Above-grade walls | Type: mass wall if proposed wall is mass; otherwise wood frame | As proposed |
Gross area: same as proposed | As proposed |
U-factor: as specified in Table N1102.1.4 | As proposed |
Solar absorptance = 0.75 | As proposed |
Remittance = 0.90 | As proposed |
Basement and crawl space walls | Type: same as proposed | As proposed |
Gross area: same as proposed | As proposed |
U-factor: from Table N1102.1.4, with insulation layer on interior side of walls | As proposed |
Above-grade floors | Type: wood frame | As proposed |
Gross area: same as proposed | As proposed |
U-factor: as specified in Table N1102.1.4 | As proposed |
Ceilings | Type: wood frame | As proposed |
Gross area: same as proposed | As proposed |
U-factor: as specified in Table N1102.1.4 | As proposed |
Roofs | Type: composition shingle on wood sheathing | As proposed |
Gross area: same as proposed | As proposed |
Solar absorptance = 0.75 | As proposed |
Emittance = 0.90 | As proposed |
Attics | Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area | As proposed |
Foundations | Type: same as proposed | As proposed |
Foundation wall area above and below grade and soil characteristics: same as proposed | As proposed |
Opaque doors | Area: 40 ft2 | As proposed |
Orientation: North | As proposed |
U-factor: same as fenestration from Table N1102.1.4 | As proposed |
Vertical fenestration other than opaque doors | Total areab = 15% of the conditioned floor area | As proposed |
Orientation: equally distributed to four cardinal compass orientations (N, E, S & W) | As proposed |
U-factor: as specified in Table N1102.1.4 | As proposed |
SHGC: as specified in Table N1102.1.2 except that for climates with no requirement (NR) SHGC = 0.40 shall be used | As proposed |
Interior shade fraction: 0.92 - (0.21 x SHGC for the standard reference design) | 0.92 - (0.21 x SHGC as proposed) |
External shading: none | As proposed |
Skylights | None | As proposed |
Thermally isolated sunrooms | None | As proposed |
Air exchange rate | Air leakage rate of 5 air changes per hour in Climate Zones 4 The mechanical ventilation rate shall be in addition to the air leakage rate and the same as in the proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1) where: CFA = conditioned floor area Nbr = number of bedrooms Energy recovery shall not be assumed for mechanical ventilation Air leakage rate of 5 air changes per hour in at a pressure of 0.2 | For residences that are not tested, the same air leakage rate as the standard reference design. For tested residences, the measured air exchange ratea. The mechanical ventilation rateb shall be in addition to the air leakage rate and shall be proposed. |
Mechanical ventilation | None, except where mechanical ventilation is specified by the proposed design, in which case: Annual vent fan energy use: kWh/yr = 0.03942 x CFA + 29.565 x (Nbr + 1) where: CFA = conditioned floor area Nbr = number of bedrooms | As proposed |
Internal gains | IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit) | Same as standard reference design. |
Internal mass | An internal mass for furniture and contents of 8 pounds per square foot of floor area | Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementc but not integral to the building envelope or structure. |
Structural mass | For masonry floor slabs, eighty percent (80%) of floor area covered by R-2 carpet and pad, and twenty percent (20%) of floor directly exposed to room air | As proposed |
For masonry basement walls, as proposed, but with insulation required by Table R402.1.4 located on the interior side of the walls | As proposed |
For other walls, for ceilings, floors, and interior walls, wood frame construction | As proposed |
Heating systemsd, e | Fuel type: same as the proposed design Efficiencies: Electric: air-source heat pump with prevailing Federal minimum standards Nonelectric Furnaces: natural gas furnace with prevailing Federal minimum standards Nonelectric boilers: natural gas boiler with prevailing Federal minimum standards Capacity: sized in accordance with Section N1103.7 | As proposed |
Cooling systemsd, f | Fuel type: electric Efficiency: in accordance with prevailing Federal minimum standards Capacity: sized in accordance with Section N1103.7 | As proposed |
Service water heatingd, e, f | Fuel type: same as proposed design Efficiency: in accordance with prevailing Federal minimum standards Use: gal/day = 30 + 10 x Nbr Tank temperature: 120° F. | As proposed Same as standard reference |
Thermal distribution systems | Duct insulation: from Section N1103.2.1 A thermal distribution system efficiency (DSE) of 0.88 shall be applied to both the heating and cooling system efficiencies for all systems other than tested duct systems. For tested duct systems, the leakage rate shall be 4 cfm (113.3 L/min) per 100 ft2 (9.29 m2) of conditioned floor area at a pressure of differential of 0.1 inches w.g. (25 Pa) | As tested or specified in Table R405.5.2(2) if not tested. Duct insulation shall be as proposed. |
Thermostat | Type: Manual, cooling temperature setpoint = 75° F.; Heating temperature setpoint = 72° F. | Same as standard reference |