Table 1
| ||
---|---|---|
Demand Factors for Feeders and Service Entrance Conductors
| ||
Number of Mobile Homes
|
Demand Factor
(percent)
| |
1
|
100
| |
2
|
55
| |
3
|
44
| |
4
|
39
| |
5
|
33
| |
6
|
29
| |
7 to 9
|
28
| |
10 to 12
|
27
| |
13 to 15
|
26
| |
16 to 21
|
25
| |
22 to 40
|
24
| |
41 to 60
|
23
| |
61 and over
|
22
|
Table 2
| ||
---|---|---|
Demand Factors For Use in Calculating Gas Piping Systems in Mobile
Home Parks
| ||
Number of Mobile Home Sites
|
BTU's Per Hour Per Mobile Home Sites
| |
1
|
125,000
| |
2
|
117,000
| |
3
|
104,000
| |
4
|
96,000
| |
5
|
92,000
| |
6
|
87,000
| |
7
|
83,000
| |
8
|
81,000
| |
9
|
79,000
| |
10
|
77,000
| |
11 to 20
|
66,000
| |
21 to 30
|
62,000
| |
31 to 40
|
58,000
| |
41 to 60
|
55,000
| |
Over 60
|
50,000
|
* NOTE: "Approved" is intended to indicate extinguishers tested and
labeled by the Underwriters' Laboratories, Inc., the Underwriters'
Laboratories of Canada (ULC) or the Factory Mutual Engineering Corporation