High Strength Waste: |
|---|
Wastewater originating from industrial or commercial business activities that, when discharged to the collection system, has a concentration of total suspended solids (TSS) and/or biochemical oxygen demand (BOD) in excess of 350 mg/l. |
High Strength Waste Fee: |
|---|
A surcharge for TSS and/or BOD discharged at concentrations above 350 mg/l. High Strength Waste Fees shall be collected pursuant to a resolution adopted by the Three Rivers Wastewater Authority Board. and remitted to the TRRWA prior to the end of the calendar month following collection. |
Sampling: |
|---|
Grab sampling will normally be used for sampling intermittent discharges that are consistent in waste strength, and when samples are to be tested for components or characteristics that are subject to significant and unavoidable change during storage (i.e., dissolved gasses, pH, temperature, etc.). |
Composite sampling will normally be used for sampling continuous discharges and for sampling variable strength wastewater. Composite samples will normally be collected over a 24 hour period, however, when industrial or commercial discharges occur for less than 24 hrs/day, composite samples will be taken for the duration of the waste discharge. |
Sampling frequency will depend upon the nature and source of the waste discharged and its potential to adversely impact treatment plant operations and efficiencies. For discharges having a significant potential for disrupting plant operations, daily sampling may be appropriate. For discharges with a minimal potential for disrupting plant operations, less frequent sampling (i.e., weekly) may be appropriate. |