The following provisions of the "Referenced Standards," as adopted, Chapter 80 of the California Fire Code are amended as follows:
NFPA 13, 2025 Edition:
7.1.3 System risers. System risers shall be located in fire control rooms of the protected premises with an exterior door. The door shall be labeled FIRE CONTROL ROOM in six (6) inch high letters.
NFPA 13D, 2025 Edition:
7.6 Alarms. Water flow switches shall be connected to smoke alarms in such a way that flow detection will cause all required smoke alarms to sound.
7.8 Multipurpose and Passive Purge.
7.8.3 The fire sprinkler system shall provide a minimum 1/2 inch NPT capped or plugged connection at all the water closets to facilitate water circulation.
7.8.5 A modified passive purge system shall be installed.
8.5.5.1.1. Fuel Fired Equipment. Where fuel fired equipment is located above or on the same level but not within an occupied area of the dwelling unit, a pilot head shall be installed above and in the vicinity of the equipment.
8.3.12 Attached Garages. Attached garages, or other structures which are attached in any manner shall be protected with a sprinkler system. They shall have quick response fire sprinklers spaced to provide a maximum of one hundred thirty square feet (130 SF).
NFPA 13R, 2025 Edition:
6.11.2 Fire department connections (FDC). FDC's shall be at least one two and one half (2 1/2) inch connection.
NFPA 24, 2025 Edition:
5.9.5.1 Fire Department Connections. Fire department connections shall be on the street side of buildings, located within forty (40) feet of a fire hydrant and immediately adjacent to an approved access road.
NFPA 72, 2025 Edition:
10.4.3.1 Fire Alarm Control Unit Locations. Fire alarm control units shall be installed in Fire Control Rooms of the protected premises. Actual location is to be determined by the fire code official.