As used in this article, the following terms
shall have the meanings indicated:
FINISHING SHOP
A building or part thereof used for the application of flammable
finishes by means of spraying or dipping.
Finishing shops in buildings containing other
occupancies shall be cut off from other portions of the building by
fire partitions or fire walls and shall be equipped with an automatic
sprinkler system.
The storage of flammable finishes inside finishing
shops shall be restricted as follows:
A. Shelves. Quantities not exceeding, in the aggregate,
20 gallons, with no container exceeding one gallon in capacity, may
be stored on a substantial shelf at least four feet above the floor
and with suitable guard strips to prevent containers from falling.
B. Cabinets. Quantities not exceeding, in the aggregate,
50 gallons, with no container exceeding five gallons' capacity, may
be stored in a cabinet entirely enclosed and made of stiffened sheet
iron of at least 18 United States gauge in thickness and double-walled
and one-and-one-half-inch air space or equivalent construction. Doors
shall be of construction equivalent to the walls of the cabinets and
shall be provided with three-point lock, fit closely, and shall be
kept closed when not in use. Door sills shall be raised at least two
inches above the bottom of the cabinet.
C. Storage rooms. Quantities in excess of those given in Subsections
A and
B above shall be in storage rooms as described in §
65-115.
Mixing operations shall be carried on only in storage rooms as described in §
65-115, provided that containers of a total capacity not exceeding two gallons may be opened and their contents mixed in the finishing room.
Receptacles containing flammable finishes shall
be kept tightly covered.
All spraying shall be performed in a spray room
or spray booth constructed and maintained in accordance with the following
provisions, except that an equivalent construction shall be acceptable
if such construction shall afford the same or greater safeguard against
fire:
A. Spray rooms. If spraying is performed in a room not
provided with a spray booth, such spray room shall be separated from
the remainder of the building by partitions having a one-and-one-half-hour
fire-rated assembly. Doors on such rooms shall be equal in fire resistance
to the partitions and shall be of the self-closing type or so installed
as to close automatically in case of fire.
B. Booths: material, size. Spray booths may be metal
or other noncombustible material and of ample size to accommodate
the object to be sprayed.
C. Ventilation of booth. Spray booths shall be provided
with exhaust systems of sufficient capacity to adequately remove vapors
or residue. The supply of air entering the room where the spray booths
are located shall be substantially equivalent to the exhaust capacity
provided. Each spray booth shall have an independent stack or vent,
except that not more than three booths, each with less than six square
feet frontal area, may connect to one stack. They shall be properly
supported and shall have at least a six-inch clearance where passing
through wooden floors, roofs, partitions or in close proximity to
them or other combustible material.
D. Use of fans. Ventilating fans in spray rooms and booths
shall be kept in continuous operation while spraying is being carried
on and shall not be stopped until all flammable vapors have been removed.
E. Receptacles. Pails or receptacles shall not exceed
10 gallons' capacity for gravity feed to spray guns and shall be kept
covered with tight-fitting noncombustible covers. Only wire cable
or those containing stranded wire cores shall be used to suspend gravity
feed pails. Pails or receptacles containing flammable finishes shall
be returned to the storage cabinet or storage room at the close of
each day.
F. Portable lamps. No portable lamp shall be used inside
spray rooms or booths. Lamps shall be prohibited inside spray booths
and ducts and in any location where there is a possibility of the
spray coming into direct contact with the lamp.
G. Electric motors. Electric motors shall not be placed
inside booths or ducts.
H. Motor vehicles. Motor vehicles shall not be moved
by their own power while in the finishing room. Electric storage batteries
shall be removed.
Dip tanks having an area in excess of 10 square
feet shall be provided with covers arranged to close automatically
in case of fire and shall be so arranged that they may be closed manually.
Smaller dip tanks shall be provided with covers or with asbestos blankets
which may be placed over the tanks. If dip tanks are protected by
an automatic fire extinguishing system employing a fire-retardant
chemical, gas or water spray, the covers specified above may be omitted.
Rooms for the storage and handling of flammable
liquids shall be constructed with walls, floors and ceilings having
a fire-resistance rating of not less than one hour, provided that
where in the opinion of the Building Department the hazard is more
than moderate, based upon a consideration of the quantity and nature
of the liquids involved and the extent of mixing operations, together
with the construction of the building and its exposures, construction
having a fire-resistance rating of not less than two hours shall be
required. Door openings to the room shall be protected by automatic
or self-closing fire doors and shall have noncombustible sills raised
at least six inches above the room floor.
All metal spray booths, dip tanks, bake ovens,
mixers, filters, pumps, motors and shafting shall be electrically
grounded.
Japanning and enameling drying ovens shall not
be placed in contact with wood floors or other combustible material.
Heating of ovens shall be done by steam coils, indirect hot-air circulation
through the ovens to the outside, indirect hot-oil circulating pipes,
indirect gas burners or electricity. Open flames or fires shall not
be in communication with the compartments where goods are being treated.
No open flames shall be permitted in storage
or mixing rooms, storage cabinets, finishing rooms or spray booths.
For heating purposes, indirect systems only shall be used.
Adequate portable fire extinguishers or other
fire extinguishing appliances shall be installed in finishing rooms
and near storage cabinets and spray booths.
Metal waste cans with self-closing covers shall
be provided for all waste and rags.
Smoking shall be prohibited in any room used
for storage of flammable finishes and in any finishing room. Suitable
"No Smoking" signs shall be prominently displayed.