The installation of all fire hydrants shall be in accordance with sound engineering practices. In addition, the following requirements shall apply to all building construction projects:
(1) Two copies of detailed plans or drawings, accurately indicating the location of all valves and fire hydrants to be installed shall be submitted to the fire chief prior to the commencement of any construction.
(2) All construction of the fire hydrant installation and its attendant water system connection shall conform to the design standards and specifications promulgated by the appropriate water authority and fire department.
(3) Fire hydrant placement shall be adequately protected against vehicle damage and be designed to allow the free flow of pedestrian travel. The specific placement and setback requirements for each hydrant installation shall be determined by the fire chief. The fire chief may require the relocation of an installed hydrant if the hydrant's location is not in compliance with this section. If the fire chief orders the relocation of a fire hydrant installed after the effective date of the ordinance codified in this section, the abutting property owner shall be responsible for the costs of relocation.
(4) An auxiliary gate valve shall be installed at the main line tee to permit the repair and replacement of the hydrant without disruption of water service.
(5) All hydrants shall stand plumb, be set to the finished grade with the lowest outlet of the hydrant no less than 18 inches above the grade, and have no less than 36 inches in diameter of clear area about the hydrant for the clearance of hydrant wrenches on both outlets and on the control valve.
(6) The pumper port shall face the street. Where the street cannot be clearly defined or recognized, the port shall face the most likely route of approach and location of the fire truck while pumping, all as determined by the fire chief.
(7) The lead from the service main to the hydrant shall be no less than six inches in diameter. Any hydrant leads over 50 feet in length from water main to hydrant shall be no less than eight inches in diameter.
(8) All hydrants newly installed in single-family residential areas shall be supplied by not less than eight-inch mains and shall be capable of delivering 1,000 gpm fire flow over and above average maximum demands at the farthest point of the installation. Hydrant leads up to 50 feet long may be six inches in diameter.
(9) All hydrants shall meet city fire hydrant specification standard.
(10) The maximum distance between fire hydrants in commercial, industrial and apartment (including duplex) use district zones shall be 400 feet.
(11) Lateral spacing of fire hydrants shall be approved by the fire chief, and predicated on hydrants being located at street intersections.
(12) The appropriate water authority and the fire department shall be notified in writing of the date the fire hydrant installation and its attendant water connection system will be available for use.
(13) The fire chief shall be notified when all newly installed hydrants or mains are placed in service.
(14) After installation of the fire hydrant and with the approval of the fire chief, a certificate of occupancy permit for the building will be issued by the building department.
(Ord. 795 § 5, 1977; Ord. 822 §§ 1, 4, 1978; Ord. 1258 § 1.0, 1997)