In all areas of special flood hazards the following standards are required:
(A)
Anchoring.
(1)
All new construction and substantial improvements shall be adequately anchored to prevent flotation, collapse or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy.
(2)
All manufactured homes shall meet the anchoring standards of SJBMC 12-1-415.
(B)
Construction Materials and Methods. All new construction and substantial improvement shall be constructed as follows:
(1)
With materials and utility equipment resistant to flood damage;
(2)
Using methods and practices that minimize flood damage;
(3)
With electrical, heating, ventilation, plumbing and air conditioning equipment and other service facilities that are designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding; and
(4)
Within Zones AH or AO, so that there are adequate drainage paths around structures on slopes to guide floodwaters around and away from proposed or existing structures.
(C)
Elevation and Floodproofing.
(1)
Residential construction, new or substantial improvement, shall have the lowest floor, including basement, as follows:
(a)
In an AO zone, elevated above the highest adjacent grade to a height equal to or exceeding the depth number specified in feet on the FIRM, or elevated at least two feet (2') above the highest adjacent grade if no depth number is specified. (The State of California recommends that the lowest floor be elevated above the highest adjacent grade to a height exceeding the depth number specified in feet on the FIRM by at least one foot (1′), or elevated at least three feet (3') above the highest adjacent grade if no depth number is specified.)
(b)
In an A Zone, elevated to or above the base flood elevation, as determined by the Flood-plain Administrator based on an engineering study done to determine the height of a base flood elevation for the property in question.
(c)
In all other zones, elevated to or above the base flood elevation.
Upon the completion of the structure, the elevation of the lowest floor including basement shall be certified by a registered professional engineer or surveyor, and verified by the community building inspector to be properly elevated. Such certification or verification shall be provided to the Flood-plain Administrator.
(2)
Nonresidential construction shall either be elevated to conform with SJBMC 12-1-400(C)(1) or, together with attendant utility and sanitary facilities, as follows:
(a)
Be floodproofed below the elevation recommended under SJBMC 12-1-400(C)(1) so that the structure is watertight with walls substantially impermeable to the passage of water;
(b)
Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy; and
(c)
Be certified by a registered professional engineer or architect that the standards of this subsection are satisfied. Such certifications shall be provided to the Floodplain Administrator.
(3)
All new construction and substantial improvement with fully enclosed areas below the lowest floor (excluding basements) that are usable solely for parking of vehicles, building access or storage, and which are subject to flooding, shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwater. Designs for meeting this requirement must exceed the following minimum criteria:
(a)
Be certified by a registered professional engineer or architect; or
(b)
Be certified to comply with a local floodproofing standard approved by the Federal Insurance Administration, Federal Emergency Management Agency; or
(c)
Have a minimum of two (2) openings having a total net area of not less than one (1) square inch for every square foot of enclosed area subject to flooding. The bottom of all openings shall be no higher than one foot (1′) above grade. Openings may be equipped with screens, louvers, valves or other coverings or devices provided that they permit the automatic entry and exit of floodwater.
(4)
Manufactured homes shall also meet the standards in SJBMC 12-1-415.