All water mains shall be constructed of either cast iron pipe or ductile iron pipe with the pipe fittings, valves and other underground appurtenances as previously approved for specific locations; such underground pipes shall be protected by the use of a sand envelope backfill. Plastic pipe may be used within the platted areas of the town if it conforms to AWWA 6-900-75 Standard; minimum class 150 (SDR 18) with cast iron dimensions and rubber ring joints; and plastic pipe may be used outside the platted areas of the town if a master meter is installed at the termination of the town mainline; provided, the plastic pipe conforms to the standards set forth previously or to the Uniform Plumbing Code (minimum pressure rating of 160 PSI). If, in the judgment of the town engineer, any proposed waterlines in unplatted areas might possibly be extended in the future so that they would then become a part of the town water system, those waterlines may use plastic water pipe that conforms only to the standard set forth above. Installation and backfill of all new water pipelines which will be or might become a part of the town water system shall conform with Class B, Class C or Class D as detailed in ASCE Manual No. 37 (6) or with the recommended practices given in ASTM D 2321 (7) along with the recommendations of the pipe manufacturer and the town engineer.
Cast-iron pipe shall be designed for 150 pounds per square inch working pressure and five feet of cover with half-thickness cement lining and shall meet the requirements of AWWA standard C106 for one cast-iron pipe centrifugally cast in metal molds, or AWWA standard C108 for cast iron pipe centrifugally cast in sand-lined molds. Pipe shall be furnished with the single gasket push-on joint.
Copper service pipe shall meet the requirements of ASTM standard specification B88 for seamless copper water tube, type K. Fittings shall be equal to Mueller H-15430 (copper tube nut), and H-15400 (three part union). Corporation cocks shall be an all bronze cock Mueller thread inlet and copper service pipe outlet equal to Mueller H-15000. Meter yokes shall be Ford or equal with inlet valve or an approved equal. Curb valves shall be Ford ball or Mueller Oviseal or equal.
Ductile iron pipe shall be designed for 150 pounds per square inch working pressure and five feet of cover, with half-thickness cement lining, meeting the requirements of AWWA Standard C151 for ductile iron pipe, centrifugally cast on metal molds or sand-lined molds. Pipe shall be furnished with the single-gasket push-on joint.
All fire hydrants shall be the Mueller A-24015 AWWA improved type with a six inch flanged inlet with two and one-half inch hose nozzles, one four inch pumper nozzle, a five-and-one-quarter-inch main valve, national standard hose threads and standard pentagon operating nut or equal. Hydrants shall be designed for a pipe depth of five feet (to top of pipe). Each hydrant shall be installed with a six inch flange x mechanical-joint auxiliary gate valve meeting the requirements previously specified.
Gate valves shall be iron-body, bronze-mounted, double-disc, parallel-seal valves meeting the requirements of AWWA Standard C500 for gate valves for ordinary water works service. All valves shall have nonrising stems and be furnished with "O-ring" packing. Valves shall be provided with a standard two inch square operating nut and shall open counterclockwise. Valves shall be equipped with mechanical-joint ends. Flange ends for hydrant auxiliary valves shall meet the requirements for ASA Class 125 cast iron pipe flanges with bolt holes straddling centerlines.
Valve boxes for both main line and hydrant auxiliary valves shall be a standard cast iron, two piece, screw-type adjustable valve box of correct size for the valve designed for a normal five-foot bury of the pipeline (to top of pipe).
Pipe fittings for either cast iron or ductile iron pipe shall meet the requirements of AWWA Standard C110 for cast iron pressure fittings. Except where otherwise specified by the town engineer, fittings shall be equipped with mechanical-joint couplings conforming to ASA Standard A21-11 for a mechanical joint for cast iron pressure pipe and fittings.
(1996 Code § 7-115; Ord. 419 Appx. 1 § 5, 1976)