In all areas of special flood hazards the following standards
are required:
(A) Anchoring. All new construction and substantial improvements of structures,
including manufactured homes, shall be adequately anchored to prevent
flotation, collapse or lateral movement of the structure resulting
from hydrodynamic and hydrostatic loads, including the effects of
buoyancy.
(B) Construction Materials and Methods. All new construction and substantial
improvements of structures, including manufactured homes, shall be
constructed:
(1) With flood resistant materials, and utility equipment resistant to
flood damage for areas below the base flood elevation;
(2) Using methods and practices that minimize flood damage;
(3) With electrical, heating, ventilation, plumbing and air conditioning
equipment and other service facilities that are designed and/or located
so as to prevent water from entering or accumulating within the components
during conditions of flooding; and
(4) Within zones AH or AO, so that there are adequate drainage paths
around structures on slopes to guide flood waters around and away
from proposed structures.
(C) Elevation and Floodproofing.
(1) Residential Construction. All new construction or substantial improvements
of residential structures shall have the lowest floor, including basement:
(a) In AE, AH, A1-30 zones, elevated to or above the base flood elevation.
(b) In an AO zone, elevated above the highest adjacent grade to a height
to or exceeding the depth number specified in feet on the FIRM, or
elevated at least two feet above the highest adjacent grade if no
depth number is specified.
(c) In an A zone, without BFEs specified on the FIRM (unnumbered A zone), elevated to or above the base flood elevation; as determined under Section
25.38.041(C).
(d) In V zones, elevated to or above the base flood elevation adjusted to reflect sea level rise as specified in Section
25.38.041(C)(2) for the expected life of the development (minimum of seventy-five years).
Upon the completion of the structure, the elevation of the lowest
floor, including basement, shall be certified by a registered civil
engineer or licensed land surveyor, and inspected by the building
inspector to be properly elevated. Such certification and inspection
record shall be provided to the floodplain administrator.
|
(2) Nonresidential Construction. All new construction or substantial improvements of nonresidential structures shall either be elevated to conform with Section
25.38.050(C)(1) or:
(a) Be floodproofed, together with attendant utility and sanitary facilities, below the elevation recommended under Section
25.38.050(C)(1), so that the structure is watertight with walls substantially impermeable to the passage of water;
(b) Have structural components capable of resisting hydrostatic and hydrodynamic
loads and effects of buoyancy; and
(c) Be certified by a registered civil engineer or architect that the standards of Section
25.38.050(C)(2)(a) and
(b) are satisfied. Such certification shall be provided to the floodplain administrator.
(3) Flood Openings. All new construction and substantial improvements
of structures with fully enclosed areas below the lowest floor (excluding
basements) that are usable solely for parking of vehicles, building
access or storage, and that are subject to flooding, shall be designed
to automatically equalize hydrostatic flood forces on exterior walls
by allowing for the entry and exit of floodwater. Designs for meeting
this requirement must meet the following minimum criteria:
(a) For non-engineered openings:
(i)
Have a minimum of two openings on different sides having a total
net area of not less than one square inch for every square foot of
enclosed area subject to flooding,
(ii)
The bottom of all openings shall be no higher than one foot
above grade,
(iii)
Openings may be equipped with screens, louvers, valves or other
coverings or devices provided that they permit the automatic entry
and exit of floodwater, and
(iv)
Buildings with more than one enclosed area must have openings
on exterior walls for each area to allow flood water to directly enter;
or
(b) Be certified by a registered civil engineer or architect.
(5) Garages and Low Cost Accessory Structures.
(a) Attached Garages.
(i)
A garage attached to a residential structure, constructed with the garage floor slab below the BFE, must be designed to allow for the automatic entry of flood waters. See Section
25.38.050(C)(3). Areas of the garage below the BFE must be constructed with flood resistant materials. See Section
25.38.050(B).
(ii)
A garage attached to a nonresidential structure must meet the
above requirements or be dry floodproofed. For guidance on below grade
parking areas, see FEMA Technical Bulletin TB-6.
(b) Detached Garages and Accessory Structures.
(i)
"Accessory structures" used solely for parking (two-car detached garages or smaller) or limited storage (small, low-cost sheds), as defined in Section
25.38.020, may be constructed such that its floor is below the base flood elevation (BFE), provided the structure is designed and constructed in accordance with the following requirements:
A.
Use of the accessory structure must be limited to parking or
limited storage;
B.
The portions of the accessory structure located below the BFE
must be built using flood-resistant materials;
C.
The accessory structure must be adequately anchored to prevent
flotation, collapse and lateral movement;
D.
Any mechanical and utility equipment in the accessory structure
must be elevated or floodproofed to or above the BFE;
E.
The accessory structure must comply with floodplain encroachment provisions in Section
25.38.056; and
F.
The accessory structure must be designed to allow for the automatic entry of flood waters in accordance with Section
25.38.050(C)(3).
(ii)
Detached garages and accessory structures not meeting the above standards must be constructed in accordance with all applicable standards in Section
25.38.050.
(6) Crawlspace Construction. This subsection applies to buildings with
crawl spaces up to two feet below grade. Below-grade crawl space construction
in accordance with the requirements listed below will not be considered
basements.
(a) The building must be designed and adequately anchored to resist flotation,
collapse and lateral movement of the structure resulting from hydrodynamic
and hydrostatic loads, including the effects of buoyancy. Crawl space
construction is not allowed in areas with flood velocities greater
than five feet per second unless the design is reviewed by a qualified
design professional, such as a registered architect or professional
engineer;
(b) The crawl space is an enclosed area below the base flood elevation
(BFE) and, as such, must have openings that equalize hydrostatic pressures
by allowing for the automatic entry and exit of floodwaters. For guidance
on flood openings, see FEMA Technical Bulletin 1-93;
(c) Crawl space construction is not permitted in V zones. Open pile or
column foundations that withstand storm surge and wave forces are
required in V zones;
(d) Portions of the building below the BFE must be constructed with materials
resistant to flood damage. This includes not only the foundation walls
of the crawl space used to elevate the building, but also any joists,
insulation, or other materials that extend below the BFE; and
(e) Any building utility systems within the crawl space must be elevated
above BFE or designed so that floodwaters cannot enter or accumulate
within the system components during flood conditions.
(f) Requirements for all below-grade crawl space construction, in addition
to the above requirements, to include the following:
(i)
The interior grade of a crawl space below the BFE must not be
more than two feet below the lowest adjacent exterior grade (LAG),
shown as D in Figure 3 of Technical Bulletin 11-01;
(ii)
The height of the below-grade crawl space, measured from the
interior grade of the crawl space to the top of the crawl space foundation
wall must not exceed four feet (shown as L in Figure 3 of Technical
Bulletin 11-01) at any point;
(iii)
There must be an adequate drainage system that removes floodwaters
from the interior area of the crawl space within a reasonable period
of time after a flood event, not to exceed seventy-two hours; and
(iv)
The velocity of floodwaters at the site should not exceed five
feet per second for any crawl space. For velocities in excess of five
feet per second, other foundation types should be used.
(Ord. 1576 § 1, 2013)
Since floodways are an extremely hazardous area due to the velocity
of flood waters which carry debris, potential projectiles and erosion
potential, the following provisions apply:
(A) Until a regulatory floodway is adopted, no new construction, substantial
development or other development (including fill) shall be permitted
within Zones A1-30 and AE, unless it is demonstrated that the cumulative
effect of the proposed development, when combined with all other development,
will not increase the water surface elevation of the base flood more
than one foot at any point within the city of Laguna Beach.
(B) Within an adopted regulatory floodway, the city of Laguna Beach shall
prohibit encroachments, including fill, new construction, substantial
improvements and other development, unless certification by a registered
civil engineer is provided demonstrating that the proposed encroachment
shall not result in any increase in flood levels during the occurrence
of the base flood discharge.
(C) If Section
25.38.056(A) and
(B) are satisfied, all new construction, substantial improvement and other proposed new development shall comply with all other applicable flood hazard reduction provisions of Sections
25.38.050 through
25.38.057.
(Ord. 1576 § 1, 2013)
Within coastal high hazard areas, zones V, V1-30, and VE, as established under Section
25.38.031, the following standards shall apply:
(A) All new residential and non-residential construction, including substantial improvement/damage, shall be elevated on adequately anchored pilings or columns and securely anchored to such pilings or columns so that the bottom of the lowest horizontal structural member of the lowest floor (excluding the pilings or columns) is elevated to or above the base flood elevation adjusted to reflect sea level rise as specified in Section
25.38.041(C)(2) for the expected life of the development (minimum of seventy-five years). The pile or column foundation and structure attached thereto shall be anchored to resist flotation, collapse and lateral movement due to the effects of wind and water loads acting simultaneously on all building components. Water loading values used shall be those associated with the base flood and anticipated sea level rise. Wind loading values used shall be those required by applicable state or local building standards.
(B) All new construction and other development shall be located on the
landward side of the reach of mean high tide.
(C) All new construction and substantial improvement shall have the space below the lowest floor free of obstructions or constructed with breakaway walls as defined in Section
25.38.020 of this chapter. Such enclosed space shall not be used for human habitation and will be usable solely for parking of vehicles, building access or storage.
(D) Fill shall not be used for structural support of buildings or roads.
(E) Man made alteration of sand dunes that would increase potential flood
damage is prohibited.
(F) The floodplain administrator shall obtain and maintain the following
records:
(1) Certification by a registered engineer or architect that a proposed structure complies with Section
25.38.057(A); and
(2) The elevation (in relation to mean sea level) of the bottom of the
lowest horizontal structural member of the lowest floor (excluding
pilings or columns) of all new and substantially improved structures,
and whether such structures contain a basement.
(Ord. 1576 § 1, 2013)