(a)
The National Electrical Code, 2020 Edition, published by the National Fire Protection Association, is expressly referred to and adopted as the electrical code of the city, and by this reference and adoption made a part of this chapter as if fully set forth herein, save and except the following portions hereinafter expressly deleted therefrom, and those specific deletions, amendments, and additions made in subsection (b) of this section. One copy of said National Electrical Code shall be filed and kept in the office of the city clerk.
(b)
The following provisions designated "deletion" are deleted and excepted from, and the following provisions designated "addition" are added to, and the following provisions designated "amendment" are amendments to the provisions of the National Electrical Code, 2020 Edition, adopted by reference as part of the Ketchikan Municipal Code so as to be and become part of the electrical code of the city as so amended:
(1)
Addition. A new subsection (D) is added to Section 110.12 (Mechanical Execution of Work) to read as follows:
(D) All abandoned electrical wiring not terminated in accessible junction boxes must be removed. |
(2)
Addition. Section 230.28 (Service Masts as Supports) Subsection (A) (Strength) is amended by adding a new sentence to the end to read as follows:
All service masts used for support of service drop conductors shall be a minimum of 2" galvanized rigid conduit. |
(3)
Addition. Section 230.28 (Service Masts as Supports) Subsection (B) (Attachment) is amended by adding a new sentence to the end to read as follows:
The use of LB's on riser pipes shall not be permitted. |
(4)
Addition. A new paragraph is added to the end of Section 230.32 (Protection Against Damage) to read as follows:
Underground installations from KPU's facility to the customer's metering point must be installed in conduit. Conduit must be inspected prior to covering. |
(5)
Addition. A new second paragraph is added to Section 230.70(A) (Location) to read as follows:
Inside nearest point of entrance of the service conductors shall mean no more than 2' from the outside of building and/or 2' of raceway (ref. 230.6). A combination meter base/main disconnect type service entrance equipment to facilitate de-energizing the wiring from outside in an emergency shall be installed. Service Equipment must not be under a roof or overhang of greater than 30". Weather head may not be installed under the eaves where the potential exists for the snow to slide off the roof and on to the service or its drops. Meter bases must be mounted on a pole or exterior of the building so that the center of the socket is 6' above finished grade, plus or minus 6", with the exception of underground location as to be readily accessible for inspection, reading, and testing. Any service over 200 Amp will require CT metering. Five-jaw "network" meter bases will be required for 120/208 – Volt single-phase service. 100 Amp is the minimum service size. |
(6)
Addition. A new sentence is added to Section 230.72(A) (General) to read as follows:
Marking shall be with a permanent label. |
(Ord. 2005 § 2, 2025)