Table 234-112: Overview of Project Classification and Pump Testing Components | ||||
|---|---|---|---|---|
Test Component | Class 1 TDD < 1,000 gpd REQUIRED | Class 2 1,000 < TDD < 2,000 gpd REQUIRED | Class 3 2,000 < TDD < 10,000 gpd REQUIRED | Class 4 TDD > 10,000 gpd REQUIRED |
Baseline Assessment Phase | 24 hours required, up to 1 week recommended | Same as Class 1 | Same as Class 1 | Same as Class 1 |
Peak Demand Phase | ||||
Flow Rate & Duration? (see below) | ||||
Residential:* | Peak demand rate = (# baths) (3 gal/min) Duration = (0.66) (TDD/peak demand rate) TDD = 100 + (# bedrooms)(100 gal/day) See § 234-112E(2)(a) | Same as Class 1 residential | Applicant may choose the Class 1 residential method, or the nonresidential method | Applicant may choose the Class 1 residential method, or the nonresidential method |
Nonresidential:* | Dependent on project (requires water use analysis report with project demand model) See § 234-112E(2)(c) | Same as Class 1 nonresidential | Same as Class 1 nonresidential | Same as Class 1 nonresidential |
Recording? | Recording - every 5 seconds for the first 2 minutes and then every 20 seconds for the remainder of the duration. Every 20 seconds for any observation well. | Same as Class 1 | Same as Class 1 | Same as Class 1 |
Constant Head Phase | ||||
Flow Rate and Duration? | Peak demand rate > constant head pump rate > TDD 2 hour min, 8 hour max duration | Peak demand rate > constant head pump rate > TDD 16 hour duration max | Peak demand rate > constant head pump rate > TDD 48 hour duration max | Peak demand rate > constant head pump rate > TDD 72 hour duration max |
Recording? | Record every 30 minutes | Same as Class 1 | Same as Class 1 | Same as Class 1 |
Recovery Phase | Flow rate = 0 (pumping stops) and well observed for 24 hours to determine if recovery of total drawdown occurs and to within 0.5 foot of baseline levels | Same as Class 1 | Same as Class 1 | Same as Class 1 |
Extended Monitoring | Recommended only Flow rate > TDD with operating withdrawal schedule for 45 days then mini pump test for 2 days | Same as Class 1 | Same as Class 1 except required when added drawdown in observation wells is greater than 1 foot but less than 2 feet | Same as Class 3 |
NOTES: | |
|---|---|
* | Swimming pools [requires external source of water for filling new pools and filling at beginning of each season, as set forth in § 234-112E(2)(d)]. |
A.
A groundwater pump test must be conducted at a sufficient rate and duration to determine aquifer characteristics such as transmissivity and storage coefficient. Groundwater pump tests are required for all well classes. As part of the pump test, test wells and observation wells (when observation wells are required as part of the test) shall be monitored as further provided in this section. All phases of pump testing and reporting required below may be completed by a well driller. Other analysis and reports required by this article shall be prepared by a qualified engineer or hydrogeologist.
B.
The pump test consists of the following phases. The first four phases are required and the fifth is recommended:
C.
General pump test standards.
(1)
In the event that the preliminary hydrogeologic evaluation indicates that a surface water and/or groundwater divide separates the lot in question, a groundwater pump test will be required for each side of the divide.
(2)
The pump test(s) must be conducted at the location(s) most representative of site geologic conditions and locations most effective for evaluating the potential impacts to proximate users of the groundwater resource. Location of Class 1 wells shall also take into consideration convenience of location to proposed improvements. All wells shall comply with PaDEP/BCHD isolation requirements. The applicant's decision shall be reviewed by the Township as part of its review of the applicant's application materials. If it is not possible to meet objectives, then the applicant shall choose a location(s) to optimize location, subject to Township approval.
(3)
Section 234-114 of this article outlines the requirements and procedures for notification of owners of existing wells and other groundwater sources (e.g., springs) within the neighbor notification distance. Inadequate notification will require the pump test to be repeated after new notice.
(4)
Hydraulic fracturing (aka hydrofracking, hydrofracting).
(a)
Any applicant proposing to use hydraulic fracturing or a similar means to increase the yield of any well must notify the Township in advance.
(b)
All relevant state, BCHD, DRBC, and/or federal permits for the use of hydraulic fracturing or other means being used to increase the well's yield must also be presented to the Township.
(c)
The applicant must also measure the amount of water put into the well to increase the well's yield, and provide that information in its post-test report along with a comparison to the amount of water removed from the well. Any water put into the well must be potable, unless otherwise approved by the Township.
(d)
The applicant must also, prior to commencing the pump test, remove the volume of water or other substance put into the well to increase the well's yield and allow the well to stabilize for 24 hours.
(5)
Precipitation.
(a)
No required phase of the pump test shall be conducted during a precipitation event or events in which total precipitation equals or exceeds 0.5 inch, or when any of the aforementioned precipitation events are forecast. With the exception of the following, a violation of this provision will require repeating the required phases of the pump test:
[1]
If the length of the required phases of the pump test, when considered together, exceeds three days, precipitation exceeding 0.5 inch per day after the third day will not result in failure of the pump test as a whole. However, the applicant's analysis must factor in the potential groundwater recharge from precipitation.
[2]
If over 0.5 inch of precipitation occurs during the recovery phase, the applicant must either repeat the pump test beginning after a reasonable assessment phase, or provide precipitation amounts and technical documentation to show that the precipitation did not recharge the aquifer during the recovery and impair the test results. The requirement to repeat the test shall be at the Township's discretion if adequate documentation is not provided to verify that the test results were not impaired by precipitation. The extended monitoring phase shall be exempt from this requirement. For applicants required to undertake extended monitoring, each applicant shall monitor precipitation amounts and provide such data as part of its final analysis.
(b)
Precipitation must be recorded with a National Weather Service acceptable rain gauge on site during all phases of testing and measurements for each day must be included in the hydrogeologic report.
(c)
Precipitation shall include both snowfall and snowmelt.
(6)
Any pump test that must be repeated, restarted, or reconducted at a reduced demand must satisfy all the requirements of this article.
(7)
It is the applicant's responsibility to collect sufficient data to determine hydrogeologic conditions and to ensure that any exogenous influences can be fully characterized, such as barometric pressure changes or off-site pumping. Barometric measurements and additional water-level measurements can be made by the applicant to evaluate the change in water levels resulting from barometric pressure changes and/or influences from off-site pumping. If an applicant has insufficient data to assess these influences, it must repeat all required phases of the pump test. The earlier failure(s) will be taken into account during application review.
(8)
During all required phases of the pump test, water must not be withdrawn from any observation well installed by the applicant. All testing must be repeated if there are insufficient observation wells as per this article or if an observation well installed by the applicant is pumped during any required phase of the pump test.
(9)
For neighboring wells that have been volunteered for observation, the well need not be fully shut down, including pump turned off, for the duration of required pump testing phases. However, lack of use is preferred. If neighboring volunteered observation wells are not fully shut down for any or all required phases of the pump test, the applicant shall obtain available drawdown data from the volunteered observation wells, to differentiate neighboring observation well usage from the impacts of the applicant's testing.
(10)
Depth-to-water measurements shall be made at the beginning and end of each pump testing phase.
(11)
General recording and equipment requirements.
(a)
Test well(s).
[1]
Measuring equipment.
[a]
A calibrated meter(s) must be used to accurately measure the total volume of water pumped from the test well(s) and provide a digital reading of the flow rate. The total meter reading must be recorded prior to the start of peak demand phase, at the end of the peak demand phase, and at the end of the constant head phase. Calibration certificates for the meter(s) must be submitted with the final report. If the meter(s) has not been calibrated within one year of the testing date, the pump test must be repeated.
[b]
Calibrated loggers must be used to monitor the water level in the test well(s) throughout all phases of the pump test. Calibration certificates for the meter(s) must be submitted with the final report. If the meter(s) has not been calibrated within one year of the testing date, the pump test must be repeated.
[2]
Pumping equipment. All pumping equipment must have sufficient check valves to prevent backflow into the well from the water in the piping once the pump is shut down. If water drains back into the well from the piping, the test will be deemed to have failed and all required components of the pump test must be repeated.
(b)
Observation wells. Observation wells shall be required to use a calibrated logger to measure water-level drawdown during the pump test and for the calculation of aquifer hydraulic characteristics. Calibration certificates for the meter(s) must be submitted with the final report. If the meter(s) has not been calibrated within one year of the testing date, the pump test must be repeated.
(12)
General data monitoring requirements. All test and observation well(s) shall be monitored to determine and evaluate water-level drawdown, calculate aquifer characteristics, determine the radius of influence, determine added drawdown in observation wells, and predict and/or observe the effect of long-term pumping in the test well(s) on water levels in existing and future wells.
(13)
General pumping requirements.
(a)
If the flow rate varies by more than 10%, the entire test shall be repeated. The initial failure(s) will be taken into account during application review.
(b)
If the pump shuts down during any pumping phase, the entire test must be repeated. The test must be restarted at the beginning of the baseline assessment phase.
(c)
If water levels in the test well and/or observation wells exceed the measurement capacity of the devices used for measuring changes in water levels and measurements are not recorded with other devices in accordance with the requirements of this article, the test must be repeated.
(d)
If the pumping data indicate a change in aquifer transmissivity as a result of fracture dewatering, all analyses of the contributing area and impacts to neighbors, streams, and wetlands must be conducted using the lower value of aquifer transmissivity. If this lower aquifer transmissivity indicates that the anticipated demand cannot be supported by the aquifer beneath the site, the applicant will need to review and adjust the proposed demand and/or extent of development. The applicant's analysis must use transmissivity data obtained during the pump test.
(e)
The discharge from the test well(s) shall be directed so that it leaves the lot in question without infiltrating to the aquifer and/or impacting the observation wells. The pumped water discharge location must be at least 200 feet downgradient from the test well, whenever possible, and shall not adversely impact adjoining properties. The Township may authorize the use of tanker trucks to contain the water if discharge is not possible due to lot or site conditions. Any and all permits required by the PaDEP and/or local authorities for the discharge of pumped water must be obtained prior to starting the test.
D.
Baseline assessment phase.
(1)
Baseline assessment phase testing shall commence no earlier than three days after the well is drilled so that water levels may stabilize.
(2)
The pumping equipment must be installed in the pumping well at least 24 hours prior to the start of the baseline assessment phase.
(3)
During the baseline assessment phase, a minimum of 24 hours of recording the water level with a five-minute frequency is required. Longer baseline assessment periods, such as one week, may be undertaken to assess ambient fluctuations in the water level. It is the applicant's responsibility to collect sufficient data to determine background conditions and to ensure that antecedent influences can be fully characterized.
E.
Peak demand phase. The purpose of the peak demand phase is to demonstrate that the well can provide the water required for peak usage.
(1)
Additional standards. On the day that the peak demand phase begins, water levels shall be collected from the test and observation wells to determine static water level conditions prior to the start of the phase.
(a)
Water levels in observation wells on neighboring properties should be allowed to stabilize within 0.5 foot of static prior to the start of pumping in the test well.
(b)
For any observation well which has been pumped within the 24 hours preceding the peak demand phase, two depth-to-water measurements, at least one hour apart, shall be collected to assess if the well has fully recovered prior to the start of pumping in the test well.
(2)
Peak demand phase duration and water amount.
(a)
Class 1 and 2 residential projects.
[1]
The flow rate shall be calculated as follows:
Peak demand rate = (no. of bathrooms)(three gallons/minute)
[2]
Total daily demand (TDD) must be calculated to determine the duration of the phase. The calculation shall be as follows:
TDD = 100 + [(no. of bedrooms)(100 gallons/day/bedroom)]
The first bedroom in every home shall be assumed to have two people in it (i.e., 200 gal/day). Every additional bedroom is assumed to have one person in it.
[3]
The duration of the phase shall be calculated as follows:
Duration = (0.66)(TDD/peak demand rate)
(b)
Class 3 and 4 residential projects. These projects may choose between the Class 1 and 2 residential method, or the method specified for nonresidential projects.
(c)
All nonresidential projects, regardless of class.
[1]
All nonresidential projects must submit a water use analysis report with a project peak demand model and must include, at a minimum, a definition of duration and peak demand for the proposed project. The applicant shall identify the means used to determine peak demand, and how its model, duration, and demand compare to established reference materials for nonresidential uses [e.g., historic water meter records from equivalent uses/facilities, 25 Pa. Code Ch. 73 on-lot sewage design flow rates, published literature; PaDEP Public Water Supply Manual, most recent version of Guide for Determination of Required Fire Flow by the Insurance Services Office (ISO); American Water Works Association Standards and Manuals].
[2]
The water use analysis report with project peak demand model must be approved by the Township in advance of the pump test being conducted. As part of its review, the Township may refer to published estimates of water usage to assist it in evaluating the applicant's proposal.
(d)
Swimming pools regardless of project type. Initial filling of new swimming pools, and filling of swimming pools at the beginning of each new season, shall be completed from a source other than an on-site water supply well per Chapter 222. "Top-offs" of already-filled pools from on-site water supply wells are not prohibited, in accordance with Article VI, § 228-26.
(3)
Recording protocol for all projects.
(a)
Recordings from the test well shall be taken every five seconds for the first two minutes, and then every 20 seconds for the remainder of the duration of the phase.
(b)
Recordings from each observation well shall be taken every 20 seconds for the duration of the phase.
(c)
Confirmation of meter calibration. A calibrated bucket and stopwatch or a properly sized orifice and manometer system constructed in accordance with the Layne & Bowler protocol must be used to confirm the accuracy of the meter readings. The calibrated bucket and stopwatch method can be used for flow rates less than or equal to 10 gallons per minute. For flow rates in excess of 10 gallons per minute, an orifice and manometer system must be used to determine the flow rate. The flow rate as measured with the bucket/stopwatch shall be recorded periodically to verify consistent flow rate. Orifice and manometer must be recorded at the same frequency and duration as specified for recordings from the test well using a meter. All measurements along with the clock time, and the elapsed time since the peak demand phase started, must be included in the final report.
(4)
If the well cannot be pumped at the required flow rate for the required duration, as calculated by the applicant in accordance with this article, the applicant fails the peak demand phase.
F.
Constant head phase. This phase assesses the aquifer's ability to sustainably supply water on a daily basis.
(1)
General requirements.
(a)
This phase must begin immediately after the peak demand phase without cessation of pumping.
(b)
To obtain a constant head pump rate, the flow rate shall be incrementally decreased (or stepped down) from the peak demand rate until a constant head is achieved in test well. A constant head is achieved when the change in head is less than 0.5 foot for a one-hour period after the cessation of the peak demand phase while the test well is being pumped at a flow rate that is equal to or in excess of the total daily demand, but less than or equal to the peak demand rate. If a constant head is not maintained, the applicant fails the constant head phase.
(c)
When stepping the flow rate down, the flow rate must be incrementally reduced such that the water level in the well remains within 10 feet of the depth to water measurement made at the end of the peak demand phase. For example, if at the end of the peak demand phase, the water level in the well is 250 feet below ground surface, then for the constant head phase, the water level in the well must be maintained below 240 feet below ground surface. If the water level increases more than 10 feet, then the flow rate should be increased to lower the water level to a point within 10 feet of the depth at which the water level was measured at the end of the peak demand test.
(d)
The required duration of the constant head phase, as specified below, shall begin after the constant head is achieved as set forth above.
(e)
If the water level in the test well or any observation well changes more than 0.5 foot per hour, and/or the flow rate drops below the total daily demand, the applicant fails the constant head phase and must restart the pump test at the baseline assessment phase.
(f)
The applicant may not pump the well at a rate lower than what will maintain a constant head in the well, even if the lower rate is still equal to or in excess of the total daily demand. If the applicant violates this provision, the applicant fails the constant head phase and must restart the pump test at the baseline assessment phase.
(2)
Constant head phase duration and water amount.
(a)
Class 1 and 2 projects. To pass the constant head phase, the applicant must remove a volume of water equal to the TDD while maintaining a constant head pump rate. Duration shall be as follows:
(b)
Class 3 and 4 projects. To pass the constant head phase, the applicant must remove a volume of water equal to twice the TDD while maintaining a constant head pump rate. Duration shall be as follows:
(3)
Recording protocol for all projects. Recordings shall be taken from the test well and each observation well every 30 minutes for the duration of the phase.
G.
Recovery phase. This phase is the final step in the pump test.
(1)
General requirements.
(a)
All pumping must cease, after which recovery in the test well and all observation wells shall be monitored.
(b)
Full recovery of total drawdown and to within 0.5 foot of baseline assessment phase conditions must be obtained in all wells.
(c)
If such recovery is not obtained within 24 hours of pumping cessation, the well fails the test.
(2)
Recording protocol for all projects.
H.
Extended monitoring phase.
(1)
The extended monitoring phase is optional except for Class 3 and 4 applicants when the pumping test results in added drawdown of greater than one foot but less than two feet in any observation well.
(2)
The extended monitoring phase consists of the following components, which may be completed in any order:
(a)
Forty-five-day period at operating withdrawal schedule.
[1]
The purpose of this phase is to determine whether there is a gradual declining trend due to the withdrawal.
[2]
During this phase, water levels in the test well shall be recorded over a forty-five-day period at a thirty-minute frequency. The well shall be operated on a cycling schedule based on the anticipated total daily demand and, where present, storage tank volume.
(b)
Two-day high-frequency recording ("mini pump test").
[1]
The purpose of this component of testing is to accurately characterize the drawdown/recovery relation of the well and aquifer.
[2]
This test component consists of high-frequency recording every five seconds over two days. Both water level and flow rate must be monitored.
[a]
During the first part of this test, the pump remains on until a constant head is achieved.
[b]
Once a constant head is achieved, the second part of the test begins. The pump must be shut off and head recovery must be observed. This procedure allows for determining the transmissivity and storage properties of the aquifer in the vicinity of the well.
(3)
Analysis of data obtained. The applicant shall compare the data obtained through the extended monitoring phase to expected seasonal water level changes for the local area and the geology in which the test well is proposed. The applicant shall account for measurement noise, and identify to what extent that influences the test results. The applicant shall also determine storage and transmissivity based on data from the mini pump test phase using the Cooper, Bredehoeft, Papadopolos method.
(4)
Observation well monitoring.
(a)
Observation wells installed by the applicant must be monitored for the duration of the entire extended monitoring phase.
(b)
If neighboring wells have been volunteered for observation, they must be monitored unless the neighbors withdraw consent for continued observation during the extended monitoring phase. Retesting is not required if consent is rescinded after the test begins.
I.
Failure standards for observation well added drawdown - required phases of pump test (excluding extended monitoring phase).
(1)
If the added drawdown is measured to be more than one foot, but less than two feet, in any observation well, the applicant's qualified hydrogeologist shall perform another pumping test, but with a modified constant head phase.
(a)
This modified phase shall be conducted at the same flow rate as the initial pumping test. The use of any lower flow rate will result in test failure.
(b)
Duration and yield requirements for modified constant head phase:
[1]
Class 1: test well must be pumped to yield one day of TDD while maintaining a constant head condition. If this cannot be done in eight hours or less from when the modified constant head phase began, the test well fails.
[2]
Class 2: test well must be pumped to yield two days of TDD while maintaining constant head conditions. If this cannot be done in 48 hours or less from when the modified constant head phase began, the test well fails.
[3]
Class 3: test well must be pumped to yield four days of TDD while maintaining constant head conditions. If this cannot be done in 72 hours or less from when the modified constant head phase began, the test well fails.
[4]
Class 4: test well must be pumped to yield four days of TDD while maintaining constant head conditions. If this cannot be done in 96 hours or less from when the modified constant head phase began, the test well fails.
(c)
Further analysis shall also be required by the Township Engineer or an independent qualified hydrogeologist on behalf of the Township, including but not limited to pumping tests of observation wells not volunteered by neighbors.
(2)
If added drawdown of two feet or more is measured in any observation well, then the Township shall not issue an approval or permit and the aquifer will be deemed to have insufficient capacity to support the proposed demand and/or extent of development. The applicant shall review and adjust the proposed demand and/or extent of development and proposed well locations to ensure that added drawdown will not exceed two feet in any observation well.
J.
Review of extended monitoring phase data. If the data shows a declining water level over the period of extended monitoring, after a comparison to expected seasonal water level changes and measurement noise, the Township will make a determination based on the data as to whether the applicant must revise the project or take some other action.