A. 
Only backflow prevention devices which have been approved by the city shall be acceptable for installation by a water user connected to the city’s potable water system.
B. 
The city will provide, upon request, to any affected customer, a list of approved backflow prevention devices.
(Ord. 88-01 § 4(A), 1988)
Backflow prevention devices shall be installed in a manner prescribed in Section 7603, Title 22 of the California Administrative Code. Location of the devices should be as close as practicable to the user’s connection. The city shall have the final authority in determining the required location of a backflow prevention device.
A. 
Air-gap Separation (AG). The air-gap separation shall be located on the user’s side of and as close to the service connection as is practical. All piping from the service connection to the receiving tank shall be above grade and be entirely visible. No water use shall be provided from any point between the service connection and the air-gap separation. The water inlet piping shall terminate a distance of at least two pipe diameters from the supply inlet, but in no case less than one inch above the overflow rim of the receiving tank.
B. 
Reduced Pressure Principle Backflow Prevention Device (RP). The approved reduced pressure principle backflow prevention device shall be installed on the user’s side of and as close to the service connection as is practical. The device shall be installed a minimum of twelve inches above grade and not more than thirty-six inches above grade measured from the bottom of the device and with a minimum of twelve inches side clearance. The device shall be installed so that it is readily accessible for maintenance and testing. Water supplied from any point between the service connection and the RP device shall be protected in a manner approved by the city.
C. 
Double Check Valve Assembly (DC). The approved double check valve assembly shall be located as close as practical to the user’s connection and shall be installed above grade, if possible, and in a manner where it is readily accessible for testing and maintenance. If a double check valve assembly is put below grade it must be installed in a vault such that there is a minimum of six inches between the bottom of the vault and the bottom of the device, so that the top of the device is no more than a maximum of eight inches below grade, so there is a minimum of six inches of clearance between the side of the device with the test cocks and the side of the vault, and so there is a minimum of three inches clearance between the other side of the device and the side of the valve. Special consideration must be given to double check valve assemblies of the "Y" type. These devices must be installed on their side with the test cocks in a vertical position so that either check valve may be removed for service without removing the device. Vaults which do not have an integrated bottom must be placed on a three-inch layer of gravel.
(Ord. 88-01 § 4(B), 1988)
A. 
The owners of any premises on which, or on account of which, backflow prevention devices are installed, shall have the devices tested by a person who has demonstrated their competency in testing of these devices to the city. Backflow prevention devices must be tested at least annually and immediately after installation, relocation or repair. The city may require a more frequent testing schedule if it is determined to be necessary. No device shall be placed back in service unless it is functioning as required. A report in a form acceptable to the city shall be filed with the city each time a device is tested, relocated or repaired. These devices shall be serviced, overhauled or replaced whenever they are found to be defective and all costs of testing, repair and maintenance shall be borne by the water user.
B. 
The city will supply affected water users with a list of persons acceptable to the city to test backflow prevention devices. The city will notify affected customers by mail when annual testing of a device is needed and also supply users with the necessary forms which must be filled out each time a device is tested or repaired.
C. 
Upon request, the city will test a customer’s back-flow prevention device to fulfill the requirements of this chapter. The customer will be charged for the test and any maintenance found necessary to keep the device in working order on the next regular water bill.
(Ord. 88-01 § 4(C), 1988)
Approval must be obtained from the city before a backflow prevention device is removed, relocated, or replaced.
A. 
Removal. The use of a device may be discontinued and the device removed from service upon presentation of sufficient evidence to the city to verify that a hazard no longer exists or is not likely to be created in the future.
B. 
Relocation. A device may be relocated following confirmation by the city that the relocation will continue to provide the required protection and satisfy installation requirements. A retest will be required following the relocation of the device.
C. 
Repair. A device may be removed for repair, provided the water use is either discontinued until repair is completed and the device is returned to service, or the service connection is equipped with other backflow protection approved by the city. A retest will be required following the repair of the device.
D. 
Replacement. A device may be removed and replaced, provided the water use is discontinued until the replacement devices are approved by the city and are commensurate with the degree of hazard involved.
(Ord. 88-01 § 4(D), 1988)