Additions. For BOCA Use Group B-Business (professional
services, storage incidental to office use): Where a Use Group B fire
area exceeds 1,500 square feet in area, an automatic fire suppression
system shall be provided:
Throughout all intervening stories and floor levels
between the B Use Group and the level of exit discharge at exits that
serve the Use Group B fire area, including level of exit discharge..."
904 Use Groups A-1, A-3 and A-4: "Where a Use Group
A-1, A-3 or A-4 fire area exceeds [1,500 square feet] in area an automatic
fire suppression system shall be provided as follows:..."
904.4 Use Group E: "An automatic fire suppression
system shall be provided throughout all buildings having a Use Group
E fire area which exceeds [1,500 square feet] in area."
904.7 Use Groups M, S-1 and F-1: "Throughout all buildings
with a Use Group M, S-1 or F-1 fire area, an automatic fire suppression
system shall be provided as follows:
1.
Where any Use Group M, S-1 or F-1 fire area
exceeds [1,500 square feet] in area;..."
Editor's Note: Section 4 of this ordinance provided "Other than those insertions and changes referenced in Section 1 above, all other parts of BOCA Section 904.0 Fire Suppression Systems, Chapter 165 of the Borough Code and Media Borough Ordinance No. 911 are preserved. Section 5 of this ordinance provided "Any violation of this article shall subject the property owner to a civil penalty of not more than $1,000 plus costs of prosecution."