All development and building work, including man-made changes to improved or unimproved real estate for which specific provisions are not specified in this Part
6 or the Uniform Construction Code (N.J.A.C. 5:23), shall meet the following requirements:
A. Be located and constructed to minimize flood damage;
B. Meet the limitations of §
200-307A of this Part
6 when located in a regulated floodway;
C. Be anchored to prevent flotation, collapse or lateral movement resulting from hydrostatic and hydrodynamic loads, including the effects of buoyancy, during the conditions of flooding up to the local design flood elevation determined according to §
200-284;
D. Be constructed of flood-damage-resistant materials as described in
ASCE 24 Chapter 5;
E. Have mechanical, plumbing, and electrical systems above the local design flood elevation determined according to §
200-284; or meet the requirements of ASCE 24, Chapter 7, which requires that attendant utilities are located above the local design flood elevation unless the attendant utilities and equipment are:
(1)
Specifically allowed below the local design flood elevation;
and
(2)
Designed, constructed, and installed to prevent floodwaters,
including any backflow through the system, from entering or accumulating
within the components.
F. Not exceed the flood storage displacement limitations in fluvial
flood hazard areas in accordance with N.J.A.C. 7:13; and
G. Not exceed the impacts to frequency or depth of off-site flooding
as required by N.J.A.C. 7:13 in floodways.
Construction and elevation in A Zones:
A. All new construction and substantial improvement of any habitable building (as defined in §
200-281) located in flood hazard areas shall have the lowest floor, including basement, together with the attendant utilities (including all electrical, heating, ventilating, air-conditioning and other service equipment) and sanitary facilities, elevated to or above the local design flood elevation as determined in §
200-284, be in conformance with ASCE Chapter 7, and be confirmed by an elevation certificate.
B. All new construction and substantial improvements of nonresidential
structures shall:
(1)
Have the lowest floor, including basement, together with the attendant utilities (including all electrical, heating, ventilating, air-conditioning and other service equipment) and sanitary facilities, elevated to or above the local design flood elevation as determined in §
200-284, be in conformance with ASCE Chapter 7, and be confirmed by an elevation certificate; or
(2)
Together with the attendant utility and sanitary facilities,
be designed so that, below the local design flood elevation, the structure:
(a)
Meets the requirements of ASCE 24, Chapters 2 and 7; and
(b)
Is constructed according to the design plans and specifications
provided at permit application and signed by a licensed design professional,
is certified by that individual in a floodproofing certificate, and
is confirmed by an elevation certificate.
C. All new construction and substantial improvements with fully enclosed
areas below the lowest floor shall be used solely for parking of vehicles,
building access, or storage in an area other than a basement and which
are subject to flooding. Enclosures shall:
(1)
For habitable structures, be situated at or above the adjoining
exterior grade along at least one entire exterior wall, in order to
provide positive drainage of the enclosed area in accordance with
N.J.A.C. 7:13; enclosures (including crawlspaces and basements) which
are below grade on all sides are prohibited;
(2)
Be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters unless the structure is nonresidential and the requirements of §
200-338B(2) are met;
(3)
Be constructed to meet the requirements of ASCE 24, Chapter
2;
(4)
Have openings documented on an elevation certificate; and
(5)
Have documentation that a deed restriction has been obtained
for the lot if the enclosure is greater than six feet in height. This
deed restriction shall be recorded in the office of the County Clerk
or the Registrar of Deeds and Mortgages in which the building is located,
shall conform to the requirements in N.J.A.C. 7:13, and shall be recorded
within 90 days of receiving a Flood Hazard Area Control Act permit
or prior to the start of any site disturbance (including preconstruction
earth movement, removal of vegetation and structures, or construction
of the project), whichever is sooner. Deed restrictions must explain
and disclose that:
(a)
The enclosure is likely to be inundated by floodwaters which
may result in damage and/or inconvenience;
(b)
The depth of flooding that the enclosure would experience to
the flood hazard area design flood elevation; and
(c)
The deed restriction prohibits habitation of the enclosure and
explains that converting the enclosure into a habitable area may subject
the property owner to enforcement.
Garages and accessory storage structures shall be designed and
constructed in accordance with the Uniform Construction Code.
All manufactured homes installed in flood hazard areas shall
be installed pursuant to the Nationally Preemptive Manufactured Home
Construction and Safety Standards Program (24 CFR 3280) and shall
comply with the following requirements:
A. Elevation. All new, relocated, and replacement manufactured homes to be placed or substantially improved in a flood hazard area shall be elevated such that the bottom of the frame is elevated to or above the elevation specified in §
200-338.
B. Foundations. All new, relocated, and replacement manufactured homes,
including substantial improvement of existing manufactured homes,
shall be placed on foundations as specified by the manufacturer only
if the manufacturer's installation instructions specify that the home
has been designed for flood-resistant considerations and provides
the conditions of applicability for velocities, depths, or wave action
as required by 24 CFR Part 3285-302. The Floodplain Administrator
is authorized to determine whether the design meets or exceeds the
performance necessary based upon the proposed site location conditions
as a precondition of issuing a flood damage prevention permit. If
the Floodplain Administrator determines that the home's performance
standards will not withstand the flood loads in the proposed location,
the applicant must propose a design certified by a New Jersey licensed
design professional and in accordance with 24 CFR 3285.301(c) and
(d) which conforms with ASCE 24, the accepted standard of engineering
practice for flood-resistant design and construction.
C. Anchoring. All new, relocated, and replacement manufactured homes
to be placed or substantially improved in a flood hazard area shall
be installed using methods and practices which minimize flood damage
and shall be securely anchored to an adequately anchored foundation
system to resist flotation, collapse and lateral movement. This requirement
is in addition to applicable state and local anchoring requirements
for resisting wind forces.
D. Enclosures. Fully enclosed areas below elevated manufactured homes shall comply with the requirements of §
200-338.
E. Protection of mechanical equipment and outside appliances. Mechanical equipment and outside appliances shall be elevated to or above the elevation of the bottom of the frame required in §
200-338 of this Part
6. An exception shall be where such equipment and appliances are designed and installed to prevent water from entering or accumulating within their components and the systems are constructed to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to the elevation required by §
200-338, the systems and equipment shall be permitted to be located below that elevation. Electrical wiring systems shall be permitted below the design flood elevation provided they conform to the provisions of NFPA 70 (National Electric Code).
In accordance with Section 312 of the International Building
Code, Utility and Miscellaneous Group U includes buildings and structures
that are accessory in character and miscellaneous structures not classified
in any specific occupancy in the Building Code, including, but not
limited to, agricultural buildings, aircraft hangars (accessory to
a one- or two-family residence), barns, carports, communication equipment
structures (gross floor area less than 1,500 square feet), fences
more than six feet (1,829 mm) high, grain silos (accessory to a residential
occupancy), livestock shelters, private garages, retaining walls,
sheds, stables, tanks and towers.
A. Flood loads. Utility and miscellaneous Group U buildings and structures, including substantial improvement of such buildings and structures, shall be anchored to prevent flotation, collapse or lateral movement resulting from flood loads, including the effects of buoyancy, during conditions up to the local design flood elevation as determined in §
200-284.
B. Elevation. Utility and miscellaneous Group U buildings and structures, including substantial improvement of such buildings and structures, shall be elevated such that the lowest floor, including basement, is elevated to or above the local design flood elevation as determined in §
200-284 and in accordance with ASCE 24. Utility lines shall be designed and elevated in accordance with N.J.A.C. 7:13.
C. Enclosures below base flood elevation. Fully enclosed areas below the design flood elevation shall be constructed in accordance with §
200-338 and with ASCE 24 for new construction and substantial improvements. Existing enclosures such as a basement or crawl space having a floor that is below grade along all adjoining exterior walls shall be abandoned, filled in, and/or otherwise modified to conform with the requirements of N.J.A.C. 7:13 when the project has been determined to be a substantial improvement by the Floodplain Administrator.
D. Flood-damage-resistant materials. Flood-damage-resistant materials shall be used below the local design flood elevation determined in §
200-284.
E. Protection of mechanical, plumbing, and electrical systems. Mechanical, plumbing, and electrical systems, equipment and components, heating, ventilation, air-conditioning, plumbing fixtures, duct systems, and other service equipment shall be elevated to or above the local design flood elevation determined in §
200-284.
(1)
Exception: Electrical systems, equipment and components, and
heating, ventilating, air-conditioning, and plumbing appliances, plumbing
fixtures, duct systems, and other service equipment shall be permitted
to be located below the local design flood elevation provided that
they are designed and installed to prevent water from entering or
accumulating within the components and to resist hydrostatic and hydrodynamic
loads and stresses, including the effects of buoyancy, during the
occurrence of flooding to the local design flood elevation in compliance
with the flood-resistant construction requirements of ASCE 24. Electrical
wiring systems shall be permitted to be located below the local design
flood elevation provided they conform to the provisions of NFPA 70
(National Electric Code).