2.
|
Veneer. Veneer shall be anchored with approved anchor ties,
conforming to the required design capacity specified in Section 3304(c)
of the 1985 Uniform Building Code, and placed at a maximum spacing
of 24 inches.
|
TABLE NO. A1-F
ALLOWABLE VALUE OF HEIGHT-THICKNESS (h/t) RATIO OF UNREINFORCED
MASONRY WALLS WITH MINIMUM QUALITY MORTAR12
| ||
---|---|---|
|
BUILDINGS WITH COMPLYING CROSS WALLS
|
ALL OTHER BUILDINGS
|
One Story Building Walls
|
13 — 16345
|
13
|
First Story of Multi-Story Buildings
|
16
|
15
|
Walls in the Top Story of Multi-Story Buildings
|
9 — 14345
|
9
|
All Other Walls
|
16
|
13
|
1
|
Minimum mortar quality shall be determined by laboratory testing
in accordance with this chapter.
|
2
|
This table is not applicable to buildings classified as essential
facilities. Such building must be analyzed in accordance with Section
A106.
|
3
|
The minimum mortar shear strengths required in the following
footnotes 4 and 5 shall be that shear strength without the effect
of axial stress in the wall at the point of the test.
|
4
|
The larger height-to-thickness ratio may be used where mortar
shear tests in accordance with Section A107(d) establish a minimum
mortar shear strength of not less than 100 psi or where the tested
mortar shear strength is not less then 60 psi and a visual examination
of the vertical wythe-to-wythe wall joint (collar joint) indicates
not less than 50 percent mortar coverage.
|
5
|
Where a visual examination of the collar joint indicates not
less than 50 percent mortar coverage and the minimum mortar shear
strength when established in accordance with Section A107(d) is greater
than 30 psi but less than 60 psi, the allowable height-to-thickness
ratio may be determined by linear interpolation between the larger
and smaller ratio values in direct proportion to the mortar shear
strength.
|
TABLES NO. A1-H
ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING
CONSTRUCTION
| |
---|---|
New Materials or Configuration of Materials1
|
Allowable Values
|
1. Horizontal Diaphragms
Plywood sheathing applied directly over existing straight sheathing
with ends of plywood sheets bearing on joists or rafters and edges
of plywood located within the center 1/3 of individual sheathing boards.
|
Same as specified in Table 25-J of the 1985 Uniform Building
Code for blocked diaphragms.
|
2. Shear Walls
|
Same as values specified in Table
|
a. Plywood sheathing applied directly over
existing wood studs. (No value shall be given to plywood applied over
existing plaster or wood sheathing boards).
|
No. 25-K of the 1985 UBC for shear walls.
|
b. Dry wall or plaster applied directly over
existing wood studs.
|
75 percent of the values specified in Table No. 47-I of the
1985 UBC.
|
c. Dry wall or plaster applied to plywood
sheathing over wood studs.
|
One-third of the values specified in Table No. 47-I of the 1985
UBC.
|
3. Shear Bolts
Shear bolts and shear dowels embedded a minimum of 8 inches
into unreinforced masonry walls. Bolt centered in a 2-1/2 inch diameter
hole with drypack or non-shrink grout around the circumference of
the bolt.13
|
133 percent of the values for plain masonry specified in Table
No. 24-J of the 1985 UBC. No values larger than those given for 3/4
inch diameter bolts shall be used.
|
4. Tension Bolts
Tension bolts and tension dowels extending entirely through
URM walls secured with bearing plates on far side of wall with at
least 30 square inches of area.234
|
1200 pounds per bolt.
|
5. Combination Shear and Tension Wall Anchors
|
|
(a) Bolts extending to the exterior face of
the wall with a 2-1/2 inch round plate under the head. Install as
specified for shear bolts. Spaced not closer than 12 inches on centers.123
|
600 lbs. per bolt for tension4. See
Item 3 (Shear Bolts) for shear values.
|
(b) Bolts or dowels extending to the exterior
face of the wall with a 2-1/2 inch round plate under the head and
drill at an angle of 22-1/2 degrees to the horizontal. Install as
specified for shear bolts.123
|
1200 lbs. per bolt or dowel for tension4. See Item 3 for shear values.
|
(c) Through bolt with bearing plate for tension
per Item 4. Combined with minimum 8 inch grouted section for shear
per Item 3.
|
See Item 4 (Tension Bolts) for tension values4. See Item 3 for shear values.
|
6. Infilled Walls
Reinforced masonry infilled openings in existing unreinforced
masonry walls with keys or dowels to match reinforcing.
|
Same as values specified for unreinforced masonry walls in this
chapter.
|
7. Reinforced Masonry
Masonry piers and walls reinforced as specified in Chapter 24
of the 1985 Uniform Building Code.
|
Same as values specified in Table No. 24-B of the Uniform Building
Code. 1985
|
8. Reinforced Concrete
Concrete footings, walls and piers reinforced as specified in
Chapter 26 and designed for tributary loads.
|
Same as values specified in Chapter 26 of the 1985 Uniform Building
Code
|
9. Existing Foundation Loads
Foundation loads for structures exhibiting no evidence of settlement.
|
Calculated existing foundation loads due to maximum dead load
plus live load may be increased by 25 percent and may be increased
50 percent for dead load plus seismic loads required by this chapter.
|
1
|
Bolts and dowels to be tested as specified in Section A107.
|
2
|
Bolts and dowels to be 1/2-inch diameter minimum.
|
3
|
Drilling for bolts and dowels shall be done with an electric
rotary drill. Impact tools shall not be used for drilling holes or
tightening anchor and shear bolt nuts.
|
4
|
Allowable bolt and dowel values specified are for installations
in minimum three wythe wall. For installations in two wythe walls
use 50 percent of the value specified, except that no value shall
be given to tension bolts that do not extend entirely through the
wall and are secured with bearing plates on the far side.
|
TABLE NO. A1-J
ALLOWABLE VALUES FOR EXISTING MATERIALS TO BE USED ONLY IN THE
COMPUTATION OF THE DEMAND CAPACITY RATIO DESIGN CHECK
| |
---|---|
Existing Materials or Configuration of Materials1
|
Allowable Values
|
1. Horizontal Diaphragms
|
|
a. Roofs with straight sheathing and roofing applied directly
to the sheathing.
|
100 lbs. per foot for seismic shear.
|
b. Roofs with diagonal sheathing and roofing applied directly
to the sheathing.
|
250 lbs. per foot for seismic shear.
|
2. Cross Walls2
|
Per Side:
|
a. Plaster on wood or metal lath.
|
200 lbs. per foot for seismic shear.
|
b. Plaster on gypsum lath.
|
175 lbs. per foot for seismic shear.
|
c. Gypsum wall board unblocked edges.
|
75 lbs. per foot for seismic shear.
|
d. Gypsum wall board blocked edges.
|
125 lbs. per foot for seismic shear.
|
1
|
Materials must be sound and in good condition.
|
2
|
For cross walls, values of all materials may be combined, except
the total combined value shall not exceed 300 lbs. per foot for seismic
shear.
|
TABLE NO. A1-K
ALLOWABLE VALUES FOR NEW MATERIALS USED IN CONJUNCTION WITH
EXISTING CONSTRUCTION MATERIALS TO BE USED ONLY IN THE COMPUTATION
OF THE DEMAND CAPACITY RATIO DESIGN CHECK
| |
---|---|
New Materials or Configuration of New and Existing Materials1
|
Allowable Values
|
1. Horizontal Diaphragms
|
|
a. Plywood sheathing applied directly over existing straight
sheathing with ends of plywood sheets bearing on rafters and edges
of plywood located on the center of individual sheathing boards.
|
225 lbs. per foot for seismic shear.
|
2. Cross Walls
|
|
a. Plywood sheathing applied directly over existing wood
studs. No value shall be given to plywood applied over existing plaster
or wood sheathing.
|
1.33 times the values specified in Table 25-K of the 1985 UBC.
|
b. Drywall or plaster applied directly over existing wood
studs.
|
100 percent of the values specified in Table 47-I of the 1985
UBC.
|
1
|
Materials must be sound and in good condition.
|
2
|
For cross walls values of all materials may be combined, except
the total combined shear value shall not exceed 300 lbs. per foot
for seismic shear.
|
FIGURE A1-L
| |
1.
|
Region of demand/capacity ratios where cross walls may be used
to increase H/T ratios.
|
2.
|
Region of demand/capacity ratios where H/T ratios of "with cross
walls" may be used whether or not they are present.
|
3.
|
Region of demand/capacity ratios where H/T ratios of "all other
buildings" must be used even if cross walls are present.
|
Demand/capacity ratio = 0.33 Wd / 2 vuD or 0.33 Wd / 2 vuD +
Vc.
|