The provisions of this division (Sections 8.04.100 through 8.04.180) shall apply to all activities for which a building permit is required by this chapter. The requirements of this division shall apply to existing buildings to the same extent as the requirements of the Uniform Building Code apply to existing buildings pursuant to Section 104 thereof, except that Sections 8.04.170(8) and 8.04.180(i)(1)8.04.180(i)(1) of this division shall apply when alterations, repairs, or additions requiring a permit occur, or when any application for a new certificate of occupancy occurs.
(Ord. 1101 § 1, 1979; Ord. 1210 § 1, 1984)
The following terms used in this division shall have the meanings indicated below:
"Approved"
means certified as meeting the requirements of this division by the enforcing authority or his authorized agents, or by other officials designated by the enforcing authority to give approval on a particular matter dealt with by the provisions of this division with regard to a given material, mode of construction, piece of equipment or device.
"Astragal"
means a molding covering the opening between the door and door jamb or adjoining door at the location of the latch.
"Auxiliary locking device"
means a secondary locking system added to the primary locking system to provide additional security.
"Bolt"
means a metal bar which, when actuated, is projected (or "thrown") either horizontally or vertically into a retaining member, such as a strike plate, to prevent a door from moving or opening.
"Bolt projection (or bolt throw)"
means the distance from the edge of the door, at the bolt centerline, to the farthest point on the bolt in the projected position, when subjected to end pressure.
"Burglary resistant glazing"
means those materials as defined in Underwriters' Laboratory Bulletin 972.
"Commercial or industrial building"
means a building, or portion thereof, used for a purpose other than dwelling.
"Component,"
as distinguished from a part, means a subassembly which combines with other components to make up a total door or window assembly. For example, the primary components of a door assembly include: door, lock, hinges, jamb/wall, jamb/strike and wall.
"Cylinder"
means the subassembly of a lock containing the cylinder core, tumbler mechanism and the keyway. A double-cylinder lock is one which has a key-actuated cylinder on both the exterior and interior of the door.
"Cylinder core" or "cylinder plug"
means the central part of a cylinder containing the keyway, which is rotated by the key to operate the lock mechanism.
"Cylinder guard"
means a hardened metal ring or plate surrounding the otherwise exposed portion of a cylinder lock to resist cutting, drilling, prying, pulling, or wrenching with common tools.
"Deadbolt"
means a lock bolt which does not have a spring action as opposed to a latch bolt, which does. The bolt must be actuated by a key and/or a knob or thumb turn, and when projected becomes locked against return by end pressure.
"Dead latch"
means a spring-actuated latch bolt having a beveled end and incorporating a plunger which, when depressed, automatically locks the projected latch bolt against return by end pressure.
"Door assembly"
means a unit composed of a group of parts or components which make up a closure for a passageway through a wall. For the purposes of this division, a door assembly consists of the following parts: doors; hinges; locking device or devices; operation contacts (such as handles, knobs, push plates); miscellaneous hardware and closures; the frame, including the head, threshold, and jambs plus the anchorage devices to the surrounding wall and a portion of the surrounding wall extending thirty-six inches from each side of the jambs and sixteen inches above the head.
"Door stops"
means the projections along the top and sides of a door jamb which check the door's swinging action.
"Double-cylinder deadbolt"
means a deadbolt which can be activated only by a key from either the interior or exterior of the building.
"Dwelling"
means a building or portion thereof designed exclusively for residential occupancy, including single-family and multiple-family dwellings.
"Enforcing authority"
means the building and safety director or his authorized representatives.
"Flushbolt"
means a manual, key or turn operated metal bolt, normally used on inactive door(s), that is attached to the top and bottom of the door and engages in the head and threshold of the frame.
"Fully tempered glazing"
means those materials meeting or exceeding ANSI Standard Z 97.1—Safety Glazing.
"Jamb"
means the vertical members of a door frame to which the door is secured.
"Jamb strike"
means that component of a door assembly which receives and holds secure the extended lock bolt; the strike and jamb used together are considered a unit.
"Jamb/wall"
means that component of a door assembly to which a door is attached and secured; the wall and jamb used together are considered a unit.
"Key-in-knob"
means a lockset having the key cylinder and other lock mechanisms contained in the knob.
"Latch" or "latch bolt"
means a beveled, spring-actuated bolt, which may or may not have a deadlocking device.
"Lock" or "lockset"
means a keyed device (complete with cylinder, latch or deadbolt mechanism, and trim such as knobs, levers, thumb turns, escutcheons, etc.) for securing a door in a closed position against forced entry.
"Locking device"
means a part of a window or sliding door assembly which is intended to prevent movement of the movable sash or door.
"Multiple-family dwelling"
means a building or portion thereof designed for occupancy by two or more families living independently of each other, including hotels, motels, apartments, duplexes and townhomes.
"Panic hardware"
means a latching device on a door assembly for use when emergency egress is required due to a fire or other threat to life safety. Such devices are designed so that they will facilitate the safe egress of people in case of an emergency when a pressure not to exceed fifteen pounds is applied to the releasing device in the direction of exit travel. Such releasing devices are bars or panels extending not less than two-thirds of the width of the door and placed at heights suitable for the service required, not less than thirty, nor more than forty-four inches above the floor.
"Part,"
as distinguished from component, means a unit (or subassembly) which combines with other units to make up a component.
"Primary locking device"
means the single locking system on a door or window unit whose function is to prevent unauthorized intrusion.
"Private dwelling" or "single-family dwelling"
means a building designed exclusively for occupancy by one family.
"Rail"
means the horizontal members of a sash frame. A meeting rail is one which mates with a rail or another sash or framing member of the window frame when the sash is in the closed position.
"Sash"
means an assembly of stiles, rails, and sometimes, muntins assembled into a single frame which supports the glazing material. A fixed sash is one which is not intended to be opened. A movable sash is in-tended to be opened.
"Sill"
means the lowest horizontal member of a window frame.
"Single-cylinder deadbolt"
means a deadbolt lock which is activated from the exterior by a key and from the interior by a knob, thumb-turn, lever or similar mechanism.
"Solid-core door"
means a door composed of solid wood or compressed wood equal in strength to solid wood construction.
"Stile"
means a vertical framing member of a window or door. A meeting stile is one which mates with a stile of another sash, or a vertical framing member of a door or window frame when the sash is in the closed position.
"Strike"
means a metal plate attached to or mortised into a door jamb to receive and to hold a projected latch bolt and/or deadbolt in order to secure the door to the jamb.
"Swinging door"
means a door hinged at the stile or at the head and threshold.
"U.L. listed"
means tested and listed by Underwriters' Laboratory, Inc.
"Window assembly"
means a unit composed of a group of parts or components which make up a closure for an opening in a wall or roof (including the anchorage) to control light, air, and other elements.
"Window frame"
means that part of a window which surrounds and supports the sashes and is attached to the surrounding wall. The members include side jambs (vertical), head jamb (upper, horizontal), sill and mullions.
(Ord. 1101 § 1, 1979)
The building and safety director or his authorized representatives are hereby empowered and directed to administer and enforce the provisions of this division relating to physical security requirements for buildings in the city. Plans and specifications for proposed construction must be approved by the building and safety director or his authorized representatives in accordance with the provisions of this division. No construction project is to be finally approved or utility release given unless the applicant for said release has satisfied the enforcing authority that applicant has complied with this division.
(Ord. 1101 § 1 (part) 1979)
It shall be unlawful for any person, firm or corporation to erect, construct, enlarge, move, improve, equip, use, occupy or maintain any building or structure in the city of Palm Springs or cause the same to be done, contrary to or in violation of any of the provisions of this division.
(Ord. 1101 § 1, 1979)
(a) 
The provisions of this division are not intended to prevent the use of any material or method of construction not specifically prescribed by this division, provided any such alternate has been approved.
(b) 
The building and safety director may approve any such alternate, provided he finds that the proposed design is satisfactory and complies with the provisions of this division and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this division in quality, strength, effectiveness, crime resistance, durability and safety.
(c) 
The building and safety director shall require that sufficient evidence or proof be submitted to substantiate any claims that may be made regarding its use.
(Ord. 1101 § 1, 1979)
Upon occupancy by the owner or proprietor, each single unit in a tract or commercial development, constructed under the same general plan, shall have locks using combinations which are interchange free from locks used in all other separate dwellings, proprietorships or similar distinct occupancies within such tract or commercial development. Every applicant shall be required to provide the enforcing authority with written confirmation of compliance with the above requirements.
(Ord. 1101 § 1, 1979)
(a) 
The above described doors shall conform to the following standards:
(1) 
Wood doors shall have panels a minimum of five sixteenths inch in thickness with the locking hardware being attached to the support framing.
(2) 
Aluminum doors shall be a minimum thickness of .0215 inches and riveted together a minimum of eighteen inches on center along the outside seams. There shall be a full-width horizontal beam attached to the main door structure which shall meet the pilot, or pedestrian access, door framing within three inches of the strike area of the pilot or pedestrian access door.
(3) 
Fiberglass doors shall have panels a minimum density of six ounces per square foot from the bottom of the door to a height of seven feet. Panels above seven feet and panels in residential structures shall have a density of not less than five ounces per square foot.
(b) 
Where sliding or accordion doors are utilized, they shall be equipped with guide tracks which shall be designed so that the door cannot be removed from the track when in the closed and locked position.
(c) 
Doors that exceed sixteen feet in width shall have two lock receiving points; or, if the door does not exceed nine-teen feet, a single bolt may be used if placed in the center of the door with the locking point located either in the floor or door frame header.
(d) 
Overhead doors shall be equipped with slide bolts which shall be capable of utilizing padlocks with a minimum nine thirty-seconds inch shackle.
(1) 
Slide bolt assemblies shall have a frame a minimum of .120 inches in thickness, a bolt diameter a minimum of one-half inch and protrude at least one and one-half inches into the receiving guide. A bolt diameter of three-eights inch may be used in a residential building.
(2) 
Slide bolt assemblies shall be attached to the door with bolts which are nonremovable from the exterior. Rivets shall not be used to attach such assemblies.
(e) 
Padlocks used with exterior-mounted slide bolts shall have a hardened steel shackle a minimum of nine thirty-seconds inch in diameter with heel-and-toe locking and a minimum five-pin tumbler operation. The key shall be non-removable when in an unlocked position.
(f) 
Doors utilizing a cylinder lock shall have a minimum five-pin tumbler operation with the bolt or locking bar ex-tending into the receiving guide a minimum of one inch.
(Ord. 1101 § 1, 1979)
The following requirements must be met for windows and sliding glass doors:
(1) 
Except as otherwise specified in Section 3.04.170 (special residential building provisions) and Section 8.04.180 (special commercial building provisions), all openable exterior windows and sliding glass doors shall comply with the tests as set forth in Uniform Building Code Standard 41-2. Other doors and locking devices shall conform to tests as set forth in Uniform Building Code Standard 41-1.
(2) 
Louvered windows shall not be used when any portion of the window is less than twelve feet vertically or six feet horizontally from an accessible or any adjoining roof, balcony, landing, stair tread, platform or similar structure.
(Ord. 1101 § 1, 1979)
The following special provisions shall apply to all residential dwellings:
(1) 
(A) 
Exterior swinging doors and swinging doors leading from the garage into living space shall be equipped with a double or single-cylinder deadbolt having a minimum projection of one inch and an embedment of at least three-fourths inch into the strike receiving the bolt. The door jamb receiving the bolt shall be securely fastened directly to 2X material. The bolt shall be constructed so as to resist cutting tool attacks. The cylinder shall have a cylinder guard, a minimum of five-pin tumblers, and shall be connected to the inner portion of the lock by connecting screws of at least one-fourth inch diameter.
(B) 
The provisions of this subsection do not apply where panic hardware is required or an equivalent device is approved by the enforcing authority. Further, a dual locking mechanism, constructed so that both the deadbolt and latch can be retracted by a single action of the inside door knob or lever, may be substituted provided it meets all other specifications for locking devices.
(2) 
The inactive leaf of double doors shall be equipped with flush bolts having a minimum embedment of five-eighths inch into the head and threshold of the door frame.
(3) 
Glazing in exterior doors or within forty inches of a door-locking mechanism shall be of fully tempered glass or rated burglary resistant glazing, except where double-cylinder deadbolts are installed.
(4) 
Hinges for outswinging exterior doors shall be equipped with nonremovable hinge pins or a mechanical interlock to preclude removal of the door from the exterior by removing the hinge pins.
(5) 
Strikeplates shall be a minimum of three and one-half inches in length and secured to the jamb with screws a minimum of two and one-half inches in length.
(6) 
All front exterior doors shall be equipped with a wide-angle (one-hundred-eighty-degree) door viewer, except where clear vision panels are installed.
(7) 
Where panic hardware is required by the Uniform Building Code or Title 19, California Administrative Code, it shall be equipped and installed as follows:
(A) 
Panic hardware shall contain a minimum of two locking points on each door; or
(B) 
On single doors, panic hardware may have one locking point which is not to be located at either the top or bottom rails of the door frame. The door shall have an astragal constructed of steel .125 inches thick which shall be attached with nonremovable bolts or welded to the outside of the door. The astragal shall extend a minimum of six inches vertically above and below the latch of the panic hardware. The astragal shall be a minimum of two inches wide and extend a minimum of one inch beyond the edge of the door;
(C) 
Double doors containing panic hardware shall have an astragal attached to the doors as their meeting point which will close the opening between them but not interfere with the operation of either door.
(8) 
The following provisions for address markings shall apply to residential dwellings:
(A) 
All residential structures shall display a street number in a prominent position so that it shall be easily visible from the street. The numerals in these numbers shall be no less than four inches in height, of a color contrasting to the background, and located so they may be clearly seen and read.
(B) 
At each driveway entrance to a multiple-family dwelling complex having four or more buildings, there shall be an illuminated diagramatic representation (plot plan) of the complex which shows the location of the viewer and the building units within the complex.
(C) 
In multiple-family dwelling complexes, any building having a separate identifying factor other than the street number shall be clearly identified in the manner described in this subsection (8), infra. Each individual unit of residence shall have a unit identifying number, letter or combination thereof displayed upon the door.
(D) 
Buildings shall be numbered in such a manner and sequence to meet with the approval of the enforcing authority.
(E) 
This section shall not prevent supplementary numbering, such as reflective numbers on street curbs or decorative numbering, but this shall be considered supplemental only and shall not satisfy the requirements of this section.
(F) 
Eight and one-half inch by eleven inch maps of the complex shall be furnished to the police and fire departments prior to completion of construction. The maps shall include building identification and unit identification.
(9) 
All exterior doors shall be equipped with a lighting device capable of providing at least one footcandle of light at the ground level during hours of darkness. Lighting devices shall be protected by vandal-resistant covers.
(10) 
Aisles and passageways within multiple-family dwelling complexes shall be equipped with lighting devices capable of providing at least .25 footcandles of light at ground level during hours of darkness. Lighting devices shall be protected by vandal-resistant covers.
(11) 
Open parking lots and carports of multiple-family dwelling complexes shall be equipped with lighting devices capable of providing at least one footcandle of light on the parking surface during hours of darkness. Lighting devices shall be protected by vandal-resistant covers.
(12) 
Bars, grilles, grates or similar devices may be installed on an emergency escape or rescue windows or doors, provided:
(A) 
Such devices for windows are equipped with approved release mechanisms which are openable from the inside without the use of a key or special knowledge or effort; and
(B) 
Such devices for doors are equipped with approved release mechanisms which are openable from the inside without the use of key or special knowledge or effort. Keys may be utilized if they are readily accessible and permanently mounted within four feet of the door; and
(C) 
The building is equipped with smoke detectors installed per the Uniform Building Code.
(Ord. 1101 § 1, 1979; Ord. 1174 § 1, 1983)
(a) 
Swinging exterior glass doors, wood or metal doors with glass panels, solid wood or metal doors shall be constructed or protected as follows:
(1) 
Wood doors shall be of solid-core construction with a minimum thickness of one and three-fourths inches. Hollow metal doors shall be constructed of a minimum equivalent to sixteen U.S. gauge steel, and have sufficient reinforcement to maintain the designed thickness of the door when any locking device is installed, such reinforcement being able to restrict collapsing of the door around the locking device.
(2) 
Except when double-cylinder deadbolts are utilized, any glazing utilized within forty inches of any doorlocking mechanism shall be constructed or protected as follows:
(A) 
Fully tempered glass or rated burglary resistant glazing; or
(B) 
Iron or steel grills of at least one-eighth inch metal with a maximum two inch mesh secured on the inside of the glazing may be utilized; or
(C) 
The glazing shall be covered with iron or steel bars of at least one-half inch round or one inch by one-fourth (1" x ¼") flat metal, spaced not more than five inches apart and secured on the inside of the glazing.
(D) 
Items (B) and (C) above shall not interfere with the operation of opening windows if such windows are required to be openable by the Uniform Building Code.
(b) 
All swinging exterior wood and steel doors shall be equipped as follows:
(1) 
A single or double door shall be equipped with a double or single cylinder deadbolt. The bolt shall have a minimum projection of one inch and be constructed so as to repel cutting-tool attack. The deadbolt shall have an embedment of at least three-fourths inch into the strike receiving the projected bolt. The cylinder shall have a cylinder guard, a minimum of five pin tumblers, and shall be connected to the inner portion of the lock by connecting screws of at least one-fourth inch in diameter. The provisions of this subsection do not apply where:
(A) 
Panic hardware is required, or
(B) 
An equivalent device is approved by the enforcing authority.
(2) 
Double doors shall be equipped as follows:
(A) 
The inactive leaf of double door(s) shall be equipped with metal flush bolts having a minimum embedment of five-eighths inch into the head and threshold of the door frame.
(B) 
Double doors shall have an astragal constructed of steel a minimum of .125 inch thick which will cover the opening between the doors. The astragal shall be a minimum of two inches wide, and ex-tend a minimum of one inch beyond the edge of the door to which it is attached. The astragal shall be attached to the outside of the active door by means of welding or with nonremovable bolts spaced apart on not more than ten-inch centers.
(3) 
Hinges for outswinging doors shall be equipped with nonremoval hinge pins or a mechanical interlock to preclude removal of the door from the exterior by removing the hinge pins.
(4) 
Strikeplates shall be a minimum of three and one-half inches in length and secured to the jamb with screws a minimum of two and one-half inches in length.
(c) 
Aluminum-frame swinging doors shall conform to the following:
(1) 
The jamb on all aluminum-frame swinging doors shall be so constructed or protected to withstand sixteen hundred pounds of pressure in both a vertical distance of three inches and a horizontal distance of one inch each side of the strike, so as to prevent violation of the strike.
(2) 
Aluminum-frame swinging doors shall be equipped with a deadbolt having a minimum bolt projection of one and one-half inches, or a hook shaped or similar bolt that engages the strike sufficiently to prevent spreading. The deadbolt lock shall have a minimum of five pin tumblers and a cylinder guard.
(d) 
Panic hardware, whenever required by the Uniform Building Code or Title 19, California Administrative Code, shall be equipped and installed as follows:
(1) 
Panic hardware shall contain a minimum of two locking points on each door; or
(2) 
On single doors, panic hardware may have one locking point, which is not to be located at either the top or bottom rails of the door frame. The door shall have an astragal constructed of steel .125 inches thick, which shall be attached with nonremovable bolts to the outside of the door. The astragal shall extend a minimum of six inches vertically above and below the latch of the panic hardware. The astragal shall be a minimum of two inches wide and extend a minimum of one inch beyond the edge of the door to which it is attached.
(3) 
Double doors containing panic hardware shall have an astragal attached to the doors at their meeting point which will close the opening between them, but not interfere with the operation of either door.
(e) 
In multiple-occupancy office buildings, all entrance doors to individual office suites shall meet the construction and locking requirements for exterior doors.
(f) 
Exterior transoms or windows shall be deemed accessible if less than twelve feet above ground or adjacent to any pedestrian walkway. Accessible windows and transoms having a pane or opening exceeding ninety-six square inches, with the smallest dimension exceeding six inches, and not visible from a public or private thoroughfare shall be protected in the following manner:
(1) 
Fully tempered glass or burglary resistant glazing; or
(2) 
The following window barriers may be used but shall be secured with bolts which are nonremovable from the exterior:
(A) 
Interior or exterior steel or iron bars of at least one-half inch round or one by one-quarter (1" x ¼") inch flat metal spaced not more than five inches apart and securely fastened; or
(B) 
Interior or exterior iron or steel grills of at least one-eighth inch metal with not more than a two-inch mesh and securely fastened.
(3) 
The protective bars or grills shall not interfere with the operation of opening windows if such windows are required to be openable by the Uniform Building Code.
(g) 
Roof openings shall be equipped as follows:
(1) 
All skylights on the roof of any building or premises used for business purposes shall be provided with:
(A) 
Rated burglary resistant glazing; or
(B) 
Iron or steel bars of at least one-half inch round or one by one-fourth (1" x ¼") inch flat metal, mounted inside the skylight and secured by bolts which are nonremovable from the exterior; or
(C) 
A steel or iron grill of at least one-eighth inch metal with a maximum two-inch mesh, mounted inside the skylight and secured by bolts which are nonremovable from the exterior.
(2) 
All hatchway openings on the roof of any building or premises used for business purposes shall be secured as follows:
(A) 
If the hatchway is of wooden material, it shall be covered on the inside with at least sixteen U.S. gauge sheet steel, or its equivalent, attached with screws.
(B) 
The hatchway shall be secured from the inside with a slide bar or slide bolts.
(C) 
Outside hinges on all hatchway openings shall be provided with nonremovable pins when using pin-type hinges.
(3) 
All air duct or air vent openings exceeding ninety-six square inches on the roof or exterior walls of any commercial building shall be secured by covering same with either of the following:
(A) 
Iron or steel bars of at least one-half inch round or one by one-fourth (1" x ¼") inch flat metal, spaced no more than five inches apart and securely fastened; or
(B) 
Iron or steel grills of at least one-eighth inch metal with a maximum two-inch mesh and securely fas-tened.
(C) 
If the barrier is on the outside, it shall be secured with bolts which are nonremovable from the exteri-or.
(D) 
The above must not interfere with venting requirements, creating a potentially hazardous condition to health and safety, or conflict with the provisions of the Uniform Building Code or Title 19, California Administrative Code.
(h) 
Readily accessible, permanently affixed ladders leading to roofs shall be fully enclosed with sheet metal to a height of ten feet. This covering shall be locked against the ladder with a case-hardened hasp, secured with nonremovable screws or bolts. Hinges on the cover will be provided with nonremovable pins when using pin-type hinges. If a padlock is used, it shall have a hardened-steel shackle, locking at both heel and toe, and a minimum five-pin tumbler operation with nonremovable key when in an unlocked position.
(i) 
The following standards for lighting and address markings shall apply to commercial buildings:
(1) 
The address number of every commercial building shall be located and displayed so that it shall be easily visible from the street. The numerals in these numbers shall be no less than six inches in height and be of a color contrasting to the background. In addition, any business which affords vehicular access to the rear through any driveway, alleyway or parking lot shall also display the same numbers on the rear of the building.
(2) 
All exterior doors to commercial buildings shall be equipped with a lighting device capable of providing a minimum of one footcandle of light. All exterior bulbs shall be protected by weather and vandalism resistant covers.
(3) 
Open parking lots, and access thereto, providing more than ten parking spaces and for use by the general public, shall be provided with a maintained minimum of one footcandle of light on the parking surface from dusk until the termination of business every operating day.
(j) 
Establishments having specific-type inventories shall be protected by the following type alarm service:
(1) 
Silent alarm system with a central station hookup and required twenty-four-hour supervised service:
(A) 
Jewelry store—manufacturing, wholesale, or retail,
(B) 
Any establishment manufacturing, storing or selling firearms and ammunition,
(C) 
Establishments selling or storing wholesale liquor, tobacco or drugs,
(D) 
Facilities selling or storing furs,
(E) 
Precious-metal storage facilities,
(F) 
Banks, savings and loan institutions, and credit unions;
(2) 
Silent alarm system not requiring a central station hookup or supervised service:
(A) 
Liquor stores,
(B) 
Pawnshops,
(C) 
Establishments manufacturing, storing or selling electronic equipment,
(D) 
Establishments dealing in coins and stamps,
(E) 
Establishments manufacturing, storing or selling industrial tool supplies,
(F) 
Establishments manufacturing, storing or selling cameras;
(3) 
Local or audible alarm system:
(A) 
Antique dealers,
(B) 
Art galleries,
(C) 
Service stations,
(D) 
Food markets.
(4) 
Nothing in this subsection shall preclude the use of an alarm system providing a higher level of security than that which is required.
(Ord. 1101 § 1, 1979)
(a) 
Whenever access into private property, other than an individual single-family residence and similar small projects, is controlled through use of gates, barriers, guard houses or other similar means, provision shall be made to facilitate access by emergency vehicles in a manner approved by the chief of police. All controlled access devices that are power operated shall have a radio-controlled override system capable of opening the gate or barrier when activated by a special transmitter located in emergency vehicles. Devices shall be equipped to facilitate opening in the event of a power failure. All controlled access devices that are not power operated shall be approved by the chief of police.
(b) 
The provisions of this section shall apply to all primary entryways into private developments, and to such other entry ways as may be designated by the chief of police.
(c) 
Properties which do not meet the requirements of this section shall be brought into conformance therewith within six months after the ordinance codified in this section is in full force and effect.
(d) 
The provisions of this section shall be in addition to, and not in lieu of, the provisions Chapter 11.02 of this code and the Uniform Fire Code as adopted thereby.
(e) 
Any person, except those authorized to install or repair, who tampers with, alters, removes or otherwise renders inoperable any device required by this section shall be guilty of a misdemeanor.
(Ord. 1274 § 1, 1986)