[Ord. No. 8748, 11-22-2021; Ord. No. 8875, 3-27-2023]
The International Residential Code, 2021 Edition, including Appendixes AA, AB, AC, AD, AE, AG, AH, AJ and AK as published by the International Code Council, Inc., one (1) copy of which was on file in the office of the City Clerk for a period of ninety (90) days prior to the adoption of this Article and available for public use, inspection and examination, and a copy of which is attached hereto and incorporated by this reference as if fully set forth herein, is hereby adopted as the Residential Code of the City of Florissant, Missouri, subject to the amendments, additions, insertions, deletions and changes set out in Section
500.070 of this Chapter.
[Ord. No. 8748, 11-22-2021; Ord. No. 8875, 3-27-2023]
A. The following numbered Sections and Subsections of the International
Residential Code, 2021 Edition, including Appendixes AA, AB, AC, AD,
AE, AG, AH, AJ and AK as published by the International Code Council,
Inc., are hereby amended by additions, insertions, deletions and amendments
so that such Sections and Subsections shall read as follows:
1.
Section R101.1 Title. (Amended) These provisions
shall be known as the Residential Code for One- and Two-Family Dwellings
of the City of Florissant and shall be cited as such and will be referred
to herein as "this code."
2.
Section R105.2 Work exempt from permit. (Amended)
Exemption from permit requirements of this code shall not be deemed
to grand authorization for any work to be done in any manner in violation
of the provisions of this code or any other laws or ordinances of
this jurisdiction. Permits shall not be required for the following:
Building:
|
1.
|
(Deleted)
|
2.
|
(Amended) Fence repairs if total linear feet of repair is twenty-five
percent (25%) or less than the total cumulative fence length on the
parcel.
|
3.
|
(Amended) Retaining walls that are not over two (2) feet in
height measured from the bottom of the footing to the top of the wall,
unless supporting a surcharge load.
|
4.
|
(Unchanged from code text)
|
5.
|
(Amended) Sidewalks and driveways not more than thirty (30)
inches above grade and not over any basement or story above. However,
any excavation in a public right-of-way requires an approval and/or
excavation permit from the City of Florissant.
|
6.
|
(Amended) Painting, papering, tiling, carpeting, cabinets, countertops
and similar finish work, unless it interferes with another required
system, component, safety condition or requirement.
|
7.
|
(Amended) Swimming pools that are less than twenty-four (24)
inches deep. (See International Swimming Pool and Spa Code as adopted.)
|
8.
|
(Amended) Swings, playground equipment and other recreational
structures or equipment accessory to detached one- and two-family
dwellings.
|
9.
|
(Unchanged from code text)
|
10.
|
(Deleted)
|
11.
|
(Added) Removal and installation of exterior coverings provided
the work does not interfere with other required systems or components.
All newly installed exterior coverings and roofing materials must
match the existing in appearance and color, texture and profile so
as not to promote visual blight and shall be constructed in a workmanlike
manner.
|
Electrical:
|
1.
|
(Unchanged from code text)
|
2.
|
(Unchanged from code text)
|
3.
|
(Unchanged from code text)
|
4.
|
(Unchanged from code text)
|
5.
|
(Unchanged from code text)
|
Gas:
|
1.
|
(Unchanged from code text)
|
2.
|
(Unchanged from code text)
|
3.
|
(Unchanged from code text)
|
Mechanical:
|
1.
|
(Unchanged from code text)
|
2.
|
(Unchanged from code text)
|
3.
|
(Unchanged from code text)
|
4.
|
(Unchanged from code text)
|
5.
|
(Unchanged from code text)
|
6.
|
(Unchanged from code text)
|
7.
|
(Unchanged from code text)
|
8.
|
(Unchanged from code text)
|
Plumbing:
|
1.
|
(Unchanged from code text)
|
2.
|
(Unchanged from code text)
|
3.
|
(Added) Installation of fixtures if water supply valve does
not fall within the scope of work.
|
4.
|
(Added) Installation, modification or replacement of under sink
tailpiece, trap or drain if not concealed behind finished surfaces.
|
3.
Section R105.2.1 Emergency repairs. (Amended) Where
equipment or system replacements and/or repairs must be performed
in an emergency situation, the permit application shall be submitted
within the next two (2) business days to the Building Official.
4.
Section R105.3.3 Integrated permits. (Added) The
Code Official shall be permitted to issue integrated building, plumbing,
electrical and/or mechanical permits on a single permit application.
The integrated permit primary applicant shall be responsible for providing
the Department of Public Works copies of the plumbing, electrical
and/or mechanical permit form with the name, signature and license
number of the appropriate subcontractor. Any change in the identity
of the named subcontractor after issuance of the permit shall result
in the assessment of a transfer or revision fee in the amount specified
in this Code.
5.
Section R105.7 Placement of permit. (Amended) The
building permit authorization card and stamped approved plans shall
be kept on the construction site until completion of the work. The
authorization card shall be placed in a window visible from the street
upon which the structure or structures face or located on the exterior
of the structure facing the street in a clear waterproof container.
6.
Section R106.3.1 Approval of construction documents. (Amended) Where the Building Official issues a permit, the construction
documents shall be approved in writing or by a stamp that states "REVIEWED
FOR CODE COMPLIANCE." One (1) set of construction documents so reviewed
shall be retained by the Building Official. The other set shall be
returned to the applicant, may be kept at the site of work or made
available at the time of inspection and shall be open to inspection
by the Building Official or a duly authorized representative.
7.
Section R108.6 Work commencing before permit issuance. (Amended) Any person who commences work requiring a permit on a
building, structure, electrical, gas, mechanical or plumbing system
before obtaining the necessary permits shall be subject to a fee established
by the applicable governing authority that shall be in addition to
the required permit fees.
Exceptions:
|
1.
|
Earthwork
|
2.
|
Stakeouts and other necessary planning procedures
|
8.
Section R112.1 General. (Deleted and replaced) In order to hear and decide appeals of orders, decisions, or determinations made by the Building Official relative to the application and interpretation of this code, The Board of Appeals shall be the Planning and Zoning Commission as established by the Code of Ordinances of the City of Florissant in Section
11.1 of the City Charter. The Building Official shall be an ex officio member of the board when hearing building code appeals but shall not have a vote on any matter before the board.
9.
Section R113.4 Violation penalties. (Amended) Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the building g official, or of a permit or certificate issued under the provisions of this code, shall be subject to the penalties of Section
100.080 of the Code of Ordinances of the City of Florissant. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
10.
Section R113.5 Method of service. (Added) Such
notice shall be deemed to be properly served upon the owner, owner's
agent or upon the person responsible for the structure if a copy thereof
is:
1.
Delivered personally by leaving the notice with a responsible
party of suitable age and discretion.
2.
Delivered by regular mail, certified mail, first class mail,
registered mail, courier service, UPS, FedEx, Amazon, or any similar
service with delivery confirmation, to the most recent known address
or the mailing address according to the real estate property records
of St. Louis County, Missouri.
3.
A copy thereof may be posted in a conspicuous place in or about
the structure affected by such notice.
11.
Section 202 definitions, story above grade plane. (Amended) Any story having its finished floor surface entirely above
grade plane, or in which the finished surface of the floor next above
is:
1.
More than six (6) feet (1,829 mm) above grade plane; and
2.
More than six (6) feet (1,829 mm) above the finished ground
level for more than fifty percent (50%) of the total building perimeter;
and
3.
More than twelve (12) feet (3,658 mm) above the finished ground
level at any point.
12.
Table R301.2 CLIMACTIC AND GEOGRAPHIC DESIGN CRITERIA. (Amended)
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour
= 0.447 m/s.
|
a.
|
Where weathering requires a higher strength concrete or grade
of masonry than necessary to satisfy the structural requirements of
this code, the frost line depth strength required for weathering shall
govern. The weathering column shall be filled in with the weathering
index, "negligible," "moderate" or "severe" for concrete as determined
from Figure R301.2(1). The grade of masonry units shall be determined
from ASTM C34, ASTM C55, ASTM C62, ASTM C73, ASTM C90; ASTM C129,
ASTM C145, ASTM C216 or ASTM C652.
|
b.
|
Where the frost line depth requires deeper footings than indicated
in Figure R403.1(1), the frost line depth strength required for weathering
shall govern. The jurisdiction shall fill in the frost line depth
column with thirty (30), the minimum depth of footing below finish
grade.
|
c.
|
The jurisdiction shall fill in this part of the table to indicate
the need for protection depending on whether there has been a history
of local subterranean termite damage.
|
d.
|
The jurisdiction shall fill in this part of the table with the
wind speed from the basic wind speed map [Figure R301.2(2)]. Wind
exposure category shall be determined on a site-specific basis in
accordance with Section R301.2.1.4.
|
e.
|
The jurisdiction shall fill in this part of the table to establish
the design criteria using Table 10A from ACCA Manual J or established
criteria determined by the jurisdiction.
|
f.
|
The jurisdiction shall fill in this part of the table with the
seismic design category determined from Section R301.2.2.1.
|
g.
|
The jurisdiction shall fill in this part of the table with:
the date of the jurisdiction's entry into the National Flood
Insurance Program (date of adoption of the first code or ordinance
for management of flood hazard areas); and the title and date of the
currently effective Flood Insurance Study or other flood hazard study.
|
h.
|
The jurisdiction shall fill in this part of the table with "NO."
|
i.
|
The jurisdiction shall fill in this part of the table with the
100-year return period air freezing index (BF-days) from Figure R403.3(2)
or from the 100-year (99%) value on the National Climatic Data Center
data table "Air Freezing Index — USA Method (Base 32° F.)."
|
j.
|
The jurisdiction shall fill in this part of the table with the
mean annual temperature from the National Climatic Data Center data
table "Air Freezing Index — USA Method (Base 32° F.)."
|
k.
|
In accordance with Section R301.2.1.5, where there is local
historical data documenting structural damage to buildings due to
topographic wind speed-up effects, the jurisdiction shall fill in
this part of the table with "YES." Otherwise, the jurisdiction shall
indicate "NO" in this part of the table.
|
l.
|
In accordance with Figure R301.2(2), where there is local historical
data documenting unusual wind conditions, the jurisdiction shall fill
in this part of the table with "YES" and identify any specific requirements.
Otherwise, the jurisdiction shall indicate "NO" in this part of the
table.
|
m.
|
In accordance with Section R301.2.1.2, the jurisdiction shall
indicate the wind-borne debris wind zone(s). Otherwise the jurisdiction
shall indicate "NO" in this part of the table.
|
n.
|
The jurisdiction shall fill in these sections of the table to
establish the design criteria using Table 1a or 1b from ACCA Manual
J or established criteria determined by the jurisdiction.
|
o.
|
The jurisdiction shall fill in this Section of the table using
the Ground Snow Loads in Figure R301.2(3) and R301.2(4).
|
13.
Section R302.1 Exterior walls. (Amended) Construction,
projections, openings and penetrations of exterior walls of dwellings
and accessory buildings shall comply with Table R302.1(1) as amended;
or dwellings equipped throughout with an automatic sprinkler system
installed in accordance with Section P2904 shall comply with Table
R302.1(2).
Exceptions:
1.
Walls, projections, openings or penetrations in walls perpendicular
to the line used to determine the fire separation distance.
2.
Walls of individual dwelling units and their accessory structures
located on the same lot.
3.
Detached tool sheds and storage sheds, playhouses and similar
structures exempted from permits are not required to provide wall
protection based on location on the lot. Projections beyond the exterior
wall shall not extend over the lot line.
4.
Detached garages accessory to a dwelling located within two
(2) feet (610 mm) of a lot line are permitted to have roof eave projections
not exceeding four (4) inches (102 mm).
5.
Foundation vents installed in compliance with this code are
permitted.
6.
Cantilevered manufactured fireplaces.
14.
Section R302.5.1 Opening protection. (Amended)
Openings from a private garage directly into a room used for sleeping
purposes shall not be permitted. Other openings between the garage
and residence shall be equipped with solid wood doors not less than
one and three eighths (1 3/8) inches (35 mm) in thickness, solid
or honeycomb-core steel doors not less than one and three eighths
(1 3/8) inches (35 mm) thick, or 20-minute fire-rated doors and
door shall be self-latching.
15.
Section R302.5.2 Duct penetration. (Amended) Ducts
in the garage and ducts penetrating the walls or ceilings separating
the dwelling from the garage shall be constructed of a minimum No.
28 gage (0.378 mm) sheet steel or other approved material and shall
not have openings into the garage.
16.
Section R302.13 Fire protection of floors. (Amended)
Floor assemblies that are not required elsewhere in this code to be
fire-resistance rated, shall be provided with a one-half-inch (12.7
mm) gypsum wallboard membrane, five-eighth-inch (16 mm) wood structural
panel membrane, or equivalent on the underside of the floor framing
member. Penetrations or openings for ducts, vents, electrical outlets,
lighting, devices, luminaires, wires, speakers, drainage, piping and
similar openings or penetrations shall be permitted. Fire blocking,
draft stopping, fire taping, and/or additional framing is not required.
Exceptions:
|
1.
|
Floor assemblies located directly over a space protected by
an automatic sprinkler system in accordance with Section P2904, NFPA
13D, or other approved equivalent sprinkler system.
|
2.
|
Floor assemblies located directly over a crawl space not intended
for storage or for the installation of fuel-fired or electric-powered
heating appliances.
|
3.
|
Portions of floor assemblies shall be permitted to be unprotected
where complying with the following:
|
|
3.1.
|
The aggregate area of the unprotected floor assembly does not
exceed one hundred (100) square feet per HVAC zone.
|
|
3.2.
|
Areas of the floor assembly covered by HVAC metal plenum, trunk
lines, and steel structural beams shall be considered protected. Gypsum
wallboard membrane shall be within two (2) inches of all previously
listed items.
|
4.
|
Wood floor assemblies using dimension lumber or structural composite
lumber equal to or greater than two-inch by ten-inch (50.8 mm by 254
mm) nominal dimension, or other approved floor assemblies demonstrating
equivalent fire performance.
|
17.
Section R303.5.2 Exhaust openings. (Amended) Exhaust
air shall not be directed below six (6) feet and eight (8) inches
onto public walkways.
18.
Section R309.5 Fire sprinklers. (Amended) Private
garages shall be protected by fire sprinklers where the garage wall
has been designed based on Table 302.1(2), Note a., and the homeowner
has opted to purchase a fire sprinkler system for their residence,
as per Section 67.281, RSMo. Sprinklers in garages shall be connected
to an automatic sprinkler system that complies with Section P2904.
Garage sprinklers shall be residential sprinklers or quick-response
sprinklers, designed to provide a density of 0.05 gpm/ft2. Garage doors shall not be considered obstructions
with respect to sprinkler placement.
19.
Section R311.3 Floors and landings at exterior doors. (Amended) There shall be a landing or floor at each required egress
exterior door. The width of each landing shall not be less than the
door served. Landings shall have a dimension of not less than thirty-six
(36) inches (914 mm) measured in the direction of travel. The slope
at exterior landings shall not exceed 1/4 unit vertical in twelve
(12) units horizontal two percent (2%).
Exception: Exterior balconies less than sixty (60)
square feet (5.6 m2) and only accessed
from a door are permitted to have a landing that is less than thirty-six
(36) inches (914 mm) measured in the direction of travel.
20.
Section R311.3.2 Floor elevations at other exterior doors. (Amended) Doors other than the required egress door shall be provided
with landings or floors not more than 7 3/4 inches (196 mm) below
the top of the threshold.
Exception: A top landing is not required where
a stairway of four (4) or fewer risers is located on the exterior
side of the door, provided that door does not swing over the stairway.
21.
Section R311.7.5.2 Treads. (Amended) The tread
depth shall be not less than ten (10) inches (254 mm). The tread depth
shall be measured horizontally between the vertical planes of the
foremost projection of adjacent treads and at a right angle to the
tread's leading edge. The greatest tread depth within any flight
of stairs shall not exceed the smallest by more than three eighths
(3/8) inch (9.5 mm).
Exceptions:
1.
For remodeling projects, such as in existing homes, homes in
urban, infill or high-density developments, or historical buildings
or dwellings, riser height of not more than eight and one-fourhts
(8 1/4) inches (210 mm) and tread depth of not more than nine
(9) inches (229 mm) will be allowed.
2.
For remodeling projects in existing homes, stair tread and riser
will be allowed to mimic previous or existing conditions.
22.
Section R312.1.1 Where required. (Amended) Guards
shall be provided for those portions of open-sided walking surfaces,
including floors, stairs, ramps and landings that are located more
than thirty (30) inches (762 mm) measured vertically to the floor
or grade below. Insect screening shall not be considered as a guard.
23.
Section R312.1.5 Retaining wall protection (Added).
Guards shall be provided where retaining walls with differences in
grade level on either side of the wall in excess of thirty (30) inches
are located closer than two (2) feet to a walk, path, parking lot
or driveway on the high side of the retaining wall.
24.
Section R312.2 Window fall protection. (Deleted)
25.
Section R313.1 Townhouse automatic fire sprinkler systems. (Amended) An automatic sprinkler system shall be installed in townhouses,
in accordance with Section 67.281 RSMo.
Exception: An automatic sprinkler system shall
not be required where additions or alterations are made to existing
townhouses that do not have an automatic sprinkler system installed.
26.
Section R313.2 One- and two-family dwellings automatic
sprinkler systems. (Amended) A builder of a single-family dwelling
or residence or multi-unit dwellings of four (4) or fewer units shall
offer to any purchaser on or before the time of entering into the
purchase contract the option, at the purchaser's cost, to install
or equip fire sprinklers in the dwelling, residence, or unit. Notwithstanding
any other provision of law to the contrary, no purchaser of such a
single-family dwelling, residence, or multi-unit dwelling shall be
denied the right to choose or decline to install a fire sprinkler
system in such dwelling or residence being purchased by any code,
ordinance, rule, regulation, order, or resolution by any County or
other political subdivision. Any County or other political subdivision
shall provide in any such code, ordinance, rule, regulation, order,
or resolution the mandatory option for purchasers to have the right
to choose and the requirement that builders offer to purchasers the
option to purchase fire sprinklers in connection with the purchase
of any single-family dwelling, residence, or multi-unit dwelling of
four (4) or fewer units.
Exception: An automatic sprinkler system shall
not be required for additions or alterations to existing buildings
that are not already provided with a sprinkler system.
27.
Section R313.2 One- and two-family dwellings automatic
fire systems (Amended). Any builder of single-family dwellings
or residences or multi-family dwellings of four (4) or fewer units
shall offer, in writing, to any purchaser the option to install or
equip such dwellings or residences with a fire sprinkler system at
the purchaser's cost in accord with the requirements of State
of Missouri law, Section 67.281, RSMo., Supp. 2009.
28.
Section R323.1 General. (Amended) This Section
applies to storm shelters where, constructed as separate detached
buildings or where, constructed as safe rooms within buildings for
the purpose of providing refuge from storms that produce high winds,
such as tornadoes and hurricanes. In addition to other applicable
requirements in this code, storm shelters shall be constructed in
accordance with ICC 500, except when located below grade or if basement
walls are fully constructed with concrete.
29.
Section R331 Fences walls and screens (Added).
30.
Section R331.1 Fences general (Added). All fences,
walls and screens must be constructed in accordance with the Zoning
Code of the City of Florissant. It shall be unlawful to erect any
division, fence or screen, in whole or in part, of cloth, canvas or
similar non-durable material.
31.
Section R331.2 Finished side (Added). The finished
side offences shall face all neighboring properties including streets
and alleys so as to prohibit the view offence posts and support rails
from adjoining properties.
Exception: In cases where both sides of a fence
are intended to be finished, i.e., shadowbox or basket weave construction,
etc.
32.
Section R401.1 Application (Amended). The provisions
of this Chapter shall control the design and construction of the foundation
and foundation spaces for buildings. In addition to the provisions
of this Chapter, the design and construction of foundations in flood
hazard areas as established by Table R301.2(1) shall meet the provisions
of Section R322. Wood foundations shall be designed and installed
in accordance with AWC PWF.
Exceptions: The provisions of this Chapter shall
be permitted to be used for wood foundations only in the following
situations:
1.
In buildings that have not more than two (2) floors and a roof.
2.
Where interior basement and foundation walls are constructed
at intervals not exceeding fifty (50) feet (15,240 mm).
3.
(Added) The provisions of this Chapter shall not be required
for detached accessory structure foundations under two hundred (200)
square feet.
Wood foundations in Seismic Design Category D0, D1 or D2 shall be
designed in accordance with accepted engineering practice.
33.
R403.1.7 Footings on or adjacent to slopes. (Amended)
The placement of buildings and structures on or adjacent to slopes
steeper than one (1) unit vertical in three (3) units horizontal (33.3%
slope) shall conform to Sections R403.1.7.1 through R403.1.7.4 or
plans as signed and sealed by a registered engineer/design professional
licensed in the State of Missouri.
34.
Section R404.1.3.2 Reinforcement for foundation walls. (Amended) Concrete foundation walls shall be laterally supported
at the top and bottom. Horizontal reinforcement shall be provided
in accordance with Table R404.1.2(1). Vertical reinforcement shall
be provided in accordance with Table R404.1.2(2), R404.1.2(3), R404.1.2(4),
R404.1.2(5), R404.1.2(6), R404.1.2(7) or R404.1.2(8). Vertical reinforcement
for flat basement walls retaining four (4) feet (1,219 mm) or more
of unbalanced backfill is permitted to be determined in accordance
with Table R404.1.2(9). For basement walls supporting above-grade
concrete walls, vertical reinforcement shall be the greater of that
required by Tables R404.1.2(2) through R404.1.2(8) or by Section R608.6
for the above-grade wall. In buildings assigned to Seismic Design
Category D0, D1 or D2, concrete foundation walls shall also comply with Section
R404.1.4.2.
Exception: Where unstable soil or ground water
conditions do not exist, concrete foundation walls may be constructed
in accordance with Table R404.1.2(10).
35.
Table R404.1.2(10) CONCRETE FOUNDATION WALLS (Added)
Maximum Wall Height
|
Maximum Depth of Unbalanced Backfill
|
Minimum Nominal Wall Thickness
|
---|
8'-0"
|
7'-6" or less
|
8" (Note a)
|
9'-0"
|
8'-6" or less
|
10" (Note b)
|
10'0"
|
9'-6" or less
|
12" (Note c)
|
Note a:
|
Concrete foundation walls may be constructed a minimum of nominal
eight (8) inches thick where the wall height from the top of the footing
to the top of the wall does not exceed eight (8) feet. A minimum of
two (2) #4 reinforcing bars shall be placed horizontally in the top
and bottom of the foundation wall. A minimum of two (2) #5 reinforcing
bars shall be provided around all window and door openings in concrete
foundation and basement walls; bars shall extend a minimum of twenty-four
(24) inches beyond the corners of the openings.
|
Note b:
|
Concrete foundation walls may be constructed a minimum of nominal
ten (10) inches thick. A minimum of two (2) #5 reinforcing bars shall
be placed horizontally in the top, middle, and bottom of the foundation
wall. A minimum of two (2) #5 reinforcing bars shall be provided around
all window and door openings in concrete foundation and basement walls;
bars shall extend a minimum of twenty-four (24) inches beyond the
corners of the openings.
|
Note c:
|
Concrete foundation walls may be constructed a minimum of nominal
twelve (12) inches thick. A minimum of three (3) #5 reinforcing bars
shall be placed horizontally in the top, middle, and bottom of the
foundation wall. A minimum of two (2) #5 reinforcing bars shall be
provided around all window and door openings in concrete foundation
and basement walls; bars shall extend a minimum of twenty-four (24)
inches beyond the corners of the openings.
|
Note d:
|
The concrete minimum wall thickness shall be eight (8) inches
for foundation walls in soil classes SC, MH, ML-CL and inorganic CL
when maximum wall height is eight (8) feet.
|
Note e:
|
The concrete minimum wall thickness shall be ten (10) inches
for foundation walls in soil classes SC, MH, ML-CL and inorganic CL
when the maximum wall height is nine (9) feet.
|
Note f:
|
The concrete minimum wall thickness shall be twelve (12) inches
for foundation walls in soil classes SC, MH, ML-CL and inorganic CL
when the maximum wall height is ten (10) feet.
|
36.
Section 405.1 Concrete or masonry foundations. (Amended)
Drains shall be provided around concrete or masonry foundations that
retain earth and enclose habitable or usable spaces located below
grade. Drainage tiles, gravel or crushed stone drains, perforated
pipe or other approved systems or materials shall be installed at
or below the top of the footing or below the bottom of the slab and
shall discharge by gravity or mechanical means into an approved drainage
system. Gravel or crushed stone drains shall extend not less than
one (1) foot (305 mm) beyond the outside edge of the footing and six
(6) inches (152 mm) above the top of the footing and be covered with
an approved filter membrane material. The top of open joints of drain
tiles shall be protected with strips of building paper. Except where
otherwise recommended by the drain manufacturer, perforated drains
shall be surrounded with an approved filter membrane or the filter
membrane shall cover the washed gravel or crushed rock covering the
drain. Drainage tiles or perforated pipe shall be placed on not less
than two (2) inches (51 mm) of washed gravel or crushed rock not less
than one sieve size larger than the tile joint opening or perforation
and covered with not less than six (6) inches (152 mm) of the same
material.
Exceptions:
1.
A drainage system is not required where the foundation is installed
on well-drained ground or sand-gravel mixture soils according to the
Unified Soil Classification System, Group I soils, as detailed in
Table R405.1.
2.
Drains provided as detailed in Section R405.1.2 are approved
as an alternative method to meet the requirements of this Section.
37.
Section R405.1.2 Soil evaluations. (Added) An evaluation
of the soil for the presence or absence of groundwater is required.
The evaluation report shall be based on either a subsurface soil investigation
or satisfactory data from adjacent areas together with an inspection
of the excavation prior to pouring concrete.
38.
Section R405.1.2.1 Groundwater present. (Added)
Provide drain tile, perforated pipe or other approved foundation drainage
systems (such as water channel system) around perimeter of the outside
of the foundation and inside the foundation. Drain discharge shall
be by gravity to daylight or be connected to a basement floor sump.
39.
Section R405.1.2.2 No groundwater present. (Added)
Provide drain tile, perforated pipe or other approved foundation drainage
systems (such as water channel system) around perimeter of the outside
of the foundation or inside the foundation. Drain discharge shall
be by gravity to daylight or be connected to a basement floor sump.
40.
Section R405.1.2.3 Filter membranes. (Added) An
approved filter membrane shall be placed over the top of the joints/pipe
perforations. The tile/pipe shall be placed on two (2) inches minimum
of gravel or crushed stone and have six (6) inches of minimum cover.
41.
Section R405.1.2.4 Drainage system. (Added) A drainage
system shall discharge by gravity to daylight or be connected to an
approved sump (fifteen (15) inches in diameter x eighteen (18) inches
deep with fitted cover). A sump pump shall be provided if the basement
is finished or partially finished with pump discharge by an approved
method.
42.
Section R506.2.3 Vapor retarder. (Amended) A minimum
six (6) mil (0.006 inch; 0.152 mm) vapor retarder conforming to ASTM
E1745 Class A requirements with joints lapped not less than six (6)
inches (152 mm) shall be placed between the concrete floor slab and
the base course or the prepared subgrade where a base course does
not exist.
43.
Section R602.12 Simplified wall bracing. (Amended)
Buildings meeting all of the following conditions shall be permitted
to be braced in accordance with this Section as an alternative to
the requirements of Section R602.10. The entire building shall be
braced in accordance with this Section; the use of other bracing provisions
of Section R602.10, except as specified herein, shall not be permitted.
1. There shall be not more than three (3) stories above the top of a
concrete or masonry foundation or basement wall. Permanent wood foundations
shall not be permitted.
2. Floors shall not cantilever more than twenty-four (24) inches (607
mm) beyond the foundation or bearing wall below.
3. Wall height shall not be greater than a nominal twelve (12) feet
when using the minimum required bracing lengths specified in Table
602.12.4.
Exception: Structural calculations and details
are not required when there are no braced wall panels in that portion
of a wall where the height exceeds a nominal twelve (12) feet and
that greater wall height segment is part of a prescriptive braced
wall line on each of the adjacent stories.
4. The building shall have a roof eave-to-ridge height of fifteen (15)
feet (4,572 mm) or less.
5. Exterior walls shall have gypsum board with a minimum thickness of
one-half (1/2) inch (12.7 mm) installed on the interior side fastened
in accordance with Table R702.3.5.
Exception: Gypsum board is not required for wall
bracing on exterior walls in garages.
6. The structure shall be located where the ultimate design wind speed
is less than or equal to one hundred thirty (130) mph (58 m/s), and
the exposure category is B or C.
7. The structure shall be located in Seismic Design Category A, B or
C for detached one- and two-family dwellings or Seismic Design Category
A, B or C for townhouses.
8. Cripple walls shall not be permitted in three-story buildings.
44.
Section R602.12.2 Sheathing materials. (Amended)
The following sheathing materials installed on the exterior side of
exterior walls shall be used to construct a bracing unit as defined
in Section R602.12.3. Mixing materials is prohibited.
1.
Wood structural panels with a minimum thickness of seven sixteenth
(7/16) inch fastened in accordance with Table R602.3(3).
2.
Structural fiberboard sheathing with a minimum thickness of
one-half (1/2) inch (12.7 mm) fastened in accordance with Table R602.3(1).
45.
Section R602.12.3 Bracing unit. (Amended) A bracing
unit shall be a full-height sheathed segment of the exterior wall
without openings or vertical or horizontal offsets and a minimum length
as specified herein. Interior walls shall not contribute toward the
amount of required bracing. Mixing of Items 1 and 2 is prohibited
on the same story.
1.
Where all framed portions of all exterior walls are sheathed
in accordance with Section R602.12.2, including wall areas between
bracing units, above and below openings and on gable end walls, the
minimum length of a bracing unit shall be three (3) feet (914 mm).
For walls with heights greater than a nominal ten (10) feet, the minimum
length of a bracing unit shall be four (4) feet (1,219 mm).
2.
Where the exterior walls are braced with sheathing panels in
accordance with Section R602.12.2 and areas between bracing units
are covered with other materials, the minimum length of a bracing
unit shall be four (4) feet (1,219 mm).
46.
Section R602.13 Alternate simplified bracing method for
one- and two-family dwellings when the entire structure is sheathed
with wood structural panels and located in wind exposure A or B. (Added) The construction documents shall detail the locations and
widths of all braced wall panels in accordance with this Section.
47.
Section R602.13.1 Wood structural sheathing. (Added)
The building exterior walls shall be sheathed with seven sixteenth
(7/16) inch (11.1 mm) or thicker plywood or OSB wood structural panels.
The wood structural panels shall be applied to all exterior walls,
gable ends and band boards. All vertical joints between panels shall
be blocked. Horizontal joints in braced wall panels shall be blocked.
48.
Section R602.13.2 Braced wall panel locations. (Added)
Braced wall panels shall be located in every exterior braced wall
line in accordance with the following criteria:
1.
The outside edge of the first braced wall panel meeting the
width established in Table R602.13.3 shall be a maximum of twelve
and five-tenths (12.5) feet (3,810 mm) or less from each end of the
braced wall line. The outside stud of the first braced wall panels
closest to the end of the braced wall line shall be secured with a
hold-down device securing the end stud to the foundation with a minimum
uplift design value of eight hundred (800) pounds.
Exception: The eight hundred (800) pound hold-down
device is not required when the braced wall panel is placed at the
end of the braced wall line and there is a twenty-four (24) inch (610
mm) wide full height sheathed wall placed ninety degrees (90°)
to the end of the braced wall line and panel.
2.
The centerline spacing of braced wall panels in a braced wall
line may not exceed twenty-five (25) feet (7,620 mm).
49.
Section R602.13.3 Braced wall panel widths. (Added)
Braced wall panel locations shall be shown on the floor plans or elevation
views and meet the widths established in Table R602.13.3.
50.
Table 602.13.3 SIMPLIFIED BRACING PANEL WIDTHS (Added)
|
Width of Solid Panela, b
|
---|
8' wall height
|
9' wall height
|
10' wall height
|
12' wall height
|
---|
Plywood/OSB Panel
|
3:1
|
32"
|
36"
|
40"
|
48"
|
Simplified Portal Wallc
|
6:1
|
16"d
|
18"d
|
20"d
|
24"d
|
a.
|
Linear interpolation is permitted.
|
b.
|
Wall height is the vertical distance from the bottom of the
sole/sill plate to the top of the double top plate. An additional
two (2) inch (50.8 mm) variation in height is allowed for pre-cut
stud framing.
|
c.
|
The Simplified Portal Wall, if applicable, shall be constructed
in accordance with the applicable detail in Figure R602.13.3. The
designer shall provide this detail on the construction documents.
|
d.
|
The Simplified Portal Wall width assumes the beam is placed
under the top plate of the wall. A smaller width may be calculated
for a lower top of beam height using the 6:1 height to width ratio.
|
51.
Section R602.13.4 Corner framing. (Added) The exterior
wall corners shall be constructed in accordance with the applicable
detail in Figure R602.10.10.4.
Exception: Braced wall panels located in accordance
with Section R602.13.2.
52.
Section R602.13.5 Braced wall line spacing. (Added)
When the perpendicular distance between the exterior braced wall lines
exceeds fifty (50) feet (15,240 mm), the registered design professional
shall include the following certification on the drawings: The interior
and exterior wall configuration braces for the structure in accordance
with or equivalent to the lateral bracing provisions of Section R602.10
of the International Residential Code, 2009 Edition, or Section 2305
of the International Building Code, 2009 Edition.
53.
Section R602.13.6 Maximum wall height. (Added)
Walls greater than twelve (12) feet (3,658 mm) (twelve (12) feet two
(2) inches (3,708 mm) actual) in height and twelve (12) feet (3,658
mm) in width shall be designed and detailed by the registered design
professional to resist wind loads in both the longitudinal and transverse
directions.
54.
Section R905.2.8.5 Drip edge. (Amended) A drip
edge shall be provided at eaves of shingle roofs. Adjacent segments
of drip edge shall be overlapped not less than two (2) inches (51
mm). Drip edges shall extend not less than one-fourth (1/4) inch (6.4
mm) below the roof sheathing and extend up back onto the roof deck
not less than two (2) inches (51 mm). Drip edges shall be mechanically
fastened to the roof deck at not more than twelve (12) inches (305
mm) o.c. with fasteners as specified in Section R905.2.5. Underlayment
shall be installed over the drip edge along eaves and under the drip
edge along rake edges.
Exception: Unless the drip edge is specifically
required by the manufacturer's installation instructions, metal
wrapped fascia extending one (1) inch under the roof covering with
the underlayment installed over it shall be deemed to meet the requirements
of this Section.
55.
Section R1005.7 Factory-built chimney offsets. (Amended)
Where a factory-built chimney assembly incorporates offsets, no part
of the chimney shall be at an angle of more than thirty degree (30°)
(0.52 rad) from vertical at any point in the assembly and the chimney
assembly shall not include more than four (4) elbows.
Exception: When chimneys are installed per manufacturer's
installation instructions.
56.
R1006.1.1 Factory-built fireplaces. Exterior combustion
air ducts for factory-built fireplaces shall be a listed component
of the fireplace or equivalent and shall be installed according to
the fireplace manufacturer's instructions.
57.
R1006.2 Exterior air intake. The exterior air intake
on masonry fireplaces shall be capable of supplying combustion air
from the exterior of the dwelling or from spaces within the dwelling
ventilated with outdoor air such as non-mechanically ventilated crawl
or attic spaces. The exterior air intake shall not be located within
the garage or basement of the dwelling. The exterior air intake, for
other than listed factory-built fireplaces, shall not be located at
an elevation higher than the firebox. The exterior air intake shall
be covered with a corrosion-resistant screen of one-fourth (1/4) inch
(6.4 mm) mesh.
58.
Section N1101.5 (R103.2) Information on construction documents. (Deleted)
59.
Section N1101.6 (R202) Defined terms. (Added) PROJECTION FACTOR. The ratio of the horizontal depth of an
overhang, eave, or permanently attached shading device, divided by
the distance measured vertically from the bottom of the fenestration
glazing to the underside of the overhang, eave, or permanently attached
shading device.
60.
Section N1101.13 (R401.2) Application. (Amended)
Residential buildings shall comply with Section N1101.13.1, N1101.13.2,
N1101.13.3 or N1101.13.4.
61.
Section N1101.13.5 (R401.2.5) Additional energy efficiency. (Deleted)
62.
Section N1101.14 (R401.3) Certificate. (Deleted)
63.
Table N1102.1.3 (R402.1.3) INSULATION MINIMUM R-VALUES
AND FENESTRATION REQUIREMENTS BY COMPONENTa (Amended)
64.
Section N1102.1.4 (R402.1.4) R-value computation. (Amended) Cavity insulation alone shall be used to determine compliance
with the cavity insulation R-value requirements in Table N1102.1.3.
Where cavity insulation is installed in multiple layers, the R-values
of the cavity insulation layers shall be summed to determine compliance
with the cavity insulation R-value requirements. The manufacturer's
settled R-value shall be used for blown-in insulation. Continuous
insulation (ci) alone shall be used to determine compliance with the
continuous insulation R-value requirements in Table N1102.1.3. Where
continuous insulation is installed in multiple layers, the R-values
of the continuous insulation layers shall be summed to determine compliance
with the continuous insulation R-value requirements. Cavity insulation
R-values shall not be used to determine compliance with the continuous
insulation R-value requirements in Table N1102.1.3. Computed R-values
may include an R-value for other building materials or air films.
Where insulated siding is used for the purpose of complying with the
continuous insulation requirements of Table N1102.1.3, the manufacturer's
labeled R-Value for insulated siding shall be reduced by R-0.6.
65.
Section N1102.1.5 (R402.1.5) Total UA alternative. (Amended) Where the total building thermal envelope UA, the sum
of U-factor times assembly area, is less than or equal to the Total
UA resulting from multiplying the U-factors in Table N1102.1.2 by
the same assembly area as in the proposed building, the building shall
be considered to be in compliance with Table N1102.1.2. The UA calculation
shall be performed using a method consistent with the ASHRAE Handbook
of Fundamentals and shall include the thermal bridging effects of
framing materials. In addition to UA compliance, the SHGC requirements
of Table N1102.1.2 and the maximum fenestration U-factors of Section
N1102.5 shall be met.
Exception: Glazed fenestration SHGC. In Climate
Zone 4, permanently shaded vertical fenestration shall be permitted
to satisfy SHGC requirements. The projection factor of an overhang,
eave, or permanently attached shading device shall be greater than
or equal to the value listed in Table N1102.2.2.1 for the appropriate
orientation. The minimum projection shall extend beyond each side
of the glazing a minimum of twelve (12) inches. Each orientation shall
be rounded to the nearest cardinal orientation (+/- forty-five degrees
(45°) or 0.79 rad) for purposes of calculations and demonstrating
compliance.
66.
Table N1102.1.5 MINIMUM PROJECTION FACTOR REQUIRED BY
ORIENTATION BOR SHGC EXEPTION. (Added)
Orientation
|
Projection Factor
|
---|
North
|
>=0.40a
|
South
|
>=0.20
|
East
|
>=0.50
|
West
|
>=0.50
|
a.
|
For the north orientation, a vertical projection located on
the west-edge of the fenestration with the equivalent of PF>=0.15
shall also satisfy the minimum projection factor requirement.
|
67.
Section N1102.2.4 (R402.2.4) Access hatches and doors. (Amended) Access hatches and doors from conditioned to unconditioned
spaces such as attics and crawl spaces shall be insulated to R-38.
Exceptions:
|
1.
|
Vertical doors providing access from conditioned spaces to unconditioned
spaces that comply with the fenestration requirements of Table N1102.1.3
based on the applicable climate zone specified in Chapter 3.
|
2.
|
Horizontal pull-down, stair-type access hatches in ceiling assemblies
that provide access from conditioned to unconditioned spaces in Climate
Zones 0 through 4 shall not be required to comply with the insulation
level of the surrounding surfaces provided that the hatch meets all
of the following:
|
|
2.1.
|
The average U-factor of the hatch shall be less than or equal
to U-0.10 or have an average insulation R-value of R-10 or greater.
|
|
2.2.
|
Not less than seventy-five percent (75%) of the panel area shall
have an insulation R-value of R-13 or greater.
|
|
2.3.
|
The net area of the framed opening shall be less than or equal
to 13.5 square feet (1.25m2).
|
|
2.4.
|
The perimeter of the hatch edge shall be weatherstripped.
|
68.
Section N1102.4 (R402.4) Air leakage. (Amended)
The building thermal envelope may be designed and constructed to limit
air leakage in accordance with the requirements of Sections N1102.4.1
through N1102.4.5.
69.
Section N1102.4.1.2
(R402.4.1.2) Testing. (Amended) Any building or dwelling unit
may be tested for air leakage. The maximum design air leakage rate
for any building or dwelling unit under any compliance path shall
not exceed 5.0 air changes per hour or twenty-eight-hundredths (0.28)
cubic feet per minute (CFM) per square foot [0.0079 m3/(s x m2)] of dwelling
unit enclosure area. For any building or dwelling unit designed for
3.0 or less air changes per hour, testing shall be conducted in accordance
with ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827 and reported at
a pressure of two-tenths (0.2) inch w.g. (50 Pascals). Where required
by the Code Official, testing shall be conducted by an approved third
party. A written report of the results of the test shall be signed
by the party conducting the test and provided to the Code Official.
Testing shall be performed at any time after creation of all penetrations
of the building thermal envelope have been sealed.
Exception: For heated, attached private garages
and heated, detached private garages accessory to one- and two-family
dwelling and townhouses not more than three (3) stories above grade
plane in height, building envelope tightness and insulation installation
shall be considered acceptable where the items in Table N1102.4.1.1,
applicable to the method of construction, are field verified. Where
required by the Code Official, an approved third party, independent
from the installer shall inspect both the air barrier and insulation
installation criteria. Heated, attached private garage space shall
be thermally isolated from all other conditioned spaces in accordance
with Sections N1102.2.12 and N1102.3.5, as applicable.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed,
but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue
dampers shall be closed, but not sealed beyond intended infiltration
control measures.
3. Interior doors, where installed at the time of the test, shall be
open.
4. Exterior or interior terminations for continuous ventilation systems
shall be sealed.
5. Heating and cooling systems, where installed at the time of the test,
shall be turned off.
6. Supply and return registers, where installed at the time of the test,
shall be fully open.
Exception: When testing individual dwelling units,
an air leakage rate not exceeding thirty-hundredths (0.30) cubic feet
per minute per square foot [0.008m3/(s
x m2)] of the dwelling unit enclosure area,
tested in accordance with ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827
and reported at a pressure of two-tenths (0.2) inch water gauge (50
Pa), shall be permitted in all climate zones for:
1. Attached single- and multiple-family building dwelling units.
2. Buildings or dwelling units that are one thousand five hundred (1,500)
square feet (139.4m2) or smaller.
Mechanical ventilation shall be provided in accordance with
Section M1505 of this code or Section 403.3.2 of the International
Mechanical Code, as applicable, or with other approved means of ventilation.
|
70.
Section N1102.4.1.3 (R402.4.1.3) Leakage rate. (Amended)
Where complying with Section N1101.13.1. the building or dwelling
unit shall have a design air leakage rate not exceeding 5.0 air changes
per hour.
71.
Table N1102.4.1.1 (402.4.1.1)a AIR BARRIER AND INSULATION INSTALLATION. (Amended)
Component
|
Air Barrier Criteria
|
Insulation Installation Criteria
|
---|
General Requirements
|
A continuous air barrier shall be installed in the building
envelope.
Breaks or joints in the air barrier shall be sealed.
|
Air-permeable insulation shall not be used as a sealing material.
|
Ceiling/attic
|
The air barrier in any dropped ceiling or soffit shall be aligned
with the insulation and any gaps in the air barrier sealed.
Access openings, drop-down stairs or knee wall doors to unconditioned
attic spaces shall be weatherstripped.
|
The insulation in any dropped ceiling/soffit shall be aligned
with the air barrier.
|
Walls
|
The junction of the foundation and sill plate shall be sealed.
|
Cavities within corners and headers of frame walls shall be
insulated by completely filling the cavity with a material having
a thermal resistance, R-value, of not less than R-3 per inch.
Exterior thermal envelope insulation for framed walls shall
be installed in substantial contact and continuous alignment with
the air barrier.
|
Windows, skylights and doors
|
The space between framing and skylights, and the jambs of windows
and doors, shall be sealed.
|
|
Rim joists
|
Rim joists shall include an exterior air barrier.b
|
Rim joists shall be insulated.
|
Floors, including cantilevered floors and floors above garages
|
The air barrier shall be installed at any exposed edge of insulation.
|
Floor framing cavity insulation shall be installed to maintain
permanent contact with the underside of subfloor decking. Alternatively,
floor framing cavity insulation shall be in contact with the top side
of sheathing, or continuous insulation installed on the underside
of floor framing and extending from the bottom to the top of all perimeter
floor framing members.
|
Basement crawl space, and slab foundations
|
Exposed earth in unvented crawl spaces shall be covered with
Class I vapor retarder/air barrier in accordance with Section R402.2.10.
Penetrations through concrete foundation walls and slabs shall
be air sealed.
Class 1 vapor retarders shall not be used as an air barrier
on below-grade walls and shall be installed in accordance with Section
R702.7
|
Crawl space insultation, where provided instead of floor insulation,
shall be installed in accordance with Section R402.2.10.
|
Shafts, penetrations
|
Duct and flue shafts and other similar penetrations to exterior
or unconditioned space shall be sealed to allow for expansion, contraction
and mechanical vibration.
Utility penetrations of the air barrier shall be caulked, gasketed
or otherwise sealed and shall allow for expansion, contraction of
materials and mechanical vibration.
|
Insulation shall be fitted tightly around utilities passing
through shafts and penetrations in the building thermal envelope to
maintain required R-value.
|
Narrow cavities
|
Narrow cavities of one (1) inch or less that are not able to
be insulated shall be air sealed.
|
Batts to be installed in narrow cavities shall be cut to fit
or narrow cavities shall be filled with insulation that on installation
readily conforms to the available cavity space.
|
Garage separation
|
Air sealing shall be provided between the garage and conditioned
spaces.
|
Insulated portions of the garage separation assembly shall be
installed in accordance with Sections R303 and R402.2.7.
|
Recessed lighting
|
Recessed light fixtures installed in the building thermal envelope
shall be sealed in accordance with Section R402.4.5.
|
Recessed light fixtures installed in the building thermal envelope
shall be airtight and IC rated, and shall be buried or surrounded
with insulation.
|
Plumbing, wiring or other obstructions
|
All holes created by wiring, plumbing or other obstructions
in the air barrier assembly shall be air sealed.
|
Insulation shall be installed to fill the available space and
surround wiring, plumbing, or other obstructions, unless the required
R-value can be met by installing insulation and air barrier systems
completely to the exterior side of the obstructions.
|
Shower/tub on exterior wall
|
|
Exterior walls adjacent to showers and tubs shall be insulated.
|
Electrical/phone box on exterior walls
|
The air barrier shall be installed behind electrical and communication
boxes. Alternatively, air-sealed boxes shall be installed.
|
|
HVAC register boots
|
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the subfloor, wall covering or
ceiling penetrated by the boot.
|
|
Concealed sprinklers
|
Where required to be sealed, concealed fire sprinklers shall
only be sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings.
|
|
For SI: 1 inch = 25.4 mm.
|
a.
|
Inspection of log walls shall be in accordance with the provisions
of ICC 400.
|
b.
|
Air barrier and insulation full enclosure is not required in
unconditioned/ventilated attic spaces and at rim joists.
|
72.
Section N1102.4.4 (R402.4.4) Rooms containing fuel-burning
appliances. (Amended) In Climate Zones 3 through 8, where open
combustion airducts provide combustion air to open combustion fuel-burning
appliances, the appliances and combustion air opening shall be located
outside the building thermal envelope or enclosed in a room that is
isolated from inside the thermal envelope. Such rooms shall be sealed
and insulated in accordance with the envelope requirements of Table
N1102.1.3, where the walls, floors and ceilings shall meet a minimum
of the basement wall R-value requirement. The door into the room shall
be fully gasketed and any water lines and ducts in the room insulated
in accordance with Section N1103. The combustion air duct shall be
insulated where it passes through conditioned space to an R-value
of not less than R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed
continuous to the outside.
2. Fireplaces and stoves complying with Sections N1102.4.2 and R1006.
3. Mechanical equipment in an unfinished space.
73.
Section N1103.3.4 (R403.3.4) Sealing. (Amended)
Ducts, air handlers and filter boxes shall be sealed. Joints and seams
shall comply with either the International Mechanical Code or Section
M1601.4.1 of this code, as applicable.
Exceptions:
1.
Air-impermeable spray foam products shall be permitted to be
applied without additional joint seals.
2.
Continuously welded and locking-type longitudinal joints and
seams in ducts operating at static pressure less than two (2) inches
of water column (500 Pa) pressure classification shall not require
additional closure systems.
3.
A duct air leakage test shall not be required where the ducts
and air handlers are located entirely within the building thermal
envelope.
74.
Section N1103.3.5
(R403.3.5) Duct testing. (Amended) Ducts shall be pressure
tested in accordance with ANSI/RESNET/ICC 380 or ASTM E1554 to determine
air leakage by one of the following methods:
1.
Rough-in test: Total leakage shall be measured with a pressure
differential of one-tenths (0.1) inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed
at the time of the test. Registers shall be taped or otherwise sealed
during the test.
2.
Postconstruction test: Total leakage shall be measured with
a pressure differential of one-tenths (0.1) inch w.g. (25 Pa) across
the entire system, including the manufacturer's air handler enclosure.
Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air-leakage test shall not be required where the ducts and
air handlers are located entirely within the building thermal envelope.
2. A duct air-leakage test shall not be required for ducts serving heating,
cooling or ventilation systems that are not integrated with ducts
serving heating or cooling systems.
75.
Section N1103.3.7 (R403.3.7) Building cavities. (Deleted)
76.
Section N1103.5.2 (R403.5.2) Hot water pipe insulation. (Amended) Insulation for service hot water piping with a thermal
resistance, R-value, of not less than R-3 shall be applied to the
following:
1.
Piping larger than three fourth (3/4) inch (19 mm) in nominal
diameter located inside the conditioned space.
2.
Piping serving more than one (1) dwelling unit.
3.
Piping located outside the conditioned space.
4.
Piping from the water heater to a distribution manifold.
5.
Piping located under a floor slab.
7.
Supply and return piping in circulation and recirculation systems
other than cold water pipe return demand recirculation systems.
77.
Section N1103.6 (R403.6) Mechanical ventilation. (Deleted)
78.
Section N1104.2 (R404.2) Interior lighting controls. (Amended) Permanently installed lighting fixtures may be controlled
with a dimmer, an occupant sensor control or another control that
is installed or built into the fixture.
Exceptions:
3.
Exterior lighting fixtures.
4.
Lighting designed for safety or security.
79.
Section N1104.3 (R404.3) Exterior lighting controls. (Deleted)
80.
Section M1301.2 Identification. (Deleted)
81.
Section M1305.1.3.3 Electrical requirements. (Amended)
A luminaire controlled by a switch located at the required passageway
opening and a receptacle outlet shall be installed at or near the
appliance location in accordance with Chapter 39, Exposed lamps, shall
be protected from damage by location or lamp guards.
Exception: Basements.
82.
Section M1307.2 Anchorage of appliances. (Amended)
Appliances designed to be fixed in position shall be fastened or anchored
in an approved manner. In Seismic Design Categories D0, D1 and D2, water
heaters and thermal storage units shall be anchored or strapped to
resist horizontal displacement caused by earthquake motion in accordance
with one (1) of the following:
1.
Anchorage and strapping shall be designed to resist a horizontal
force equal to one-third (1/3) of the operating weight of the water
heater storage tank, acting in any horizontal direction. Strapping
shall be at points within the upper one-third (1/3) and lower one-third
(1/3) of the appliance's vertical dimensions. At the lower point,
the strapping shall maintain a minimum distance of four (4) inches
(102 mm) above the controls.
2.
The anchorage strapping shall be in accordance with the appliance
manufacturer's recommendations.
83.
Section M1411.3.1.2 Appliance, equipment and insulation
in pans. (Deleted)
84.
Section M1502.4.2 Duct installation. (Amended)
Exhaust ducts shall be supported at intervals not to exceed twelve
(12) feet (3,658 mm) and shall be secured in place. The insert end
of the duct shall extend into the adjoining duct or fitting in the
direction of airflow. Exhaust duct joints shall be sealed in accordance
with Section M1601.4.1.
85.
Section M1502.4.5 Booster fans. (Amended) All dryer
exhaust system booster fans must be UL listed and labeled.
86.
Section M1502.4.6.1 Specified length. (Amended)
The maximum length of the exhaust duct shall be thirty-five (35) feet
(10,688 mm) from the connection to the transition duct from the dryer
to the outlet terminal. Where fittings are used, the maximum length
of the exhaust duct shall be reduced in accordance with Table M1502.4.6.1.
The maximum length of the exhaust duct does not include the transition
duct.
Exception: The maximum developed length may be
extended to fifty-five (55) feet if clearly labeled cleanouts are
provided within twelve (12) inches of the second elbow, at every elbow
thereafter, and at least every fifteen (15) feet of developed length
thereafter.
87.
Section M1503.6 Makeup air required. (Amended)
Where one (1) or more gas, liquid or solid fuel-burning appliance
that is neither direct-vent nor uses a mechanical draft venting system
is located within a dwelling unit's air barrier, each exhaust
system capable of exhausting in excess of six hundred (600) cubic
feet per minute shall be mechanically or passively provided with makeup
air at a rate approximately equal to the exhaust air rate. Such makeup
air systems shall be equipped with not fewer than one (1) damper complying
with Section M1503.6.2.
Exception: Makeup air is not required for exhaust
systems installed for the exclusive purpose of space cooling and intended
to be operated only when windows or other air inlets are open.
88.
Section M1504.3 Exhaust openings. (Amended) Air
exhaust openings shall terminate as follows:
1.
Not less than three (3) feet (914 mm) from gravity air intake
openings, operable windows and doors.
2.
Not less than ten (10) feet (3,048 mm) from mechanical air intake
openings except where the exhaust opening is located not less than
three (3) feet (914 mm) above the air intake opening. Openings shall
comply with Sections R303.5.2 and R303.6.
89.
Section M1601.1.1 Above-ground duct systems. (Amended)
Above-ground duct systems shall conform to the following:
1.
|
Equipment connected to duct systems shall be designed to limit
discharge air temperature to not greater than two hundred fifty degrees
Fahrenheit (250° F.) (121° C.).
|
2.
|
Fibrous glass duct construction shall conform to the SMACNA
Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct
Construction Standards.
|
3.
|
Field-fabricated and shop-fabricated metal and flexible duct
constructions shall conform to the SMACNA HVAC Duct Construction Standards —
Metal and Flexible except as allowed by Table M1601.1.1. Galvanized
steel shall conform to ASTMA 653.
|
4.
|
The use of gypsum products to construct return air ducts or
plenums is permitted, provided that the air temperature does not exceed
one hundred twenty-five Fahrenheit (125° F.) (52° C.) and
exposed surfaces are not subject to condensation.
|
5.
|
Duct systems shall be constructed of materials having a flame
spread index of not greater than two hundred (200).
|
6.
|
Stud wall cavities and the spaces between solid floor joists
to be used as non-ducted air plenums shall comply with the following
conditions:
|
|
6.1.
|
These cavities or spaces shall not be used as a plenum for air
supply.
|
|
6.2.
|
These cavities or spaces shall not be a part of required fire-resistance-rated
assembly.
|
|
6.3.
|
Stud wall cavities shall not convey air from more than one (1)
floor level.
|
|
6.4.
|
Stud wall cavities and joist-space plenums shall be isolated
from adjacent concealed spaces by tight-fitting fireblocking in accordance
with Section R302.11. Fire-blocking materials used for isolation shall
comply with Section R302.11.1.
|
|
6.5.
|
Stud wall cavities in the outside walls of building envelope
assemblies shall not be utilized as air plenums.
|
|
6.6.
|
Building cavities used as plenums shall be sealed.
|
7.
|
Volume dampers, equipment and other means of supply, return
and exhaust air adjustment used in system balancing may be provided
with access.
|
90.
Table M1601.1.1. DUCT CONSTRUCTION MINIMUM SHEET METAL
THICKNESS FOR SINGLE DWELLING UNITSa (Amended)
Round Duct Diameter
(inches)
|
Static Pressure
|
---|
1/2 inch water gage
|
1 inch water gage
|
---|
Thickness (inches)
|
Thickness (inches)
|
---|
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
|
---|
< 12
|
0.013
|
0.018
|
0.013
|
0.018
|
12 to 14
|
0.013
|
0.018
|
0.016
|
0.023
|
15 to 17
|
0.016
|
0.023
|
0.019
|
0.027
|
18
|
0.016
|
0.023
|
0.024
|
0.034
|
19 to 20
|
0.019
|
0.027
|
0.024
|
0.034
|
Rectangular Duct Dimension
(largest dimension)
|
Static Pressure
|
---|
1/2 inch water gage
|
1 inch water gage
|
---|
Thickness (inches)
|
Thickness (inches)
|
---|
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
|
---|
< 8
|
0.013
|
0.018
|
0.013
|
0.018
|
9 to 10
|
0.013
|
0.018
|
0.016
|
0.023
|
11 to 12
|
0.016
|
0.023
|
0.019
|
0.027
|
13 to 16
|
0.016
|
0.027
|
0.019
|
0.027
|
17 to 18
|
0.019
|
0.027
|
0.024
|
0.034
|
19 to 20
|
0.019
|
0.034
|
0.024
|
0.034
|
For SI: 1 inch = 25.4 mm, 1 inch water gage = 249 Pa.
|
a.
|
Ductwork that exceeds twenty (20) inches by dimension or exceeds
a pressure of one (1) inch water gage shall be constructed in accordance
with SMACNA HVAC Duct Construction Standards — Metal and Flexible.
|
91.
Section M1601.4.1 Joints, seams and connections. (Amended) Joints of duct systems shall be made substantially airtight
in an unconditioned area by means of tapes, mastics, liquid sealants,
gasketing or other approved closure systems. Closure systems used
with rigid fibrous glass ducts shall comply with UL 181A and shall
be marked 181A-P for pressure-sensitive tape, 181A-M for mastic or
181A-H for heat-sensitive tape. Closure systems used with flexible
air ducts and flexible air connectors shall comply with UL 181B and
shall be marked 181B-FX for pressure-sensitive tape or 181B-M for
mastic. Duct connections to flanges of air distribution system equipment
or sheet metal fittings shall be mechanically fastened. Mechanical
fasteners for use with flexible nonmetallic air ducts shall comply
with UL 181B and shall be marked 181B-C. Crimp joints for round metal
ducts shall have a contact lap of at least one (1) inch and shall
be mechanically fastened with at least three (3) sheet metal screws
or rivets equally spaced around the joint. Closure systems used to
seal metal ductwork shall be installed in accordance with the manufacturer's
installation instructions.
Exceptions:
1.
Spray polyurethane foam shall be permitted to be applied without
additional joint seals.
2.
Where a duct connection is made that is partially without access,
three (3) screws or rivets shall be equally spaced on the exposed
portion of the joint so as to prevent a hinge effect.
3.
Continuously welded and locking-type longitudinal joints and
seams in ducts operating at static pressure less than two (2) inches
of water column (500 Pa) pressure classification shall not require
additional closure systems.
92.
M1602.2 Return air openings. Return air openings
for heating, ventilation and air conditioning systems shall comply
with all of the following:
1.
|
Openings shall not be located less than ten (10) feet (3,048
mm) measured in any direction from an open combustion chamber or draft
hood of another appliance located in the same room or space.
|
2.
|
Return and transfer openings shall be sized in accordance with
the appliance or equipment manufacturers' installation instructions,
Manual D or the design of the registered design professional.
|
3.
|
Return air shall not be taken from a closet less than sixty-four
(64) square feet, bathroom, toilet room, kitchen, garage, mechanical
room, boiler room, furnace room or unconditioned attic.
|
|
Exceptions:
|
|
1.
|
Taking return air from a kitchen is not prohibited where such
return air openings serve the kitchen only, and are located not less
than ten (10) feet (3,048 mm) from the cooking appliances.
|
|
2.
|
Dedicated forced-air systems serving only the garage shall not
be prohibited from obtaining return air from the garage.
|
|
4.
|
For other than dedicated HVAC systems, return air shall not
be taken from indoor swimming pool enclosures and associated deck
areas except where the air in such spaces is dehumidified.
|
|
5.
|
Taking return air from an unconditioned crawl space shall not
be accomplished through a direct connection to the return side of
a forced-air furnace. Transfer openings in the crawl space enclosure
shall not be prohibited.
|
|
6.
|
Return air from one (1) dwelling unit shall not be discharged
into another dwelling unit.
|
93.
Section M2101.16 CPVC plastic pipe. (Deleted)
94.
Section M2101.22.6 Expansion tanks. (Deleted)
95.
Section M2101.26 Pipe penetrations. (Amended) Openings
for pipe penetrations in walls, floors and ceilings shall be larger
than the penetrating pipe. Openings in the foundation wall underground
shall be sealed to not allow groundwater into a building.
96.
Section M2105.4 Piping and tubing materials standards. (Amended) Ground-source heat-pump ground-loop pipe and tubing shall
conform to the standards listed in Table M2105.4. However, polyvinyl
chloride (PVC) and chlorinated polyvinyl chloride (CPVC) shall not
be used on geothermal ground loops both inside and underground.
97.
Section M2105.9 CPVC plastic pipe. (Deleted)
98.
Section G2408.4 (305.7) Clearances from grade. (Amended)
Equipment and appliances installed at grade level shall be supported
on a level concrete slab or other approved material extending not
less than two (2) inches (50.8 mm) above adjoining grade or shall
be suspended not less than six (6) inches (152 mm) above adjoining
grade. Such supports shall be installed in accordance with the manufacturer's
installation instructions.
99.
Section G2409.1 (308.1) Scope. (Amended) This Section
shall govern the reduction in required clearances to combustible materials
and combustible assemblies for chimneys, vents, appliances, devices
and equipment. Clearance requirements for air-conditioning equipment
and central heating boilers and furnaces shall comply with Sections
G2409.3 and G2409.4.
100.
Section G2412.9 (401.9) Identification. (Deleted)
101.
Section G2412.10 (401.10) Piping materials standards. (Deleted)
102.
Section G2415.3 (404.3) Prohibited Locations. (Amended)
Pipe fittings shall not be installed in or through a ducted supply,
return or exhaust, or a clothes chute, chimney or gas vent, dumbwaiter
or elevator shaft. Piping installed downstream of the point of delivery
shall not extend through any townhouse unit other than the unit served
by such piping.
Exception: Or installed as approved by the Authority
Having Jurisdiction (AHJ), such as Ameren or Spire.
103.
Section G2439.7.4.1 (614.9.4.1) Specified length. (Amended) The maximum length of the exhaust duct shall be thirty-five
(35) feet (10,688 mm) from the connection to the transition duct from
the dryer to the outlet terminal. Where fittings are used, the maximum
length of the exhaust duct shall be reduced in accordance with Table
G2439.7.4.1. The maximum length of the exhaust duct does not include
the transition duct.
Exception: The maximum developed length may be
extended to fifty-five (55) feet if clearly labeled cleanouts are
provided within twelve (12) inches of the second elbow, at every elbow
thereafter, and at least every fifteen (15) feet of developed length
thereafter.
104.
Section G2442.3 (618.3) Prohibited sources. (Amended)
Outdoor or return air for forced-air heating and cooling systems shall
not be taken from the following locations:
1.
|
Closer than ten (10) feet (3,048 mm) from an appliance vent
outlet, a vent opening from a plumbing drainage system or the discharge
outlet of an exhaust fan, unless the outlet is three (3) feet (914
mm) above the outside air inlet.
|
2.
|
Where there is the presence of objectionable odors, fumes or
flammable vapors; or where located less than ten (10) feet (3,048
mm) above the surface of any abutting public way or driveway; or where
located at grade level by a sidewalk, street, alley or driveway.
|
3.
|
A hazardous or insanitary location or a refrigeration machinery
room as identified in the International Mechanical Code.
|
4.
|
A room or space, the volume of which is less than twenty-five
percent (25%) of the entire volume served by such system. Where connected
by a permanent opening having an area sized in accordance with this
code, adjoining rooms or spaces shall be considered as a single room
or space for the purpose of determining the volume of such rooms or
spaces.
|
|
Exception: The minimum volume requirement shall
not apply where the amount of return air taken from a room or space
is less than or equal to the amount of supply air delivered to such
room or space.
|
5.
|
A room or space containing an appliance where such a room or
space serves as the sole source of return air.
|
|
Exception: This shall not apply where:
|
|
1.
|
The appliance is a direct-vent appliance or an appliance not
requiring a vent in accordance with Section G2425.8.
|
|
2.
|
The room or space complies with the following requirements:
|
|
|
2.1.
|
The return air shall be taken from a room or space having a
volume exceeding one (1) cubic foot for each ten (10) Btu/h (9.6L/W)
of combined input rating of all fuel-burning appliances therein.
|
|
|
2.2.
|
The volume of supply air discharged back into the same space
shall be approximately equal to the volume of return air taken from
the space.
|
|
|
2.3.
|
Return-air inlets shall not be located within ten (10) feet
(3,048 mm) of a draft hood in the same room or space or the combustion
chamber of any atmospheric burner appliance in the same room or space.
|
|
3.
|
Rooms or spaces containing solid fuel-burning appliances, provided
that return-air inlets are located not less than ten (10) feet (3,048
mm) from the firebox of such appliances.
|
6.
|
A closet, bathroom, toilet room, kitchen, garage, boiler room,
furnace room or unconditioned attic.
|
|
Exceptions:
|
|
1.
|
Where return air intakes are located not less than ten (10)
feet (3,048 mm) from cooking appliances and serve only the kitchen
area, taking return air from a kitchen area shall not be prohibited.
|
|
2.
|
Dedicated forced air systems serving only a garage shall not
be prohibited from obtaining return air from the garage.
|
|
3.
|
Where a closet sixty four (64) square feet or greater in size
is provided with a supply register, taking return air from the closet
shall not be prohibited.
|
7.
|
A crawl space by means of direct connection to the return side
of a forced-air system. Transfer openings in the crawl space enclosure
shall not be prohibited.
|
105.
Section P2609.1 Identification. (Deleted)
106.
Section P2609.2 Installation of materials. (Deleted)
107.
Section P2609.3 Plastic pipe, fittings and components. (Deleted)
108.
Section P2609.4 Third-party certification. (Deleted)
109.
Section P2609.5 Water supply systems. (Deleted)
110.
Section P2706.2 Prohibited waste receptors. (Amended)
Plumbing fixtures that are used for washing or bathing shall not be
used to receive the discharge of indirect waste piping.
Exceptions:
1. A kitchen sink trap is acceptable for use as a receptor for a dishwasher.
2. A laundry tray is acceptable for use as a receptor for a clothes
washing machine.
3. A drain or waste pipe above a trap is acceptable for use as a receptor
for mechanical equipment condensate drains.
111.
Section P2801.8 Water heater seismic bracing. (Amended)
In Seismic Design Categories D0, D1 and D2 water heaters shall
be anchored or strapped in the upper one-third (1/3) and in the lower
one-third (1/3) of the appliance to resist a horizontal force equal
to one-third (1/3) of the operating weight of the water heater, acting
in any horizontal direction, or in accordance with the appliance manufacturer's
recommendations.
112.
Section P3201.2.1 Trap seal protection. (Amended)
Traps seals of emergency floor drain traps and traps subject to evaporation
shall be protected by one (1) of the methods in Sections P3201.2.1.1
through P3201.2.1.4.
Exception: Basement floor drains with a condensate
line draining to it.
113.
Section E3601.8 Emergency disconnects. (Deleted)
114.
Section E3606.5 Surge protection. (Amended)
115.
Section E3701.5.1 Disconnecting means. (Amended)
Each multi-wire branch circuit may be provided with a means that will
simultaneously disconnect all ungrounded conductors at the point where
the branch circuit originates. [210.4(B)]
116.
Section E3902.2 Garage and accessory building receptacles. (Amended) 125-volt through 250-volt receptacles installed in garages
and grade-level portions of unfinished accessory buildings used for
storage or work areas and supplied by single-phase branch circuits
rated one hundred fifty (150) volts or less to ground shall have ground-fault
circuit-interrupter protection for personnel. [210.8(A)(2)]
Exception: Fastened in place appliances or outlets
designated for refrigerators/freezers.
117.
Section E3902.5 Basement receptacles. (Amended)
125-volt through 250-volt receptacles installed in basements and supplied
by single-phase branch circuits rated one hundred fifty (150) volts
or less to ground shall have ground-fault circuit-interrupter protection
for personnel. [210.8(A)(5)]
Exceptions:
1.
A receptacle supplying only a permanently installed fire alarm
or burglar alarm system. A receptacle installed in accordance with
this exception shall not be considered as meeting the requirements
of Section E3901.9. Receptacles installed in accordance with this
exception shall not be considered as meeting the requirement of Section
E3901.9. [210.8(A)(5) Exception]
2.
Fastened in place appliances or outlets designated for refrigerators/freezers.
118.
Section E3902.6 Kitchen receptacles. (Amended)
125-volt through 250-volt receptacles that serve countertop surfaces
and are supplied by single-phase branch circuits rated one hundred
fifty (150) volts or less to ground shall have ground-fault circuit-interrupter
protection for personnel. [210.8(A)(6)]
Exception: Fastened in place appliances or outlets
designated for refrigerators/freezers.
119.
Section E3902.9 Laundry areas. (Deleted)
120.
Section E3902.11 Kitchen dishwasher branch circuit. (Deleted).
121.
Section E3902.15 Location of ground-fault circuit interrupters. (Amended) Ground-fault circuit interrupters shall be installed only
in a readily accessible location. [210.8(A)]
122.
E3902.17 Arc-fault circuit-interrupter protection. (Amended) Branch circuits that supply 120-volt, single-phase, 15-
and 20-ampere outlets installed in bedrooms shall be protected by
any of following: [210.12(A)]
1.
|
A listed combination-type arc-fault circuit interrupter, installed
to provide protection of the entire branch circuit. [210.12(A)(1)]
|
2.
|
A listed branch/feeder-type AFCI installed at the origin of
the branch-circuit in combination with a listed outlet branch-circuit
type arc-fault circuit interrupter installed at the first outlet box
on the branch circuit. The first outlet box in the branch circuit
shall be marked to indicate that it is the first outlet of the circuit.
[210.12(A)(2)]
|
3.
|
A listed supplemental arc-protection circuit breaker installed
at the origin of the branch circuit in combination with a listed outlet
branch-circuit type arc-fault circuit-interrupter installed at the
first outlet box on the branch circuit where all of the following
conditions are met:
|
|
3.1.
|
The branch-circuit wiring shall be continuous from the branch-circuit
overcurrent device to the outlet branch-circuit arc-fault circuit
interrupter.
|
|
3.2.
|
The maximum length of the branch-circuit wiring from the branch-circuit
overcurrent device to the first outlet shall not exceed fifty (50)
feet (15.2 m) for 14 AWG conductors and seventy (70) feet (21.3 m)
for 12 AWG conductors
|
|
3.3.
|
The first outlet box in the branch circuit shall be marked to
indicate that it is the first outlet on the circuit. [210.12(A)(3)]
|
4.
|
A listed outlet branch-circuit-type arc-fault circuit interrupter
installed at the first outlet on the branch circuit in combination
with a listed branch-circuit overcurrent protective device where all
of the following conditions are met:
|
|
4.1.
|
The branch-circuit wiring shall be continuous from the branch-circuit
overcurrent device to the outlet branch-circuit arc-fault circuit
interrupter.
|
|
4.2.
|
The maximum length of the branch-circuit wiring from the branch-circuit
overcurrent device to the first outlet shall not exceed fifty (50)
feet (15.2 m) for 14 AWG conductors and seventy (70) feet (21.3 m)
for 12 AWG conductors.
|
|
4.3.
|
The first outlet box in the branch circuit shall be marked to
indicate that it is the first outlet on the circuit.
|
|
4.4.
|
The combination of the branch-circuit overcurrent device and
outlet branch-circuit AFCI shall be identified as meeting the requirements
for a system combination-type AFCI and shall be listed as such. [210.12(A)(4)]
|
1.
|
Where metal raceways, metal wireways, metal auxiliary gutters
or Type MC or Type AC cable meeting the applicable requirements of
Section E3908.9 with metal boxes, metal conduit bodies and metal enclosures
are installed for the portion of the branch circuit between the branch-circuit
overcurrent device and the first outlet, a listed outlet branch-circuit
type AFCI installed at the first outlet shall be considered as providing
protection for the remaining portion of the branch circuit. [210.12(A)(5)]
|
2.
|
Where a listed metal or non-metallic conduit or tubing or Type
MC cable is encased in not less than two (2) inches (50.8 mm) of concrete
for the portion of the branch circuit between the branch-circuit overcurrent
device and the first outlet, a listed outlet branch-circuit type AFCI
installed at the first outlet shall be considered as providing protection
for the remaining portion of the branch circuit. [210.12(A)(6)]
|
|
Exception: AFCI protection shall not be required
for an individual branch circuit supplying a fire alarm system where
the branch circuit is installed in a metal raceway, metal auxiliary
gutter, steel-armored cable, Type MC or Type MC or Type AC, meeting
the requirements of Section E3908.9, with metal boxes, conduit bodies
and enclosures.
|
123.
Section E3902.18 Arc-fault circuit interrupter protection
for branch circuit extensions or modifications. (Amended) Where
branch-circuit wiring is modified, replaced, or extended in any of
the areas specified in Section E3902.17, the branch circuit shall
be protected by one (1) of the following:
1.
A combination-type AFCI located at the origin of the branch
circuit.
2.
An outlet branch-circuit type AFCI located at the first receptacle
outlet of the existing branch circuit. [210.12(B)]
Exception: AFCI protection shall not be required
where the extension of the existing branch-circuit conductors is not
more than thirty (30) feet (9.5 m) in length and does not include
any additional outlets or devices other than splicing devices. This
measurement shall not include the conductors inside an enclosure,
cabinet or junction box. [210.12(B) Exception]
124.
Section E4002.8 Damp locations. (Amended) A receptacle
installed outdoors in a location protected from the weather or in
other damp locations shall have an enclosure for the receptacle that
is weatherproof when the receptacle cover(s) is closed and an attachment
plug cap is not inserted. An installation suitable for wet locations
shall also be considered suitable for damp locations. A receptacle
shall be considered to be in a location protected from the weather
where located under roofed open porches, canopies and similar structures
and not subject to rain or water runoff. [406.9(A)]
125.
Section E4002.14 Tamper resistant receptacles. (Deleted)