A.
The Chief of the Bureau of Fire Prevention or Fire
Inspector shall survey each place of assembly, business, education,
industry, health, mercantile, storage, multiple-residence occupancy,
public and private schools, nursery schools and day-care centers and
shall specify suitable fire extinguishing equipment, systems or appliances
and fire detecting devices as shall be necessary to provide reasonable
safety to persons and property.
B.
Such devices or appliances may consist of automatic
fire alarm systems, automatic sprinklers or water spray systems, standpipes
and hoses, fixed or portable fire extinguishers of a type suitable
for the likely probable class of fire, exit lights, emergency lighting
units, panic hardware or other equipment. For special storage or hazardous
processes, appliances of more than one type or special systems may
be required. Automatic fire alarm and sprinkler systems shall be defined
in Section 902 of the Fire Code of New York State.[1]
A.
In accordance with Table I,[1] all buildings and structures occupied for purposes other
than residential buildings with less than six units that exceed 5,000
square feet of total floor area, or a place of assembly with an occupant
load of more than 100 persons, except assembly spaces used expressly
for religious purposes, shall be fully protected by an automatic sprinkler.
[1]
Editor's Note: Table I is included at the end of this chapter.
B.
Requirements for existing buildings.
(1)
Approved automatic sprinkler systems shall be installed
and maintained in operable condition, as specified in this section,
in all of the following existing buildings:
(a)
All places of public assembly where the maximum
number of occupants permitted is determined to be 200 or greater.
(b)
All educational buildings which are three or
more stories in height.
(c)
All institutional-type occupancies (i.e., nursing
homes, hospitals, homes for aged, etc.).
(d)
All multiple residences of a transient nature,
including rooming houses and boardinghouses, which contain six or
more units.
(e)
Any building, regardless of its nature or classification,
in which an unusually hazardous condition exists.
C.
Where the installation of approved automatic sprinkler systems is required in existing buildings pursuant to Subsection B(1) above, such sprinkler systems must be installed within two years of the effective date of this section.
D.
All sprinkler systems shall be installed and maintained
in accordance with the most current edition of the National Fire Protection
Association Standard for Sprinkler Systems (NFPA 13) or the appropriate
NFPA Standard for special occupancies.
E.
All sprinkler system components shall be tested and
inspected in accordance with National Fire Protection Association
Standard for the Inspection, Testing and Maintenance of Water-Based
Fire Protection Systems (NFPA 25) Copies of all service, repair, inspection
and testing reports shall be forwarded to the Fire Inspector within
10 days of such service repair, inspection or testing.
In order to ensure that fire fighters utilize
the proper siamese connection, all siamese connections and/or the
protective covers installed on the siamese connection shall be color
coded as follows:
RED
|
Siamese supplying a standpipe (fire hose) system.
|
GREEN
|
Siamese supplying a sprinkler system.
|
YELLOW
|
Siamese supplying a combination of standpipe
and sprinkler system.
|
A.
All buildings and structures other than one-family
and two-family residences shall be equipped with fire detection and
alarm systems as described in Table I.[2] A sprinkler system with a water flow device monitored
to immediately send an alarm to the Fire Department shall be considered
a fire detection system.
[2]
Editor's Note: Table I, Fire Prevention Device Requirements, is included at the end of this chapter.
B.
Where a 110-volt (hard-wired) smoke detector is required
to be installed in any building (including a one- or two-family dwelling)
by the New York State Uniform Fire Prevention and Building Code or
successor standards adopted by New York State or any other applicable
regulation, such smoke detector shall be equipped with a battery backup
to ensure operation of the smoke detector in the event of a power
interruption.
C.
All fire detection and alarm systems shall be installed
and maintained in accordance with the most current edition of the
National Fire Protection Association Fire Alarm Code (NFPA 72). Copies
of all service, repair, inspection and testing reports shall be forwarded
to the Fire Inspector within 10 days of such service, repair, inspection
or testing.
D.
The Fire Inspector shall be notified in writing prior
to the installation of any fire alarm or fire detection system. Such
notification shall consist of plans sufficient to determine compliance
with the Fire Code.
E.
Fire alarm or fire detection systems shall have an
annunciation or remote located at or near the main entrance of the
building. Such annunciation shall show the location and type of alarm.
A floor plan of the protected premises shall also be provided at this
location. The location of any annunciator or panel not clearly visible
upon entry of the main entrance of a building shall be marked with
a sign.
F.
Upon activation of a fire alarm the persons in charge
of a premises shall cause the premises to be evacuated unless an evacuation
plan preapproved by the Fire Inspector and Fire Department is in place.
In such case the provisions of the plan shall be followed.
G.
No fire system shall be reset from an alarm condition
unless approved by the Fire Inspector or Fire Department Officer-in-Charge.
A sign stating such shall be provided on all fire alarm panels capable
of resetting an alarm.
H.
The owner or responsible party of any premises containing
a fire alarm or fire detection system shall ensure that a qualified
technician is available to respond within two hours of notification
to initiate needed repair or service of the system.
I.
If the fire alarm system signal transmission to the
alarm receiving station is not tested on a daily basis, all dedicated
phone lines used for the purpose of transmitting fire alarm signals
shall be equipped with a visual/audio signal on the exterior of the
building to operate in the event of a line failure or disablement.
It shall be the sole responsibility of the property owner to maintain
all dedicated fire alarm system phone lines active at all times.
Portable fire extinguishers, installed and maintained
in accordance with National Fire Protection Association Standard No.
10, the Standard for Portable Fire Extinguishers, shall be provided
in all occupancies as required by Table I.[1]
[1]
Editor's Note: Table I is included at the end of this chapter.
A.
All commercial cooking appliances, exhaust removal
systems, ductwork, and related equipment shall be protected by an
automatic fire extinguishing system installed and maintained in compliance
with current applicable National Fire Protection Association Standards.
B.
These systems shall be inspected by an approved service
firm on a semiannual basis. To ensure proper inspection, a uniform
inspection form, provided by the Fire Inspector, shall be utilized
with a copy of the completed form forwarded to the Fire Inspector
within 10 days of the inspection.
Wherever deemed necessary for the protection
of a special hazard, the Fire Inspector may require the installation
of a special extinguishing system. Any such special extinguishing
system shall be installed and maintained in accordance with the most
current applicable National Fire Protection Association Standards.
A.
In order to notify responding fire fighters of conditions
within a building or structure equipped with sprinkler systems, fire
alarm systems, or containing hazardous materials or other hazards
to fire fighters, identification strobe lights shall be installed
on the exterior of the building as follows:
RED STROBE LIGHT
|
Located above the fire department siamese connection
of a sprinklered building to indicated activation of the water flow
alarm.
| |
YELLOW STROBE LIGHT
|
Installed to indicate activation of a pull station,
smoke detector, heat detector or other alarm device.
| |
BLUE STROBE LIGHT
|
Installed to indicate the presence of hazardous
materials, conditions or other danger to fire fighters.
|
B.
The exact location of these lights shall be determined
by the Fire Inspector.