TABLE B105.1(1) REQUIRED FIRE-FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES | |||
|---|---|---|---|
CALCULATION AREA (square feet) | AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) |
0-3,600 | No automatic sprinkler system | 1,000 | 1 |
3,601 and greater | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) at the required fire-flow rate |
0-3,600 | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 750 | 3/4 |
3,601 and greater | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 1/2 value in Table B105.1(2) but not less than 1500 | 1 |
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m |
TABLE B105.2 REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES | ||
|---|---|---|
AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) |
No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) |
Section 903.3.1.1 or Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2) but not less than 1500 | Duration in Table B105.1(2) |
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m |