Revise Section 5.1.1.2 to read as follows:
NFPA.13D.5.1.1.2. A supply of at least three sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced.
Add Sections 5.1.1.2.1 as follows:
NFPA.13D.5.1.1.2.1. The sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. The stock sprinklers shall include not less than one sprinkler of all types and ratings installed.
Add Sections 5.1.1.2.2 as follows:
NFPA.13D.5.1.1.2.2. The sprinklers shall be kept in a mounted and accessible cabinet located where the temperature to which they are subjected will at no time exceed the maximum ceiling temperatures specified in NFPA 13R Table 5.1.1.6.1 for each of the sprinklers within the cabinet.
Add Sections 5.1.1.2.4 as follows:
NFPA.13D.5.1.1.2.4. One sprinkler wrench, and socket if necessary, as specified by the sprinkler manufacture shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system.
Add Section 7.2.1.1 to read as follows:
NFPA.13D.7.2.1.1 On systems protecting in excess of 1,500 sq. ft., an additional inspector's test valve shall be provided when a change of elevation isolates a portion of the system. The valve shall be installed at a high point of the system to function as an air release. The valve shall be identified with signage and protected from unauthorized operation.
Revise Section 7.6 to read as follows:
NFPA.13D.7.6 A local waterflow alarm shall be provided on all sprinkler systems.
Add Section 8.1.3.1.2.1 to read as follows:
NFPA.13D.8.1.3.1 Garages are permitted to be protected by residential sprinklers.
Revise Section 8.3.4 to read as follows:
NFPA.13D.8.3.4 Sprinklers shall not be required in detached garages, open attached porches, detached carports, and similar structures unless otherwise required by the California Building or Fire Codes.
Add Section 8.3.5.2 to read as follows:
NFPA.13D.8.3.5.2 At least one quick-response intermediate temperature residential sprinkler shall be installed within 5 feet and above attic access openings.
Revise Section 11.2.1.1 to read as follows:
NFPA.13D.11.2.1.1 Where a fire department pumper connection is not provided, the system shall be hydrostatically tested at not less than 200 psi without evidence of leakage.