Section 107.1 is hereby amended to read as follows:
107.1 General.
In order to hear and decide appeals of orders, decisions or
determinations made by the Building Official relative to the application
and interpretation of this code, there shall be and is hereby created
a Board of Appeals consisting of 3 members and 2 alternates who are
qualified by experience and training to pass upon matters pertaining
to building construction and who are not employees of the jurisdiction.
The Building Official shall be an ex officio member
of and shall act as Secretary to said Board but shall have no vote
on any matter before the Board. The Board shall adopt rules of procedure
for conducting its business and shall render all decisions and findings
in writing to the appellant with a duplicate copy to the Building
Official.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)
Section 104.5 is hereby amended to read as follows:
104.5 Fees.
The fee for each permit shall be as established by Resolution
of the City Council.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)
Table 104.5 is hereby deleted.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)
Appendix L is hereby deleted.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)
Section 609.3.1 is hereby added to read as follows:
609.3.1 Copper tubing serving plumbing fixtures
within dwelling unit kitchen islands shall be installed without joints
and the installation shall satisfy the following requirements.
1. The
copper tubing shall be installed within a watertight continuous sleeve
that prevents direct contact between the copper tubing and underslab
soils. During construction the protective sleeve shall be capped at
both ends until the copper tubing is installed and released for inspection.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)
Section H701.2 is hereby amended to read as follows:
H701.2 Multiple Installations.
Multiple seepage pit installations shall be served through an
approved distribution box. The inlet into the pit shall have an approved
vented leg fitting extending not less than 12 inches below the inlet
fitting.
(Ord. No. 899 § 7, 2016; Ord. No. 956 § 7, 2019; Ord. No. 1011 § 7, 2022)