Section BG102.1 is amended to read as follows:
Section BG102 Air-Borne Sound.
Section BG102.1 General: Amended. Walls, partitions, and floor-ceiling assemblies separating dwelling units from each other or from public or service areas shall have a sound transmission class (STC) of not less than 50 (45 if field tested) for air-borne noise when tested in accordance with ASTM E 90. Penetrations or openings in construction assemblies for piping, electrical devices, recessed cabinets, bathtubs, soffits, or heating, ventilating or exhaust ducts shall be sealed, lined, insulated, or otherwise treated to maintain the required ratings. This requirement shall not apply to dwelling unit entrance doors; however, such doors shall be tight fitting to the frame and sill.
Section BG103.1 is amended to read as follows:
Section BG103 Structural-Borne Sound.
Section BG103.1 General: Amended. Floor-ceiling assemblies between dwelling units or between a dwelling unit and a public or service area within the structure shall have an impact insulation class (IIC) rating of not less than 50 (45 if field tested) when tested in accordance with ASTM E 492.
(Ord. 1679-2025, 10/22/2025)