The purpose of this article is to abate or control
actual or potential cross-connections and protect the public health.
This article provides for establishment and enforcement of a program
of cross-connection control and backflow prevention in accordance
with the Commonwealth of Virginia, State Board of Health, Waterworks
Regulations 1995, or as amended. This article is directed at service
line protection (containment).
The authority for this article is the Commonwealth
of Virginia, Department of Health Waterworks Regulations, Part II,
Article 3, Cross-Connection Control and Backflow Prevention in Waterworks.
Effective cross-connection control and backflow
prevention requires the cooperation of the Toms Brook-Maurertown Sanitary
District, the Chief Operator, the owner(s) of the property served,
the Local Building Official and the backflow prevention device tester.
A. The program shall be carried out in accordance with
the Commonwealth of Virginia, State Board of Health, Waterworks Regulations
and shall, at a minimum, provide containment of potential contaminants
at the consumer's service connection.
B. The Toms Brook-Maurertown Sanitary District has full
responsibility for water quality and for the construction, maintenance
and operation of the waterworks beginning at the water source and
ending at the service connection.
C. The Toms Brook-Maurertown Sanitary District shall,
to the extent of its jurisdiction, provide continuing identification
and evaluation of all cross-connection hazards. This shall include
an assessment of each consumer's water supply system for cross-connections,
to be followed by requirement, if necessary, of installation of a
backflow prevention device or separation. Assessments shall be performed
at least annually.
D. In the event of the backflow of pollution or contamination
into the waterworks, the Toms Brook-Maurertown Sanitary District shall
promptly take or cause corrective action to be taken to confine and
eliminate the pollution or contamination. The Toms Brook-Maurertown
Sanitary District shall report to the appropriate Commonwealth of
Virginia, Department of Health, Office of Drinking Water in the most
expeditious manner (usually by telephone) when backflow occurs and
shall submit a written report by the 10th day of the month following
the month during which backflow occurred addressing the incident,
its causes, effects, and preventive or control measures required or
taken.
E. The Toms Brook-Maurertown Sanitary District shall
take positive action to ensure that the waterworks is adequately protected
from cross-connections and backflow at all times. If a cross-connection
exists or backflow occurs into a consumer's water supply system or
into the waterworks or if the consumer's water supply system causes
the pressure in the waterworks to be lowered below 10 psi gauge, the
Toms Brook-Maurertown Sanitary District may discontinue the water
service to the consumer, and water service shall not be restored until
the deficiencies have been corrected or eliminated to the satisfaction
of the Toms Brook-Maurertown Sanitary District.
F. In order to protect the occupants of a premises, the
Chief Operator should inform the consumer's water supply system owner(s)
of any cross-connection beyond the service connection that should
be abated or controlled by application of an appropriate backflow
prevention device or separation. An appropriate backflow prevention
device or separation should be applied at each point-of-use and/or
applied to the consumer's water supply system, isolating an area which
may be a health or pollution hazard to the consumer's water supply
system or to the waterworks.
G. Records of backflow prevention devices, separations,
and consumer's water supply systems, including inspection records,
records of backflow incidents, and records of device tests, shall
be maintained by the Toms Brook-Maurertown Sanitary District for 10
years.
As used in this article, the following terms
shall have the meanings indicated:
AIR GAP
The unobstructed vertical distance through the free atmosphere
between the lowest point of the potable water outlet and the rim of
the receiving vessel.
AUXILIARY WATER SYSTEM
Any water system on or available to the premises other than
the waterworks. These auxiliary waters may include water from a source
such as wells, lakes, or streams; or process fluids; or used water.
They may be polluted or contaminated or objectionable, or constitute
an unapproved water source or system over which the water purveyor
does not have control.
BACKFLOW
The flow of water or other liquids, mixtures, or substances
into a waterworks from any source or sources other than its intended
source.
BACKFLOW PREVENTION BY SEPARATION ("SEPARATION")
Preventing backflow by either an air gap or by physical disconnection
of a waterworks by the removal or absence of pipes, fittings, or fixtures
that connect a waterworks directly or indirectly to a nonpotable system
or one of questionable quality.
BACKPRESSURE BACKFLOW
Backflow caused by pressure in the downstream piping which
is superior to the supply pressure at the point of consideration.
BACKSIPHONAGE BACKFLOW
Backflow caused by a reduction in pressure which causes a
partial vacuum creating a siphon effect.
CONSUMER
A person who drinks water from a waterworks.
CONTAINMENT
The prevention of backflow into a waterworks from a consumer's
water supply system by a backflow prevention device or by backflow
prevention by separation at the service connection.
CONTAMINANT
Any objectionable or hazardous physical, chemical, biological,
or radiological substance or matter in water.
CROSS-CONNECTION
Any connection to or structural arrangement of the waterworks,
direct or indirect, whereby backflow can occur.
DEGREE OF HAZARD
Either a high, moderate or low hazard based on the nature
of the contaminant; the potential health hazard; the probability of
the backflow occurrence; the method of backflow either by backpressure
or by backsiphonage; and the potential effect on waterworks structures,
equipment, and appurtenances used in the storage, collection, purification,
treatment, and distribution of pure water.
DISTRIBUTION MAIN
A water main whose primary purpose is to provide treated
water to service connections.
DIVISION
The Commonwealth of Virginia, Virginia Department of Health,
Office of Water Programs, Division of Water Supply Engineering.
DOMESTIC USE OR USAGE
Normal family or household use, including drinking, laundering,
bathing, cooking, heating, cleaning and flushing toilets (see Appendix
A for Title 32.1, Chapter 6, Article 2, Code of Virginia, 1950, as
amended).
DOUBLE GATE-DOUBLE CHECK VALVE ASSEMBLY
An approved assembly designed to prevent backsiphonage or
backpressure backflow and used for moderate- or low-hazard situations,
composed of two independently operating, spring-loaded check valves,
tightly closing shutoff valves located at each end of the assembly
and fitted with properly located test cocks.
ENTRY POINT
The place where water from the source is delivered to the
distribution system.
HEALTH HAZARD
Any condition, device, or practice in a waterworks or its
operation that creates, or may create, a danger to the health and
well being of the water consumer.
ISOLATION
The prevention of backflow into a waterworks from a consumer's
water supply system by a backflow prevention device or by backflow
prevention by separation at the sources of potential contamination
in the consumer's water supply system. This is also called "point-of-use
isolation." Isolation of an area or zone within a consumer's water
supply system confines the potential source of contamination to a
specific area or zone. This is called "area of zone isolation."
MAXIMUM CONTAMINANT LEVEL
The maximum permissible level of contaminant in water which
is delivered to the free-flowing outlet of the ultimate user of a
waterworks, except in the cases of turbidity and VOCs, where the maximum
permissible level is measured at each entry point to the distribution
system. Contaminants added to the water under circumstances controlled
by the user, except those resulting from corrosion of piping and plumbing
caused by water quality, are excluded from this definition. Maximum
contaminant levels may be either "primary" (PMCL), meaning based on
health considerations, or "secondary" (SMCL), meaning based on aesthetic
considerations.
PLUMBING FIXTURE
A receptacle or device which is either permanently or temporarily
connected to the water distribution system of the premises, and demands
a supply of water therefrom; or discharges used water, waste materials,
or sewage, either directly or indirectly, to the drainage system of
the premises; or requires both a water supply connection and a discharge
to the drainage system of the premises.
POLLUTION
The presence of any foreign substance (chemical, physical,
radiological, or biological) in water that tends to degrade its quality
so as to constitute an unnecessary risk or impair the usefulness of
the water.
POLLUTION HAZARD
A condition through which an aesthetically objectionable
or degrading material may enter the waterworks or a consumer's water
system.
PREMISES
A piece of real estate; house or building and its land.
PRESSURE VACUUM BREAKER
An approved assembly designed to prevent backsiphonage backflow
and used for high-, moderate-, or low- hazard situations, composed
of one or two independently operating, spring-loaded check valves;
an independently operating, spring-loaded air-inlet valve; tightly
closing shut-off valves located at each end of the assembly; and fitted
with properly located test cocks.
PROCESS FLUIDS
Any kind of fluid or solution, which may be chemically, biologically,
or otherwise contaminated or polluted which would constitute a health,
pollutional, or system hazard if introduced into the waterworks. This
includes, but is not limited to:
A.
Polluted or contaminated water;
C.
Used water, originating from the waterworks
which may have deteriorated in sanitary quality;
E.
Contaminated natural waters taken from wells,
lakes, streams, or irrigation systems;
F.
Chemicals in solution or suspension; and
G.
Oils, gases, acids, alkalis, and other liquid
and gaseous fluid used in industrial or other processes, or for fire-fighting
purposes.
PURE WATER or POTABLE WATER
Water fit for human consumption and domestic use which is
sanitary and normally free of minerals, organic substances, and toxic
agents in excess of reasonable amounts for domestic usage in the area
served and normally adequate in quantity and quality for minimum health
requirements of the persons served.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICE (RPX DEVICE)
An approved assembly designed to prevent backsiphonage or
backpressure backflow used for high-, moderate-, or low-hazard situations,
composed of a minimum of two independently operating, spring-loaded
check valves together with an independent, hydraulically operating
pressure differential relief valve located between the two check valves.
During normal flow and at the cessation of normal flow, the pressure
between these two checks shall be less than the supply pressure. The
unit must include tightly closing shutoff valves located at each end
of the assembly and be fitted with properly located test cocks.
SERVICE CONNECTION
The point of delivery of water to a customer's building service
line as follows:
A.
If a meter is installed, the service connection
is the downstream side of the meter.
B.
If a meter is not installed, the service connection
is the point of connection to the waterworks.
C.
When the water purveyor is also the building
owner, the service connection is the entry point to the building.
SYSTEM HAZARD
A condition posing a threat of or actually causing damage
to the physical properties of the waterworks or a consumer's water
supply system.
USED WATER
Water supplied from the waterworks to a consumer's water
supply system after it has passed through the service connection.
WATER SUPPLY
The water that shall have been taken into a waterworks from
all wells, streams, springs, lakes, and other bodies of surface water
(natural or impounded), and the tributaries thereto, and all impounded
groundwater, but the term "water supply" shall not include any water
above the point of intake of such waterworks.
WATERWORKS
A system that serves piped water for dinking or domestic
use to (1) the public, (2) at least 15 connections, or (3) an average
of 25 individuals for at least 60 days out of the year. The term "waterworks"
shall include all structures, equipment, and appurtenances used in
the storage, collection, purification, treatment, and distribution
of pure water except the piping and fixtures inside the building where
such water is delivered (see Title 32.1, Chapter 6, Article 2, Code
of Virginia, 1950, as amended).
WATERWORKS OWNER
An individual, group of individuals, partnership, firm, association,
institution, corporation, government entity, or the federal government
which supplies or proposes to supply water to any person within this
state from or by means of any waterworks (see Title 32.1, Chapter
6, Article 2, Code of Virginia, 1950, as amended).