For the purpose of this Article, crude oil means
oil which has not been refined, processed or treated except to remove
or separate therefrom any sand, water or other foreign substances,
and which oil has a closed cup flash point below one hundred seventy-five
degrees Fahrenheit. Refined oil means all oil, other
than crude oil, which has such a flash point.
All state laws, governing and regulating the drilling of wells
for, and the producing of oil, gas and other hydrocarbon substances,
the erection, operation, maintenance, abandonment and removal of derricks,
production equipment and other structures and facilities appurtenant
to such wells, are hereby adopted by reference.
This article known as the "Oil Code" Shall not in any manner
repeal, amend, modify or supersede any zoning ordinance of the City
as same may now exist or be hereafter amended, or any business license
ordinance of the City, as same may now exist or be hereafter amended;
as the provisions, terms, requirements and conditions of said "Oil
Code" are intended to be in addition and supplementary to the provisions
of any such zoning ordinance or business license ordinance.
Except as otherwise provided, it is unlawful and a nuisance
to drill any well or well-hole, or to erect any derrick or production
equipment, or to operate or maintain the same or any thereof, or any
portion of any thereof, in or upon any real property in the City.
Upon obtaining the necessary permits therefor, and during such
time as such permits are kept in full force and effect, and each and
all of the terms and conditions of such permits and of all of the
regulations and provisions of all laws and all ordinances of the City
applicable thereto, are complied with, the permittee may drill, operate
and maintain a well or well-hole and erect, operate and maintain the
necessary derrick and production equipment for the drilling, operation
and maintenance of such well.
It shall be unlawful for any person to erect any wooden derrick
for use as any part of the equipment for the purpose of drilling or
operating an oil well or gas well.
There shall be at least one forty-gallon foam engine for each
derrick or well. In lieu of the forty-gallon foam engine, a foam generator
or generators and foam powder may be substituted, subject to the approval
of the Fire Chief. Location of fire extinguishers or agents shall
be subject to the approval of the Fire Chief.
All required extinguishers or agents and appliances shall be
maintained in proper working condition at all times.
It shall be unlawful for any person to drill for or store oil
or petroleum in the City unless there is immediately available a good
and sufficient supply of water for fire fighting purposes, adequate
in the opinion of the Fire Chief for the particular installation or
operation to be protected; or without the provision of a sufficient
number of fire hydrants to be approved both as to the spacing and
number by said Fire Chief.
It shall be lawful for the Fire Chief or his duly authorized
representative to enter upon any premises and into any derrick or
structure appurtenant thereto if necessary, in the opinion of the
Fire Chief or his duly authorized representative, in order to preserve
or protect the public safety.
It shall be unlawful for any person to locate, maintain, or
operate any derrick, well or well-hole within one hundred feet of
any steam boiler, or other source of ignition or tank or container
holding flammable gas or light gravity flammable oil where the property
owned or controlled by any such person will permit a greater distance.
In no case shall a derrick, well or well-hole be located, maintained,
or operated within twenty-five feet of any such boiler, other source
of ignition, tank or container. Where the area under ownership or
control of any person locating, maintaining, or operating a derrick,
well or well-hole does not permit the one-hundred foot limit distance
above specified, location of such derrick, well or well-hole shall
be designated by the Fire Chief on the property owned or controlled
by such person, and proper safeguards shall be provided as may be
determined by the Fire Chief. The provisions of this Section shall
not apply to flow tanks not more than two in number nor greater than
five hundred barrels capacity each, gas traps, or electrical dehydrators.
It shall be unlawful for any person to locate, maintain, or
operate any steam boiler or other source of ignition within one hundred
feet of any derrick, well or well-hole, or any storage tank or container
holding flammable gas or light gravity flammable oil, where the property
owned or controlled by any such person will permit a greater distance.
In no case shall a boiler or other source of ignition be located,
maintained, or operated within twenty-five feet of any such derrick,
well, well-hole, tank or container. Where the area under ownership
or control of any person locating, maintaining or operating a boiler
or other source of ignition does not permit the one-hundred-foot-limit
distance above specified, location of such boiler or other source
of ignition shall be designated by the Fire Chief on the property
owned or controlled by such person, and proper safeguards shall be
provided as may be determined by the Fire Chief. The provisions of
this Section shall not apply to flow tanks not more than two in number
nor greater than five hundred barrels capacity each, gas traps, or
electrical dehydrators.
If more than one steam boiler is to be hereafter maintained,
or operated for a particular use, such steam boilers must be so located
as to form a battery. Every such steam boiler, or battery of boilers,
except when housed or enclosed, or except when elevated to a height
of twenty-four inches above the surrounding terrain, shall be completely
surrounded by a retaining wall of not less than twenty-four inches
in height, constructed of non-combustible material, and located not
less than fifteen feet distant from such boiler, or battery of boilers;
if earth is used, such retaining wall shall be not less than eighteen
inches in width at the top.
The location and construction of all tanks, sumps, retaining
walls and other equipment for the storage or treating of oil or petroleum
shall be approved by the Superintendent of Building and Safety and
the Fire Chief, before being used.
(Ord. 2397 5-5-81)
Where required, in the judgment of the Fire Chief, every steam
boiler located within one hundred feet of any oil well or oil storage
tank, shall be equipped with a water or steam line of not less than
one-inch diameter, piped from a point outside the retaining wall where
required, into the boiler fire box. Such water or steam line shall
be controlled by an emergency valve to be located as designated by
the Fire Chief. Such emergency control valve shall have a metal tag
not less than three inches by six inches attached thereto, which tag
shall have printed thereon "EMERGENCY VALVE TO BOILERS (STEAM OR WATER)."
Where required, in the judgment of the Fire Chief, every steam
boiler located within one hundred feet of any oil well or oil storage
tank, shall be equipped with an emergency quick acting valve so located,
outside the retaining wall where required, as to completely shut off
all fuel feed lines to each and every boiler. Such valve shall be
located not more than two feet from the valve controlling the steam
or water line to the fire box and shall have a metal tag not less
than three inches by six inches attached thereto, which tag shall
have printed thereon, "EMERGENCY VALVE TO BOILERS (FUEL LINE)."
On all dry gas lines used for the purpose of furnishing fuel
to boilers, or for the agitation of petroleum products within tanks,
holders or containers, there shall be installed a positive shut-off
valve at or near the point of entry to the lease, or a suitable location
designated by the Fire Chief. Such valve shall have a metal tag not
less than three inches by six inches attached thereto, which tag shall
have printed thereon "EMERGENCY VALVE—DRY GAS LINE," (Name,
or number of lease and name of oil company).
It shall be unlawful for any person to place, divert or discharge
into or upon, or permit, allow or assist in the placing, discharging
or diverting into or upon any street, drainage canal or ditch, storm
drain or flood-control channel any liquid containing oil or petroleum
products.
It shall be unlawful for any person to cause or permit any oil,
waste oil, refuse or waste matter to be or remain on the surface of
the ground under, around or near any oil derrick, pump, boiler, oil
storage or bleeder tank, or any combustible structure, except within
an oil sump or oil tank.
It shall be unlawful for any person to use or maintain any permanent
sump for the purpose of storing petroleum or its liquid byproducts
more than one foot above the natural ground level unless such sump
is constructed and maintained with the approval of the Fire Chief
and the Superintendent of Building and Safety. The walls of such sump
shall be of well compacted earth having a minimum horizontal width
at the top of six feet, and a maximum slope ratio of one foot vertical
to one and one-half feet horizontal. The level of the liquid in any
sump shall not be allowed to rise above a point twelve inches below
the lowest top point of the enclosing walls of the sump, and such
point shall be marked by a gauge or marker at least four inches square,
located at a point most accessible for gauging, and the top of such
gauge shall indicate the maximum liquid level.
All waste shall be piped into such sumps and no drain or outlet
shall be permitted through the sumps at any point above the natural
ground level.
(Ord. 2397 5-5-81)
It shall be unlawful for any person to set fire to, or burn,
any oil or liquid with petroleum content in any sump hole, open pool
or reservoir, or permit oil so situated upon premises belonging to
such person to be burned, unless a permit therefor been obtained from
the Fire Chief.
It shall be unlawful for any person to smoke or throw, place
or deposit any lighted or smoldering cigar, cigarette, ash, match,
or other smoldering substance, within one hundred feet of any oil
well derrick, or storage tank or oil sump containing petroleum or
any of its fluid byproducts. "NO SMOKING" signs shall be posted, and
all such signs shall have letters at least four inches in height.
All land within a radius of one hundred feet from any derrick,
tank, building, machinery or equipment used in the development, production
or storage of petroleum products shall at all times be kept free and
clear from dry weeds or grass, rubbish or other flammable material.
Tanks used for heat treating petroleum or products thereof,
shall not be of the open type, nor shall the capacity of any such
tank exceed two thousand barrels. Tanks into which petroleum or any
products thereof exceed a temperature of one hundred thirty degrees
Fahrenheit is discharged or stored shall be equipped with a suitable
vent stack which shall extend upward and terminate a point at least
thirty feet above the ground; or a vent shall be tightly connected
to a vapor recovery system of a type approved by the Fire Chief. No
pipeline connected to any system containing air under pressure shall
enter into any such tank, and it shall be unlawful to cause or permit
the contents of any such tank to be agitated with air at any time.
During the drilling operations of any well, the following equipment
shall be provided:
(1) A drilling
or master gate for closing the well in completely when the drill pipe
is out of the hole.
(2) A ram-type
gate or packing-head assembly for closing the well in with the drill
pipe or kelly in the hole.
(3) A high
pressure gate for closing in the mud flow line when the packing-head
assembly is being used.
(4) A high
pressure mud fill-up line, with a high pressure gate, into the casing
below the master gate.
(5) All master
gates and ram-type gates mounted on the casing shall have controls
extending beyond the derrick floor.
(6) All fittings
shall be of sufficient strength to withstand one and one-half times
the "top hole shut in pressure" of the well.
Except as hereinafter specifically provided, no tank shall be
constructed except in accordance with the American Petroleum institute
specifications for standard tanks as follows:
(1) A.P.I.
Standards No. 12-A (for tanks with riveted shells) Seventh Edition,
March, 1941.
(2) A.P.I.
Standards No. 12-B (for bolted tanks) Fifth Edition, September, 1944.
(3) A.P.I.
Standards No. 12-C (for all welded oil well storage tanks) Seventh
Edition, August, 1946.
(4) A.P.I.
Standards No. 12-D (for all welded production tanks) Third Edition,
September, 1944; a full, true and correct printed copy of each of
which is on file in the office of the City Clerk in the City Hall
open to public inspection.
If a tank is of a capacity and height for which no specifications are given in said standards referred to in Section
6-48 such tank shall comply with specifications approved by the Fire Chief and the Superintendent of Building and Safety, which specifications so approved shall not allow working stresses in excess of those specified in said A.P.I. standards and shall be in accordance with all of the requirements of said A.P.I. standards except for size; provided, further, that spherical, spheroidal and horizontal cylindrical tanks may be constructed in accordance with specifications submitted by the applicant, which have been approved by the Fire Chief and the Superintendent of Building and Safety; provided, further, that the installation of a new location of any tank heretofore erected in the City shall be deemed to be a new construction. The removal and erection of such tank shall be subject to the approval of the Fire Chief and the Superintendent of Building and Safety.
(Ord. 2397 5-5-81)
No tank used as a flow tank or production tank, or as a lease
shipping tank in connection with oil production (not including wash
tanks) shall exceed sixteen feet six inches in height, or two thousand
barrels capacity. Not more than two tanks of two thousand barrels
capacity each shall be erected for each well-hole.
No tank hereafter erected shall be used for a wash tank or settling
tank for the purpose of separating sand, water and other foreign substances
from petroleum and other hydrocarbons unless such tank is less than
twenty-four feet in height and less than thirty feet in diameter.
All wash tanks or settling tanks and other equipment or facilities,
whether heretofore or hereafter constructed for use or used for the
purpose of separating sand, water and other foreign substances from
petroleum and other hydrocarbons shall be of a type of design approved
by the Fire Chief and Superintendent of Building and Safety, and if
such tank contains oil or other hydrocarbons which at any time exceeds
a temperature of one hundred thirty degrees Fahrenheit, such tank
shall be equipped with a vent stack of a type or design approved by
the Fire Chief and the Superintendent of Building and Safety. Said
stack shall extend upward and terminate at a point at least thirty
feet above the ground; provided, however, that in lieu of such vent
stack, the vents to such tanks may be tightly connected by means of
a pipe and fittings to a vapor recovery system constructed and maintained
in a manner which is approved by the Fire Chief and the Superintendent
of Building and Safety; provided, further, that no pipe line that
is connected to any system containing air under pressure shall enter
into any such tank, nor shall the contents of any such tank be agitated
with air in any manner.
(Ord. 2397 5-5-81)
No boiler fuel tank shall be erected for use in connection with
the drilling, operation or maintenance of any well or well-hole, or
in connection with the erection, operation or maintenance of any derrick,
production equipment, refinery, natural gasoline plant, commercial
dehydration plant, loading rack or bulk distributing plant, unless
constructed of steel or iron of thickness not less than twelve gauge,
and not exceeding two hundred barrel capacity, and unless located
not less than twenty-five feet from any portion of the fire-box of
any boiler, such tank must be riveted, bolted or welded as specified
in this Article. Not more than two boiler fuel tanks heretofore or
hereafter erected shall be operated in one setting.
A floating or diaphragm roof of a type or design approved by
the Fire Chief and the Superintendent of Building and Safety may be
installed on any tank in lieu of any fixed roof.
(Ord. 2397 5-5-81)
No tank shall be erected within twenty-five feet of any steam
boiler or open flame, or at any location which is not in accordance
with the following table (the measurements to be taken from the shell
of the tank):
LOCATION OF TANKS
|
---|
Capacity of Tank In 42 Gal. Barrels
|
Distance from All Buildings, Structures or Line of Adjoining
Property Which May Be Built Upon
|
Distance From Nearest Tank
|
---|
1 to 266
|
8 Feet
|
2 Feet
|
267 to 720
|
10 Feet
|
3 Feet
|
721 to 1,600
|
15 Feet
|
5 Feet
|
1,601 to 2,884
|
15 Feet
|
5 Feet
|
2,885 to 5,031
|
20 Feet
|
7 Feet
|
5,032 to 10,200
|
20 Feet
|
7 Feet
|
10,201 to 15,000
|
25 Feet
|
10 Feet
|
15,001 to 23,500
|
30 Feet
|
15 Feet
|
23,501 to 40,000
|
40 Feet
|
20 Feet
|
40,001 to 70,000
|
50 Feet
|
25 Feet
|
70,001 to 95,000
|
60 Feet
|
30 Feet
|
Any tank which has a vapor space which must breathe and which
is to be used for holding or storing any flammable liquid having a
closed cup flash point below one hundred degrees Fahrenheit or any
such tank so designed or constructed that the contents may be heated
to its flash point, shall be so equipped as to maintain a substantially
gas tight condition of the container. The breathing vent for such
tank shall conform to A.P.I. standards for the venting of low pressure
above-ground storage tanks.
In horizontal tanks or other tanks heretofore or hereafter erected
and in which entire dependence for relief is placed on some form of
emergency relief construction other than a weak roof seam, a relief
device shall be provided which shall have capacity as prescribed in
the table hereafter set forth. If the pressure relief device is in
the form of a free substantially circular opening it shall be designed
in accordance with the dimensions given in said table.
MINIMUM EMERGENCY RELIEF CAPACITY
|
EMERGENCY RELIEF OF EXCESSIVE INTERNAL PRESSURE IN TANKS
|
|
APPROXIMATE DIAMETER OF FREE CIRCULATOR OPENING (UNOBSTRUCTED
BY VALVE DISC., ETC.) REQUIRED TO DISCHARGE PETROLEUM VAPORS AT THE
GIVEN RATES FOR THE FOLLOWING INTERNAL PRESSURES
|
|
CAPACITY of tank in gals.
|
CUBIC ft. per hour (based upon an orifice co-efficient of 0.7
and vapor specific gravity of 2.5)
|
COL. I 33″ of water or less
|
COL. 2 1-lb. per sq. in. or less
|
1,000
|
16,000
|
4 in.
|
2½ in.
|
4,000
|
44,000
|
63/4 in.
|
33/4 in.
|
18,000
|
88,000
|
9½ in.
|
5½ in.
|
25,000
|
105,000
|
10¼ in.
|
6 in.
|
56,000
|
160,000
|
123/4 in.
|
7¼ in.
|
100,000
|
230,000
|
15¼ in.
|
83/4 in.
|
155,000
|
290,000
|
17¼ in.
|
93/4 in.
|
222,000
|
330,000
|
18¼ in.
|
10½ in.
|
475,000
|
395,000
|
20 in.
|
11¼ in.
|
Unlimited
|
410,000
|
20½ in.
|
11½ in.
|
|
|
COL. 3
|
COL. 4
|
|
|
9-lbs. per sq. in. or less
|
25-lbs. per sq. in. or less
|
1,000
|
16,000
|
1½ in.
|
1 in.
|
4,000
|
44,000
|
2¼ in.
|
13/4 in.
|
18,000
|
88,000
|
3¼ in.
|
2½ in.
|
25,000
|
105,000
|
3½ in.
|
23/4 in.
|
56,000
|
160,000
|
4¼ in.
|
33/4 in.
|
100,000
|
230,000
|
5 in.
|
4 in.
|
155,000
|
290,000
|
53/4 in.
|
4½ in.
|
222,000
|
330,000
|
6 in.
|
43/4 in.
|
475,000
|
395,000
|
63/4 in.
|
5 in.
|
Unlimited
|
410,000
|
63/4 in.
|
5¼ in.
|
Every pipe or other connection to any tank whereby any of the
contents of such tank can flow out by gravity or be siphoned therefrom
shall be provided with a steel shut-off valve as close as possible
to the tank shell. Such valve shall be installed on the nozzle or
other connection to the tank so that such flow can be effectively
stopped, and there shall be no branch or connection to any such pipe
between any such valve and such tank except that there may be installed
a bypass line of not to exceed three-quarter-inch iron pipe size equipped
with a steel check or non-return valve designed to permit excessive
pressure in the pipe line to be relieved into the tank.
Any such valve hereafter installed shall be of metal which will
not lose more than seventy-five percent of its rated tensile strength
when subjected to a temperature of one thousand degrees Fahrenheit;
provided, however, that nothing herein contained shall preclude the
use of such valves as are permitted by the California State Industrial
Accident Commission. Liquefied Petroleum Gases Safety Orders.
Tanks, the bottoms of which set more than one foot above ground,
shall have foundation and supports of noncombustible materials; provided,
however, that such to the approval of the Fire Chief and the Superintendent
of Building and Safety, wooden cushions may be permitted. Where such
supports heretofore or hereafter constructed are of metal, they shall
be covered by at least three inches of concrete or masonry.
(Ord. 2397 5-5-81)
All nozzles and other openings hereafter installed in welded
or riveted tank shells shall be designed, constructed, installed and
maintained in accordance with all of the applicable requirements of
the American Petroleum Institute specifications (Standards Nos. 12-A
and 12-C).
A complete vapor recovery system, satisfactory to the Fire Chief,
shall be installed on all tanks or other equipment wherever gathering
lines are available.
Every tank or group of tanks heretofore or hereafter constructed,
or maintained, except tanks used for storage of liquefied petroleum
gases as defined by the Liquefied Petroleum Gases and Safety Orders
issued by the Industrial Accident Commission of the State of California,
and which are protected as required by said safety orders, shall be
surrounded by or adequately protected by a retaining wall, as herein
provided. Such retaining walls may be constructed of masonry or earth
work in a manner approved by the Fire Chief and Superintendent of
Building and Safety. Each retaining wall shall be so constructed as
to retain and impound the entire maximum content of all the tanks
in the area surrounded by or protected by such wall. Any deviation
from the one hundred percent retention of the contents of such tanks
shall be subject to the approval of the Superintendent of Building
and Safety and Fire Chief. The maximum content of such tanks shall
be deemed to be the maximum cubical capacity thereof, and shall be
clearly designated on each such tank.
Each such retaining wall shall be constructed so that the same
will not leak and there shall be no doors or windows or any other
opening in or through such wall or underneath the same except piping
installed and maintained in a manner approved by the Fire Chief and
the Superintendent of Building and Safety. Each such retaining wall
shall be provided with such means of ingress to and egress from the
enclosure within the area surrounded by or protected by said retaining
wall as may be required by the Fire Chief and the Superintendent of
Building and Safety.
No combustible material, other than the oil within the storage
tanks, shall be permitted in or as a part of, any such retaining walls,
provided, however, that evergreen shrubs may be planted to cover the
surface of earthwork retaining walls; provided, further, that wooden
ladders, stairways, ramps, walkways and landings may be erected and
maintained over and upon such retaining wall and within the area surrounded
by such wall.
Every such retaining wall, whether heretofore or hereafter constructed,
shall be maintained at all times so as to be capable of retaining
and so as to retain the maximum content for which it is required by
this Section.
The maximum total storage capacity of any group of tanks located
within a single retaining basin, formed by retaining walls, shall
not exceed eighteen thousand barrels. Suitable provisions, satisfactory
to the Fire Chief and the Superintendent of Building and Safety, shall
be made in order to effectively drain oil, water, or other effluent
from all areas within the enclosures formed by retention walls, banks
or dikes.
(Ord. 2397 5-5-81)
All tanks shall be electrically grounded by resting directly
upon moist earth, or otherwise be electrically grounded to permanent
moisture in a manner approved by the Fire Chief and the Superintendent
of Building and Safety. All steel work of masonry retaining walls
hereafter constructed, protecting or surrounding any tanks shall be
interconnected and grounded by a method approved by the Fire Chief
and the Superintendent of Building and Safety.
(Ord. 2397 5-5-81)
All sump holes, tanks and storage locations shall be fenced
in a manner satisfactory to the Fire Chief, with not less than No.
9 galvanized wire or chain link fencing. Such fence shall be not less
than six feet high, mounted on steel posts and shall have three strands
of barbed wire around the top, spaced to the satisfaction of said
Fire Chief.
Telephones or suitable alarm systems satisfactory to the Fire
Chief shall be installed and maintained in good working order where
operations are conducted for the production or treatment of oil, gas
or other hydrocarbon substances.
It shall be unlawful for any person to collect, keep, store,
hold or handle any "crude oil" in any tank or group of tanks, unless
there is provided therefor a foam protection system for both tank
fire extinguishment and ground fire extinguishment. The type and amount
of such foam protection system shall be subject to the approval of
the Fire Chief; provided, however, that when such tank or group of
tanks are horizontal cylindrical tanks, or spheroidal tanks, or have
pontoon type floating roofs or vapor recovery systems installed, maintained
and operated thereon so that the vapors within such tanks will exceed
the explosive limits for petroleum vapor-air mixtures, foam shall
not be required except in the quantity necessary for extinguishing
ground fires for such tanks as provided in this Article.
Whenever, in the opinion of the Fire Chief, an unusually hazardous
condition exists by reason of the failure to keep and maintain any
tank, group of tanks, or other apparatus or facility used to hold,
handle or process oil, in a safe and proper condition as required
by the provisions of this Article, or by reason of the failure to
keep the premises clean on which the same is situated, as provided
in this Article, or by reason of the failure to employ practices in
the operation of the same in conformity with the requirements of this
Article, the Fire Chief may require foam to be provided for such tank,
group of tanks, apparatus or facility, in the quantity required by
the provisions of this Article for extinguishing ground fires for
a tank with an oil-surface area equivalent to the ground surface area
occupied by such tank, group of tanks, apparatus or facility. The
provisions of this Section may be applied regardless of whether the
oil in such tank, group of tanks, apparatus or facility is crude oil
or refined oil.
Whenever foam protection is required for tank fire extinguishment
for any single tank there shall be provided for such purpose the following
quantities of foam for each square foot of oil-surface area in such
tank, according to the method of applying such foam, to wit:
(1) Non-splash
application: thirty gallons
(2) Foam
nozzle stream application: eighty gallons
(3) Other
types of application: fifty gallons
Whenever foam protection is required for tank fire extinguishment
for any group of tanks consisting of not more than two tanks, there
shall be provided for such purpose the quantity of foam required by
the provisions of this Article for a tank having the same oil-surface
area as that of the largest tank in such group.
Whenever foam protection is required for tank fire extinguishment
for any group of tanks consisting of more than two tanks, there shall
be provided for such purpose the quantity of foam required by the
provisions of this Article for a tank having the same oil surface
as that of the largest tank in such group, plus twenty percent of
the quantity required by said Section for a tank having the same oil-surface
area as that of the second largest tank in such group, plus ten percent
of the quantity required by said Section for a tank having the same
oil-surface area as the total oil-surface area of all of the remaining
tanks in said group; provided, however, that if the tanks in any such
group are separately diked, or otherwise surrounded to the satisfaction
of the Fire Chief, or are separated, shell to shell, a distance not
less than the diameter of the largest tank, the quantity of foam required
for tank fire extinguishment shall be only such amount as is required
by this Article for a tank having the same oil-surface area as that
of the largest tank in such group.
Whenever foam protection for the purpose of ground fire extinguishment
is required, there shall be provided for such purpose (in addition
to the quantity of foam required by the provisions of this Article
for tank fire extinguishment) the following quantity of foam, according
to the total oil-surface area for which such protection is required,
to wit:
TOTAL OIL SURFACE AREA TO BE PROTECTED
|
QUANTITY OF FOAM
|
---|
Less than 2,000 sq. ft.
|
5,500 gals.
|
2,000 to 3,000 sq. ft.
|
10,000 gals.
|
over 3,000 sq ft.
|
20,000 gals.
|
In determining whether an adequate supply of foam solutions
is being maintained to create the foam required (whether for tank
fires or for ground fires) it shall be considered that eight gallons
of foam is produced by the combining of one pound of Underwriters
Approved dry foam chemicals with one gallon of fresh water at sixty
degrees Fahrenheit, or the combining of one-half gallon each of A
solution and B solution; provided, however, that all such solutions
shall be so maintained that the production of not less than six gallons
of foam results from the combining of one-half gallon each of A and
B solutions at a temperature of sixty degrees Fahrenheit.
(a) Each
person required to provide foam protection shall provide means of
producing and applying such foam at a rate based on the method of
applying foam to the oil-surface. A non-splash applicator shall be
any device, portable or fixed to the tank shell, by which foam can
be applied under severe fire conditions onto the oil-surface regardless
of depth, at a velocity not in excess of that acquired by a free downward
fall of foam through a vertical distance of four feet. When such non-splash
application is employed, a rate of three-eighth gallons per minute
of foam for each square foot of normal oil-surface of the largest
tank protected by the system will be acceptable.
(b) When
other than non-splash applicators, excepting foam nozzle streams are
employed, a rate of three-quarters gallon per minute per square foot
of the largest tank protected shall be available.
(c) When
foam nozzle streams are employed, the application rate shall be one
gallon per minute per square foot of normal oil surface of the largest
tank protected; provided, however, that hose streams shall not be
the sole means available for applying foam onto a tank having more
than one thousand square feet of normal oil-surface.
(d) No application
rate, whether for tank fires or ground fires, shall be less than three
hundred gallons per minute of foam regardless of lesser area requirements
provided herein.
A separate license and a separate permit must be procured under
this Article for each individual oil well or gas well. Notwithstanding
the provisions of this Article, the permit fee for each such well
shall be $1,000.00 which shall be paid at or before the time of the
issuance of such permit.
(Ord. 1267 1-1-56)