacles required by this Section shall be located
in at least one assigned parking space per dwelling unit where assigned
parking is provided but need not exceed 50% of the total number of
assigned parking spaces provided on the site.
|
Exceptions:
|
1. Areas of parking facilities served by parking lifts, including,
but not limited to, automated mechanical-access open parking garages
as defined in the California Building Code; or parking facilities
otherwise incapable of supporting electric vehicle charging.
|
2. Hotels and motels may substitute Level 2 EV chargers for
some or all of the required EV charging receptacles. Where Level 2
EV chargers are installed in place of low power Level 2 receptacles,
at least 50% of the installed EV chargers shall be equipped with J1772
connectors.
|
2. EV Ready parking spaces with EV chargers.
a. Hotels and motels. Fifteen percent of the total number of parking
spaces for hotels and motels shall be equipped with Level 2 EV chargers.
At least 50% of the required EV chargers shall be equipped with J1772
connectors.
b. Multifamily parking facilities. Fifteen percent of the total number
of parking spaces shall be equipped with Level 2 EV chargers. At least
50% of the required EV chargers shall be equipped with J1772 connectors.
Where common use parking or unassigned parking is provided, EV chargers
shall be located in common use or unassigned parking areas and shall
be available for use by all residents or guests.
Exception:
|
1. Areas of parking facilities served by parking lifts, including,
but not limited to, automated mechanical-access open parking garages
as defined in the California Building Code; or parking facilities
otherwise incapable of supporting electric vehicle charging.
|
An automatic load management system (ALMS) may be used to reduce
the maximum required electrical capacity to each space served by the
ALMS. The electrical system and any on-site distribution transformers
shall have sufficient capacity to deliver at least 3.3 kW simultaneously
to each EV charging station (EVCS) served by the ALMS. The branch
circuit shall have a minimum capacity of 40 amperes, and installed
EV chargers shall have a capacity of not less than 30 amperes.
|
A4.106.8.2.2 Technical requirements. The
EV spaces required by Section A4.106.8.2 shall be designed and constructed
in accordance with Sections 4.106.4.2, 4.106.4.2.2.1.1, 4.106.4.2.2.1.2,
and 4.106.4.2.5.
(Added by Ord. No. 2634CCS §
2, adopted 4/28/20; amended by Ord. No 2723CCS § 3, adopted 10/11/22; Ord. No. 2783CCS, 6/25/2024)
Section 5.106.5.3 of the 2022 California Green Building Code
and its subsections are amended to read as follows:
5.106.5.3 Electric vehicle (EV) charging. Construction
shall comply with Section A5.106.5.3.1 Tier 1, and in accordance with
regulations in the
California Building Code and the California Electrical
Code.
A5.106.5.3.1 Tier 1. Comply with Section 5.106.5.3.1
EV capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations
and associated Table A5.106.5.3.1 Tier 1, or comply with Section A5.106.5.3.2
Electric vehicle charging stations (EVCS) — Power
allocation method and associated Table A5.106.5.3.2 Tier 1.
Refer to Section 5.106.5.3.2 for the permitted use of Level
2 or direct current fast charger (DCFC) to create EVCS. Refer to Section
5.106.3.2.1 for the allowed use of DCFC to comply with both EV capable
spaces and Level 2 EVSE. Refer to Section 5.106.5.3.3 for the allowed
use of automatic load management system (ALMS).
Table A5.106.5.3.1
|
---|
Total Number of Actual Parking Spaces
|
Tier 1 Number of Required EV Capable Spaces
|
Tier 1 Number of EVCS (EV Capable Spaces Provided with EVSE)2
|
---|
0-9
|
2
|
0
|
10-25
|
5
|
2
|
26-50
|
11
|
4
|
51-75
|
19
|
5
|
76-100
|
26
|
9
|
101-150
|
38
|
13
|
151-200
|
53
|
18
|
201 and over
|
30% of actual parking spaces1
|
33% of EV capable spaces1
|
Notes:
|
1. Calculation for spaces shall be rounded up to the nearest
whole number.
|
2. The number of required EVCS (EV capable spaces provided with
EVSE) in column 3 count toward the total number of required EV capable
spaces shown in column 2.
|
3. At least one Level 2 EVSE shall be provided.
|
A5.106.5.3.2 Electric vehicle charging stations (EVCS)
- Power Allocation method. The power allocation method may
be used as an alternative to the requirements in Section 5.106.5.3.1,
Section 5.106.5.3.2, and associated Table A5.106.5.3.1 Tier 1. Use
Table A5.106.5.3.2 Tier 1 to determine the total power in kVA required
based on the total number of actual parking spaces.
Power allocation method shall include the following:
|
1.
|
Use any kVA combination of EV capable spaces, low power Level
2, Level 2 or DCFC EVSEs.
|
2.
|
At least one Level 2 EVSE shall be provided.
|
Table A5.106.5.3.2 Tier 1
|
---|
Total Number of Actual Parking Spaces
|
Minimum Total kVA@ 6.6 kVA
|
Total kVA Required in any Combination of EV Capable3, 4, Low Power Level 2, Level 21, 2, or DCFC
|
---|
0-9
|
13.2
|
13.2
|
10-25
|
33
|
33
|
26-50
|
72.6
|
72.6
|
51-75
|
125.4
|
125.4
|
76-100
|
171.6
|
171.6
|
101-150
|
250.8
|
250.8
|
151-200
|
349.8
|
349.8
|
201 and over
|
30% of actual parking spaces x 6.6
|
Total required kVA = P x 0.30 x 6.6
Where P = Parking spaces in facility
|
Notes:
|
1.
|
Level 2 EVSE at 6.6 kVA minimum.
|
2.
|
At least one Level 2 EVSE shall be provided.
|
3.
|
Maximum allowed kVA to be utilized for EV capable spaces is
67%.
|
4.
|
If EV capable spaces are utilized, they shall meet the requirements
of Section 5.106.5.3.1 EV capable spaces.
|
5.106.5.3.3 Use of automatic load management systems (ALMS). ALMS shall be permitted for EVCS. When an ALMS is installed, the
required electrical load capacity specified in Section 5.106.5.3.1
for each EVCS may be reduced when serviced by an EVSE controlled by
an ALMS. Each EVSE controlled by an ALMS shall deliver a minimum 30
amperes to an EV when charging one vehicle and shall deliver a minimum
3.3 kW while simultaneously charging multiple EVs.
5.106.5.3.4 Accessible electric vehicle charging station
(EVCS). When EVSE is installed, accessible EVCS shall be provided
in accordance with the
California Building Code Chapter 11B, Section
11B-228.3.
Note: 5.106.5.3.5 Electric
vehicle charging station signage. For EVCS
signs, refer to Electric vehicle charging stations
shall be identified by signage or pavement markings in compliance
with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission
Vehicle Signs and Pavement Markings) or its successor(s).
5.106.5.3.5.1 Additional EV ready requirement for office
facilities. In addition to the requirements of Table A5.106.5.3.1,
for office parking facilities, an additional 20% (rounded to the nearest
whole number) of the total number of parking spaces shall be equipped
with low power Level 2 EV charging receptacles.
5.106.5.4 Additions or alterations to existing buildings
or parking facilities [A]. [BSC-CG] Existing buildings or parking
facilities being modified by one of the following shall comply with
Section 5.106.5.4.1 or 5.106.5.4.2. When EVSE is installed, accessible
EVCS shall be provided in accordance with the California Building
Code, Chapter 11B, Section 11B-228.3.
1. When the scope of construction work includes
an increase in power supply to an electric service panel as part of
a parking facility addition or alteration.
|
2. When a new photovoltaic system is installed covering
existing parking spaces.
|
3. When additions or alterations to existing buildings
are triggered pursuant to code Section 301.3 and the scope of work
includes an increase in power supply to an electric service panel.
|
Exceptions:
|
1. On a case-by-case basis where the local enforcing
agency has determined compliance with this Section is not feasible
based upon one of the following conditions:
|
a. Where there is no local utility power supply.
|
b. Where the local utility is unable to supply adequate
power.
|
c. Where there is evidence suitable to the local
enforcement agency substantiating that additional local utility infrastructure
design requirements, directly related to the implementation of Section
5.106.5.3, may adversely impact the construction cost of the project.
|
d. Where demonstrated as impracticable excluding
local utility service or utility infrastructure issues.
|
2. Remote parking facilities that do not have access
to the building service panel.
|
3. Parking area lighting upgrades where no trenching
is part of the scope of work.
|
4. Emergency repairs, including, but not limited
to, water line break in parking facilities, natural disaster repairs,
etc.
|
5.106.5.4.1 Existing buildings or parking areas without
previously installed EV capable infrastructure [A]. When EV
capable infrastructure does not exist at an existing parking facility
or building, and the parking facility or building undergoes an addition
or alteration listed in Section 5.106.5.4, construction shall include
electric vehicle charging in compliance with either Section 5.106.5.3
and associated Table 5.106.5.3.1, or Section 5.106.5.3.6 and associated
Table 5.106.5.3.6 for the total number of actual parking spaces being
added or altered.
5.106.5.4.2 Existing buildings or parking areas with previously
installed EV capable infrastructure [A]. When EV capable infrastructure
is available at an existing parking facility or building, and the
parking facility or building is undergoing an addition or alteration
listed in Section 5.106.5.4, construction shall include electric vehicle
charging in compliance with either Section 5.106.5.3 and associated
Table 5.106.5.3.1, or Section 5.106.5.3.6 and associated Table 5.106.5.3.6
utilizing the existing EV capable allocated power and infrastructure
for the total number of actual parking spaces being added or altered.
If the area being added or altered exceeds the existing EV capable
capacity, allocated power and infrastructure, provide additional EV
charging as needed to comply with this section.
5.106.5.5 Electric vehicle (EV) charging: medium-duty
and heavy-duty. [N] [BSG-CG] Construction shall comply with
Section 5.106.5.4.1 to facilitate future installation of electric
vehicle supply equipment (EVSE). Construction for warehouses, grocery
stores and retail stores with planned off-street loading spaces shall
also comply with Section 5.106.5.4.5.1 for future installation of
medium- and heavy-duty EVSE.
Exceptions:
|
1.
|
On a case-by-case basis where the local enforcing agency has
determined compliance with this section is not feasible based upon
one of the following conditions:
|
|
a.
|
Where there is no local utility power supply.
|
|
b.
|
Where the local utility is unable to supply adequate power.
|
|
c.
|
Where there is evidence suitable to the local enforcing agency
substantiating that additional local utility infrastructure design
requirements, directly related to the implementation of Section 5.106.5.3,
may adversely impact the construction cost of the project.
|
When EVSE(s) is/are installed, it shall be in accordance with
the
California Building Code, the California Electrical Code and as
follows:
5.106.5.4.5.1 Electric vehicle charging readiness requirements
for warehouses, grocery stores and retail stores with planned off-street
loading spaces. In order to avoid future demolition when adding
EV supply and distribution equipment, spare raceway(s) or busway(s)
and adequate capacity for transformer(s), service panel(s) or subpanel(s)
shall be installed at the time of construction in accordance with
the California Electrical Code. Construction plans and specifications
shall include, but are not limited to, the following:
1.
|
The transformer, main service equipment and subpanels shall
meet the minimum power requirement in Table 5.106.5.5.1 to accommodate
the dedicated branch circuits for the future installation of EVSE.
|
2.
|
The construction documents shall indicate one or more location(s)
convenient to the planned off-street loading space(s) reserved for
medium- and heavy-duty ZEV charging cabinets and charging dispensers,
and a pathway reserved for routing of conduit from the termination
of the raceway(s) or busway(s) to the charging cabinet(s) and dispenser(s),
as shown in Table 5.106.5.5.1.
|
3.
|
Raceway(s) or busway(s) originating at a main service panel
or a subpanel(s) serving the area where potential future medium- and
heavy-duty EVSE will be located, and shall terminate in close proximity
to the potential future location of the charging equipment for medium-
and heavy-duty vehicles.
|
4.
|
The raceway(s) or busway(s) shall be of sufficient size to carry
the minimum additional system load to the future location of the charging
for medium- and heavy-duty ZEVs as shown in Table 5.106.5.4.5.1.
|
Table 5.106.5.4.5.1
Raceway Conduit and Panel Power Requirements for Medium- and
Heavy-Duty EVSE [N]
|
---|
Building Type
|
Building Size
(sq. ft.)
|
Number of Off-Street Loading Spaces
|
Additional Capacity Required (kVa) for Raceway & Busway
and Transformer & Panel
|
---|
Grocery
|
|
1 or 2
|
200
|
10,000 to 90,000
|
3 or Greater
|
400
|
Greater than 90,000
|
1 or Greater
|
400
|
Manufacturing Facilities
|
10,000 to 50,000
|
1 or 2
|
200
|
10,000 to 50,000
|
3 or Greater
|
400
|
Greater than 50,000
|
1 or Greater
|
400
|
Office Buildings
|
10,000 to 135,000
|
1 or 2
|
200
|
10,000 to 135,000
|
3 or Greater
|
400
|
Greater than 135,000
|
1 or Greater
|
400
|
Retail
|
10,000 to 135,000
|
1 or 2
|
200
|
3 or Greater
|
400
|
Greater than 135,000
|
1 or Greater
|
400
|
Warehouse
|
20,000 to 256,000
|
1 or 2
|
200
|
3 or Greater
|
400
|
Greater than 256,000
|
1 or Greater
|
400
|
5.106.5.6 Electric vehicle (EV) charging at public schools
and community colleges. [DSA-SS] Electric vehicle infrastructure
and electric vehicle charging stations shall comply with Section 5.106.5.6
and shall be provided in accordance with regulations in the California
Building Code and the California Electrical Code.
Exceptions:
|
1. On a case-by-case basis where compliance with
this Section has been demonstrated to be not feasible based upon one
of the following conditions, and with concurrence by the Division
of the State Architect (DSA), compliance with Section 5.106.5.6 shall
not be required.
|
|
a.
|
Where there is no local utility power supply.
|
|
b.
|
Where the local utility is unable to supply adequate power.
|
|
c.
|
The installation of EVCS is impracticable.
|
2. Parking spaces accessible only by automated mechanical
car parking systems are not required to comply with Section 5.106.5.6.
|
5.106.5.6.1 EV capable spaces. EV capable spaces
shall be provided in accordance with Table A5.106.5.6.1 and the following
requirements:
|
1. Raceways complying with the California Electrical
Code and no less than one-inch (25 mm) diameter shall be provided
and shall originate at a service panel or a subpanel(s) serving the
area and shall terminate in close proximity to the proposed location
of the EV capable space and into a suitable listed cabinet, box, enclosure
or equivalent. A common raceway may be used to serve multiple EV capable
spaces.
|
2. A service panel or subpanel(s) shall be provided
with panel space and electrical load capacity for a dedicated 208/240
volt, 40-ampere minimum branch circuit for each EV capable space,
with delivery of 30-ampere minimum to an installed EVSE at each EVCS.
|
3. The electrical system and any on-site distribution
transformers shall have sufficient capacity to supply full rated amperage
at each EV capable space.
|
4. The service panel or subpanel circuit directory
shall identify the reserved overcurrent protective device space(s)
as "EV CAPABLE." The raceway termination location shall be permanently
and visibly marked as "EV CAPABLE."
|
5.106.5.6.2 Electric vehicle charging stations (EVCS). EV capable spaces shall be provided with EVSE to create EVCS in
the number indicated in Table 5.106.5.6.1 and shall comply with Section
5.106.5.6.2. EVCS shall be serviced by Level 2 or Direct Current Fast
Charging (DCFC) EVSE, or with EVSE in any combination of Level 2 and
DCFC. Accessible EVCS shall be provided in accordance with California
Building Code Chapter 11B.
5.106.5.6.2.1 Reduced number of EV capable spaces. The installation of each DCFC EVSE shall be permitted to reduce
the minimum number of required EV capable spaces indicated in Table
5.106.5.6.1 by five and reduce proportionally the required electrical
load capacity to the service panel or subpanel.
5.106.5.6.2.2 Multiple connectors. EVSE with multiple
vehicle connectors capable of charging multiple EVs simultaneously
shall be permitted if the electrical load capacity required by Section
5.106.5.6.1 for each EV capable space is accumulatively supplied to
the EVSE.
5.106.5.6.2.3 Use of automatic load management systems
(ALMS). ALMS shall be permitted for EVCS installed in accordance
with Section 5.106.5.6.2. When ALMS is installed, the required electrical
load capacity specified in Section 5.106.5.6.1 for each EVCS may be
reduced when serviced by an EVSE controlled by an ALMS. Each EVSE
controlled by an ALMS shall deliver a minimum 30 amperes to an EV
when charging one vehicle and shall deliver a minimum 3.3 kW while
simultaneously charging multiple EVs.
5.106.5.6.3 EVCS alternative compliance.
In lieu of compliance with Section 5.106.5.6.2, EVCS shall be
provided with Level 1, low power Level 2, or Level 2, or any combination
of Level 1, low power Level 2 or Level 2 EVSE such that the total
power supplied by the combination of EVSE meets the minimum power
indicated in Table 5.106.5.6.3, based on the total number of actual
parking spaces in each parking facility.
Table 5.106.5.6.3
|
---|
Number of Parking Spaces in a Parking Facility
|
Minimum Total Power (kVa) Required for EVCS
|
---|
0-9
|
0
|
10-25
|
7
|
26-50
|
14
|
51-75
|
20
|
76-100
|
27
|
101-150
|
40
|
151-200
|
60
|
201 and over
|
Total required KVA = P x 0.05 x 6.6
Where P = Parking spaces in facility
|
5.106.5.6.4 EVCS for alterations of or additions to parking
facilities. Alterations of or additions to parking facilities
shall provide EVCS in compliance with Section 5.106.5.6.4. The installation
of infrastructure for EV capable spaces required to be provided without
EVSE shall not be required.
5.106.5.6.4.1 Alterations of and additions to parking
facilities. EVCS shall be provided in accordance with the number
indicated in Table 5.106.5.6.1 or minimum power indicated in Table
5.106.5.6.3 when the scope of work includes an increase in power supply
to an electric panel serving light fixtures illuminating the parking
area or when area containing parking spaces is added to a parking
facility. The number of required EVCS shall be based on the total
number of existing and new parking spaces in the parking facility.
5.106.5.6.4.2 Alterations consisting of the installation
of photovoltaic systems. EVCS shall be provided in accordance
with the number indicated in Table 5.106.5.6.1 or maximum power indicated
in Table 5.106.5.6.3 when a new photovoltaic system is installed in
an existing parking facility.
5.106.5.6.5 Requirement to install EVSE. Level
2 EVSE shall be provided in all existing EV capable spaces to create
EVCS when a project is required by
California Administrative Code
Section 4-309 to be submitted for plan approval to the Division of
the State Architect. When EVSE is installed in existing EV capable
spaces, accessible EVCS shall be provided in accordance with California
Building Code Chapter 11B.
Exception: Projects in which improvements in parking
areas consist only of accessibility improvements are not required
to comply with Section 5.106.5.6.5.
(Added by Ord. No. 2634CCS §
3, adopted 4/28/20; amended by Ord. No. 2723CCS § 4, adopted 10/11/22; Ord. No. 2783CCS, 6/25/2024)
(a)
Adoption of Local Amendments. That certain document
entitled "California Green Building Standards Code, 2022 Edition,"
as published by the California Building Standards Commission, is hereby
amended with the following local amendments:
(b)
Definitions. Unless defined herein, all defined
terms shall be those found in the 2022 California Green Building Standards
Code. For the application of this Section the following definitions
shall apply:
Cement Limit:
The maximum allowed amount of cement in concrete at specified
compressive strengths measured in pounds per cubic yards and listed
on concrete mix designs.
Concrete:
Any approved combination of mineral aggregates bound together
into a hardened conglomerate in accordance with the requirements of
this Code.
Environmental Product Declaration (EPD):
EPDs present quantified environmental information on the
lifecycle of a product to enable comparisons between products fulfilling
the same function. EPDs must conform to ISO 14025, and EN 15804 or
ISO 21930, and have at least a "cradle to gate" scope (which covers
product lifecycle from resource extraction to the factory).
High Early Strength Cement:
Cement used to produce concrete with the compressive strength
shown on submitted building plans within 12 hours.
Newly-Constructed Building:
A new structure that has never before been used or occupied
for any purpose or removal and replacement of an existing structure,
or repair, alteration, modification, addition to, or rehabilitation
of an existing structure, where a demolition will occur, as defined
Santa Monica Municipal Code Section 9.25.030(A)(1) or (A)(2).
(c)
Scope. The requirements of this Section shall apply to all newly-constructed buildings and swimming pools and spas as provided in Section
8.106.130, subsection
(a) for which a building permit for construction is issued on or after 30 days following the second reading of the ordinance codified in this Section. Projects that do not meet the thresholds requiring plan review, as determined by the Building Officer, shall be exempt from this Section.
(d)
(1)
Structural concrete shall be designed and constructed in accordance with the requirements of this Chapter and ACI 318 as amended in Section 1905 of this Code and Santa Monica Municipal Code Section
8.106.130. Except for the provisions of Sections
1904 and
1907, and other than compliance with Santa Monica Municipal Code Section
8.106.130, the design and construction of slabs on grade shall not be governed by this Chapter unless they transmit vertical loads or lateral forces from other parts of the structure to the soil.
(2)
Section R402.2.1 of the 2022 California Residential Code
is hereby amended as follows:
R402.2.1 Materials for concrete. Materials for concrete shall comply with the requirements of Section R608.5.1, as amended by Santa Monica Municipal Code Section
8.106.130.
(3) Section R404.1.3 of the 2022 California Residential Code is
hereby amended as follows:
R404.1.3 Concrete foundation walls. Concrete foundation walls that support light-frame walls shall be designed and constructed in accordance with the provisions of this Section, ACI 318, ACI 332, or PCA 100, as amended by Santa Monica Municipal Code Section
8.106.130. Concrete foundation walls that support above-grade concrete walls that are within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of this Section, ACI 318, ACI 332, or PCA 100, as amended by Santa Monica Municipal Code Section
8.106.130. Concrete foundation walls that support above-grade concrete walls that are not within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of ACI 318, ACI 332, or PCA 100, as amended by Santa Monica Municipal Code Section
8.106.130. Where ACI 318, ACI 332, PCA 100 or the provisions of this Section, as amended by Santa Monica Municipal Code Section
8.106.130, are used to design concrete foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
(4)
Section R506.1 of the 2022 California Residential Code
is hereby amended as follows:
R506.1 General. Concrete slab-on-ground floors shall be designed and constructed in accordance with the provisions of this Section or ACI 332, as amended by Santa Monica Municipal Code Section
8.106.130. Floors shall be a minimum 3 1/2 inches (89 mm) thick (for expansive soils, see Section R403.1.8). The specified compressive strength of concrete shall be as set forth in Section R402.2.
(5)
Section R608.5 of the 2022 California Residential Code
is hereby amended as follows:
R608.5 Materials. Materials used in the construction of concrete walls shall comply with this section, as amended by, Santa Monica Municipal Code Section
8.106.130.
(6)
Section 301 of the 2022 California Green Building Standards Code is hereby augmented with the following:
301.6 Low-carbon concrete requirements for all projects. Plain and reinforced concrete installed as part of any project subject to the application of this Code shall demonstrate compliance with the requirements of Santa Monica Municipal Code Section
8.106.130, the full text of which is herein added to this Code by reference.
(7)
Section 5.409.3 Product GWP compliance - prescriptive
path, of the California Green Building Standards Code, is hereby adopted
and amended as follows:
5.409.3 Product GWP compliance - Prescriptive path. Each product that is permanently installed and listed in Table 5.409.3
shall have a Type III environmental product declaration (EPD), either
product-specific or factory-specific. All concrete must comply with
Section 5.409.3.2.
Table 5.409.3
PRODUCT GWP LIMITS
|
---|
Buy Clean California Materials Product Category1
|
Maximum acceptable GWP value
(unfabricated)
(GWP allowed)
|
Unit of Measurement
|
---|
Hot-rolled structural steel sections
|
1.77
|
MT CO2e/MT
|
Hollow structural sections
|
3.00
|
MT CO2e/MT
|
Steel plate
|
2.61
|
MT CO2e/MT
|
Concrete reinforcing steel
|
1.56
|
MT CO2e/MT
|
Flat glass
|
2.50
|
kg CO2e/MT
|
Light-density mineral wool board insulation
|
5.83
|
kg CO2e/1 m2
|
Heavy-density mineral wool board insulation
|
14.28
|
kg CO2e/1 m2
|
Concrete, Ready-Mixed2, 3
|
---|
Concrete Product Category
|
Maximum GWP allowed value
(GWP allowed)
|
Unit of Measurement
|
---|
up to 2499 psi
|
450
|
kg CO2e/m3
|
2500-3499 psi
|
489
|
kg CO2e/m3
|
3500-4499 psi
|
566
|
kg CO2e/m3
|
4500-5499 psi
|
661
|
kg CO2e/m3
|
5500-6499 psi
|
701
|
kg CO2e/m3
|
6500 psi and greater
|
799
|
kg CO2e/m3
|
Concrete, Lightweight Ready-Mixed2
|
---|
Concrete Product Category
|
Maximum GWP allowed value
(GWP allowed)
|
Unit of Measurement
|
---|
up to 2499 psi
|
875
|
kg CO2e/m3
|
2500-3499 psi
|
956
|
kg CO2e/m3
|
3500-4499 psi
|
1,039
|
kg CO2e/m3
|
Footnotes:
|
1.
|
The GWP values of the products listed in Table
5.409.3 are based on 175 percent of Buy Clean California Act (BCCA)
GWP values, except for concrete products which are not included in
BCCA.
|
2.
|
For concrete, 175 percent of the National Ready
Mix Concrete Association (NRMCA) 2022 version 3 Pacific Southwest
regional benchmark values are used for the GWP allowed, except for
High Early strength.
|
3.
|
Concrete High Early Strength ready-mixed shall
be calculated at 130 percent of the Ready mixed concrete GWP allowed
values for each product category.
|
5.409.3.1. Products shall not exceed the
maximum GWP value specified in Table 5.409.3.
Exception: Concrete may be considered
one product category to meet compliance with this section. A weighted
average of the maximum GWP for all concrete mixes installed in the
project shall be less than the weighted average maximum GWP allowed
per Table 5.409.3 using Exception Equation 5.409.3.1. Calculations
shall be performed with consistent units of measurement for the material
quantity and the GWP value. For the purposes of this exception, industry
wide EPD's are acceptable.
Exception EQUATION 5.409.3.1
GWPn < GWPallowed
where
GWPn = Ʃ (GWPn)(Vn) and GWPallowed = Ʃ (GWPallowed)(Vn)
and
n = each concrete mix installed in the project
GWPn = the GWP for concrete
mix n per concrete mix EPD, in kg CO2e/m3
GWPallowed = the GWP potential
allowed for concrete mix n per Table 5.409.3
Vn = the volume of concrete
mix n installed in the project, in m3.
5.409.3.2. Verification of compliance. Calculations to demonstrate compliance, Type III EPDs for products
required to comply if included in the project, and Worksheet WS-5
signed by the design professional of record shall be provided on the
construction documents. Updated EPDs for products used in construction
shall be provided to the owner at the close of construction and to
the enforcement entity upon request. The enforcing agency may require
inspection and inspection reports in accordance with Sections 702.2
and 703.1 during and at completion of construction to demonstrate
substantial conformance. Inspection shall be performed by the design
professional of record or third party acceptable to the enforcing
agency.
5.409.3.2 Reduction in cement use requirements. All plain and reinforced concrete installed in residential and non-residential newly-constructed buildings and swimming pools and spas as provided in Section
8.106.130, Subsection
(a) for which a building permit for construction is issued on or after 30 days after the second reading of the ordinance codified in this Section shall comply with Section 5.409.3 to reduce embodied carbon in concrete. Projects that do not meet the thresholds requiring plan review, as determined by the Building Officer, shall be exempt from this Section.
5.409.3.2.1. Products shall comply with the requirements
for product GWP or cement limit performance in accordance with Section
5.409.3 using the maximum acceptable GWP or cement limit value for
the product category listed in Table 5.409.3.5.
5.409.3.3 Project based compliance. A weighted
average of the maximum GWP or cement limit for all concrete mixes
installed in the project shall be less than the weighted average maximum
GWP or cement limit allowed per Table 5.409.3.5 using Project Based
Equation 5.409.3.3A or 5.409.3.3B calculations shall be performed
with consistent units of measurement for the material quantity and
the GWP or cement limit value. For the purposes of this exception,
industry wide EPDs are acceptable.
5.409.3.4 Verification of compliance. Calculations
to demonstrate compliance, Type III EPDs for products required to
comply if included in the project, or mix designs showing the cement
content, and the Acknowledgement Worksheet signed by the design professional
of record shall be provided on the construction documents. Updated
EPDs or mix designs for products used in construction shall be provided
to the owner at the close of construction and to the City. The City
requires inspection and inspection reports in accordance with Sections
702.2 and 703.1 during and at completion of construction to demonstrate
substantial conformance. Inspection shall be performed by the design
professional of record or third party acceptable to the City
TABLE 5.409.3.5
|
Concrete GWP and Cement Limits
|
Note: Acceptable supplementary cementitious materials used to
replace cement in concrete mix designs include, but are not limited
to:
|
1. Fly ash conforming to ASTM C618.
|
2. Slag cement (GGBFS) conforming to ASTM C989.
|
3. Silica fume conforming to ASTM C1240.
|
4. Natural pozzolan conforming to ASTM C618.
|
5. Blended supplementary cementitious materials
conforming to ASTM C1697.
|
6. Ultra-fine fly ash (UFFA) conforming to ASTM
C618.
|
7. Metakaolin conforming to ASTM C618.
|
8. Ground-glass pozzolan per ASTM C1866/C1866M.
|
9. Other materials with comparable or superior environmental
benefits, as approved by the Engineer of Record and enforcing authority.
|
Concrete, Ready-Mixed
|
---|
|
Cement Limits
|
Global Warming Potential (GWP) Limits
|
---|
Minimum specified 28 day compressive strength f'c, psi
|
Maximum cement content, lbs/yd3
|
Maximum Global Warming Potential (GWP) kg CO2e/m3
|
---|
up to 2500
|
362
|
260
|
3000
|
410
|
289
|
4000
|
456
|
313
|
5000
|
503
|
338
|
6000
|
531
|
356
|
7000
|
594
|
394
|
7001 and higher
|
657
|
433
|
up to 2499 light weight
|
512
|
500
|
Up to 3499 light weight
|
571
|
546
|
Up to 4499 light weight
|
629
|
594
|
Notes
|
(1)
|
For concrete strengths between the stated values, use linear
interpolation to determine cement and/or GWP limits.
|
(2)
|
Cement of any type per ASTM C150, ASTM C595.
|
(3)
|
Project applicants can choose to comply using the maximum cement
limits OR the maximum global warming potential limits.
|
5.409.3.6 Allowable increases.
|
1. Cement or GWP limits shown in Table 5.409.3.5 can be increased
by 30% for concrete demonstrated in writing to the Building Official
or for Public Works Projects, the City Engineer, as requiring high
early strength. Such concrete could include precast, prestressed concrete;
beams and slabs above grade; shotcrete; and other applications as
demonstrated in writing by the professional engineer or other licensed
professionals.
|
2. Approved Cements. The industry-average EPD describing Portland
cements produced in the United States by the Portland Cement Association,
certified by ASTM, lists a Portland cement global warming potential
of 922 kg CO2e/metric ton. If your plant specific
EPD for a cement or blended cement, demonstrated to the Building Official
by an approved EPD, is lower than 922 kg CO2e/metric ton an increase in cement is allowed (e.g. use of ASTM 595
Type 1L Cement). The maximum cement content may be increased above
the compliance level in Table 5.409.3.5 proportionate to the percentage
difference in GWP of the plant specific EPD and the industry-average
922 kg CO2e/metric ton.
|
Formula: 922 - Plant Specific GWP = Difference
|
Difference/922 = Percent Allowable Increase
|
For example: A plant specific EPD of 900 kg CO2e/metric ton could allow up to a 2% increase in allowable
cement.
922 - 900 = 22
|
22/922 = 0.02.
|
5.409.3.7 Exemptions. If an applicant for a project
subject to this chapter believes that circumstances exist that make
it a hardship or infeasible to meet the requirements of this Section,
the applicant may request an exemption in writing to the Building
Department or Public Works (for City project or work within the public
right-of-way). In applying for an exemption, the burden is on the
applicant to show hardship or infeasibility. Circumstances that constitute
hardship or infeasibility may include:
|
1.
|
There is a lack of commercially available material necessary
to comply with this Section. Applicant must provide written notice
from at least two local concrete suppliers that there is a lack of
commercially available materials necessary to comply.
|
2.
|
The cost of the concrete mix that achieves compliance is more
than the cost of a 100% Portland cement (ASTM C-150) or a 100% Portland
limestone cement (ASTM C-595 Type 1L) mix. Applicant must provide
quotes from at least two local concrete suppliers comparing the cost
of a 100% PC (ASTM C-150) or 100% PLC (ASTM C-595 Type 1L) mix and
equivalent strength low-carbon concrete mix.
|
3.
|
Emergency purchases made in conformance with Section 2.24.240.
|
4.
|
Building permit applications submitted over the counter are
exempt from this Section.
|
5.
|
This Section does not apply to pre-packaged proprietary concrete
bags used for small quantities (less than three yards) or where there
is an immediate need for on-site concrete mixing.
|
(Added by Ord. No. 2778CCS, 5/14/2024)