Existing Materials. 1. Unreinforced masonry walls. Unreinforced masonry walls analyzed in accordance with this chapter may provide vertical support for roof and floor construction and resistance to lateral loads.
All units of both bearing and non-bearing walls shall be laid with full shoved mortar joints; all head, bed and wall (collar) joints shall be solidly filled with mortar; and the bonding of adjacent wythes of multi-wythe walls shall be as follows:
The facing and backing shall be bonded so that not less than 4 percent of the wall surface of each face is composed of headers extending not less than four inches into the backing. The distance between adjacent fulllength headers shall not exceed 24 inches either vertically or horizontally. In walls where a single header does not extend through the wall, headers from the opposite sides shall overlap at least four inches, or headers from opposite sides shall be covered with another header course overlapping the header below at least four inches.
Wythes of walls not bonded as described above shall be considered as veneer. The veneer wythe shall not be included in the effective thickness used to calculate the height-to-thickness ratio and the shear capacity of the wall.
Tension stresses due to seismic forces normal to the wall may be neglected if the wall does not exceed the height-to-thickness ratio set forth in Table A1-F and the in-plane shear stresses due to seismic loads set forth in Table A1-I. If the wall height-to-thickness ratio exceeds the specified limit, the wall may be supported by vertical bracing members designed to satisfy the requirements of the 1985 Uniform Building Code. The deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness.
Exception: The wall may be supported by flexible bracing members designed in accordance with Section A106(b) of this chapter if the deflection at design loads is not less than one-quarter nor more than one-third of the wall thickness at the level under consideration.
All vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half the unsupported height of the wall nor ten feet, whichever is less.
The wall height may be measured vertically to bracing elements other than a floor or roof. Spacing of bracing elements and wall anchors shall not exceed six feet. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by components of vertical displacements of the floor or roof.
2. | Veneer. Veneer shall be anchored with approved anchor ties, conforming to the required design capacity specified in Section 3304(c) of the 1985 Uniform Building Code, and placed at a maximum spacing of 24 inches. |
Exception: Existing veneer anchor ties may be acceptable provided the ties are in good condition and conform to the minimum size, maximum spacing and material requirements as indicated below. The veneer anchor ties shall be corrugated galvanized iron strips not less than one inch in width, eight inches in length and one-sixteenth of an inch in thickness and shall be located and laid in every alternate course in the vertical height of the wall at a spacing not to exceed 17 inches on center horizontally. As an alternate, the spacing may be every fourth course vertically at a spacing not to exceed nine inches on center horizontally.
The existence and condition of existing veneer anchor ties shall be verified as follows:
1. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a report to the Chief Building Inspector for approval as a part of the structural analysis.
2. The veneer in a selected area shall be removed to expose a representative sample of ties (not less than four) for inspection by the Chief Building Inspector.
3. Existing roof, floors, walls, footings, and wood framing. Existing materials, including wood shear walls, may be used as a part of the lateral load resisting system, provided that stresses in these materials do not exceed the values shown in Table No. A1-G.