The following items are the additions, insertions and changes
to the International Building Code:
Section 101.1 Title.
Delete all and insert "These regulations shall be known as the
Building Code of the Village of Lincolnwood, hereinafter referred
to as 'this code.' The Village of Lincolnwood shall be inferred
whenever the term 'Village' is used in this code."
Section 101.4.3 Plumbing.
Delete all and insert "The provisions of the Illinois Plumbing
Code, most current edition shall apply to the installation, alteration,
repair and replacement of plumbing systems, including equipment, appliances,
fixtures, fittings and appurtenances, and where connected to a water
or sewage system and all aspects of a medical gas system. All references
to the International Plumbing Code throughout this code shall be replaced
with the Illinois Plumbing Code, most current edition."
Section 101.4.6 Energy.
Delete all and insert "The provisions of the Illinois Energy
Conservation Code, most current edition shall apply to all matters
governing the design and construction of buildings for energy efficiency.
All references to the International Energy Conservation Code throughout
this code shall be replaced with the Illinois Conservation Code, most
current edition."
Section 102.4.2 Provisions in referenced codes and standards.
Delete all and insert "Where the extent of the reference to
a referenced code or standard includes subject matter that is within
the scope of this code as well as the Illinois Plumbing Code, most
current edition and the Illinois Energy Conservation Code, most current
edition or the International Codes listed in Section 101.4, the provisions
of this code as well as the Illinois Plumbing Code, most current edition
and the Illinois Energy Conservation Code or the International Codes
listed in Section 101.4 shall take precedence over the provisions
in the referenced code or standard.
"1. All references to Chapter
11 Accessibility, any/all sections, throughout this code shall be referenced back to the Illinois Accessibility Code, most current edition."
Section 103.1 Creation of enforcement agency.
Delete all and insert "The Division of Building Safety, as part
of the Community Development Department, is hereby created, and the
official in charge shall be known as the Building Official."
Add (new section) 105.1.3 Failure to pick up an approved
permit within six months.
Insert "Failure to pick up an approved permit within six months
from time of initial permit submittal where contact was made to the
applicant and/or owner to pay for, pick up and set up appropriate
inspections, shall be deemed 'Work performed prior to issuance
of permit' and subject to double the standard permit fees pursuant
to the Village's Annual Fee Resolution, and Section
14-14-6 of the Village Code."
Section 105.2 Work exempt from permit. Building:
Delete all and insert:
"1.
|
Painting, papering, tiling not in showers or bathtubs, carpeting,
finish flooring, and other similar finish work but not including cabinetry
and countertops where plumbing exists.
|
"2.
|
Prefabricated swimming pools accessory to a Group R-3 occupancy
that are less than 24 inches (610 mm) deep, are not greater than 5,000
gallons (18,925 L) and are installed entirely above ground.
|
"3.
|
Swings and other playground equipment accessory to detached
one- and two-family dwellings.
|
"4.
|
Nonfixed and movable fixtures, cases, racks, counters and partitions
not over five feet nine inches (1,753 mm) in height."
|
Section 105.2 Work exempt from permit. Electrical:
Delete all and insert:
"1.
|
Repairs and maintenance: Minor repair work, including
the replacement of lamps or the connection of approved portable electrical
equipment to approved permanently installed receptacles.
|
"2.
|
Temporary testing systems: A permit shall not be
required for the installation of any temporary system required for
the testing or servicing of electrical equipment or apparatus."
|
Section 105.3 Application for permit.
Delete "department of building safety" and insert "Division
of Building Safety."
Section 105.5 Expiration.
Delete all and insert "Every permit issued shall become invalid
unless the work on the site authorized by such permit is commenced
within 180 days after its issuance, or if the work authorized on the
site by such permit is suspended or abandoned for a period of 180
days after the time the work is commenced. The Building Official is
authorized to grant, in writing, one permit renewal or reissuance,
for a period not to exceed 180 days. The renewal or reissuance shall
be requested in writing and justifiable cause demonstrated. The Village
Manager is authorized to grant, in writing, any subsequent permit
renewals or reissuances, for periods not to exceed 180 days. Any subsequent
renewals or reissuances shall be in writing and justifiable cause
demonstrated. However, no permit or approval shall be valid for a
period of more than one year after the date of issuance."
Add (new section) 105.8 Permit fee extension.
Insert "There shall not be any fee for the first renewal or
reissuance of any permit that extends the validity of the initial
permit for a period not to exceed 180 days. The fee for any subsequent
renewal or reissuance of any permit that extends the validity of the
initial permit for additional periods not to exceed 180 days shall
be assessed at 25% of the original cost of the original permit."
Section 107.2.5 Site plan.
Delete all and insert "The construction documents submitted
with the application for permit shall be accompanied by a site plan
showing to scale the size and location of new construction and existing
structures on the site, distances from lot lines, the established
street grades and the proposed finished grades and, as applicable,
flood hazard areas, floodways, and design flood elevations; and it
shall be drawn in accordance with an accurate boundary line survey.
In the case of demolition, the site plan shall show construction to
be demolished and the location and size of existing structures and
construction that are to remain on the site or plot. The Building
Official is authorized to waive or modify the requirement for a site
plan where the application for permit is for alteration or repair
or where otherwise warranted. The site and grading plan shall be submitted
in both paper and electronic versions."
Add (new section) 107.2.5.2 Compliance with site plan.
Insert "It shall be the responsibility of the builder/developer
to submit to the Division of Building Safety a spot survey prepared
by a registered land surveyor after the foundation is installed. This
spot survey must be at a scale of not less than one inch equal to
30 feet. The spot survey must also indicate the elevation above sea
level of the top of the foundation wall and the top of the curb and
sidewalk at lot lines extended relative to a United States Geological
Survey benchmark. No construction will be allowed to proceed except
for decking, underground water and sewer, and related items until
the spot survey is approved by the Building Official. This section
applies to principal structures only and not to additions or accessory
structures."
Section 109.2 Schedule of permit fees.
Delete all and insert "On buildings, structures, electrical,
gas, mechanical and plumbing systems or alterations requiring a permit,
a fee for each permit shall be paid as required, in accordance with
the Village's Annual Fee Resolution."
And insert lines (A, 1 through 3) as follows:
"A.
|
A fee for each plan examination, building permit and inspection
shall be paid prior to the issuance of permit(s) in accordance with
the following schedule:
|
|
"1.
|
Building permit fees are set forth in the Village's Annual
Fee Resolution. Whenever the cost of construction is a factor in determining
a permit or plan review fee, the valuation of building projects shall
be established based on the greater of:
|
|
|
"a.
|
The cost of construction established by the International Code
Council (ICC) and published on its website. The most current schedule
shall be used based upon ICC published data; or
|
|
|
"b.
|
The cost of construction as stated by the applicant or agent
on the application for the relevant permit.
|
|
"2.
|
Building plan review fees are set forth in the Village's
Annual Fee Resolution. Further, an Amendment Form is required to be
submitted detailing the changes for any revisions from previously
approved plans. For building plans that have been previously reviewed,
and the permit issued, any revisions to the building plan that, based
upon the changes proposed, require the review of two or more disciplines,
a plan review fee for the Amendment Form is set forth in the Village's
Annual Fee Resolution.
|
|
"3.
|
Recovery of third-party costs. The Village may recover all third-party
vendor and consultant fees incurred by the Village for plan reviews
and subsequent inspections even if/when a permit is/was never issued."
|
Section 109.3 Building permit valuations.
Delete all and insert "The applicant for a permit shall provide a detailed estimated permit value or detailed contractor proposals at time of application. Final building permit valuations shall be in accordance with Section
14-14-1(A) through (F)."
Add (new section) 110.3.10.2 Final storm sewer inspection.
Insert "A final inspection of the storm sewer shall be scheduled
with and approved by the Department of Public Works prior to the issuance
of a certificate of occupancy."
Add (new section) 110.7 Final grading/TOPO survey.
Insert "If the topography of the land or property has been materially
altered in connection with any work completed thereon, a final grading/TOPO
plat of survey, performed, signed and sealed by a licensed land surveyor,
shall be submitted to the Village for review prior to the issuance
of a certificate of occupancy. The survey shall be submitted in both
paper and electronic versions and shall include the location of the
water meter."
Add (new section) 111.3.1 Deposit and compliance.
Insert "Prior to the granting of a temporary occupancy permit,
the applicant shall submit a deposit equal to 110% of the cost of
completion of all outstanding items necessitating the request for
a temporary occupancy permit. The deposit shall be forfeited to the
Village upon noncompletion of any outstanding items prior to the expiration
of the temporary occupancy permit."
Section 112 Service Utilities.
Delete in its entirety.
Section 113 Board of Appeals.
Delete in its entirety and insert new section title 113
Appeals.
Add (new section) 113.1 General.
Insert lines (A, 1 through 3, B and C) as follows:
"A.
|
Any person shall have the right to appeal a decision of the
Building Official to the Village Manager. A letter for appeal shall
be based on a claim for one of the following three reasons:
|
|
"1.
|
That the true intent of this code or the rules legally adopted
thereunder have been incorrectly interpreted; or
|
|
"2.
|
The provisions of this code do not fully apply; or
|
|
"3.
|
An equivalent or better method of construction is proposed.
|
"B.
|
All appeals shall be filed within 30 days of the decision of
the Building Official.
|
"C.
|
The Village Manager shall affirm, modify, or reverse the decision
of the Building Official."
|
Section 114.4 Violation penalties.
Delete all and insert "Any person who violates a provision of
this code or fails to comply with any of the requirements thereof
or who erects, constructs, alters or repairs a building or structure
in violation of the approved construction documents or directive of
the Building Official, or of a permit or certificate issued under
the provisions of this code, shall be subject to penalties as prescribed
by law or as set forth in the Village's Annual Fee Resolution."
Section 115.3 Unlawful continuance.
Delete all and insert "Any person who shall continue any work
after having been served with a stop-work order, except such work
as that person is directed to perform to remove a violation or unsafe
condition, shall be subject to penalties as prescribed by law. Violation
of unlawful continuance is subject to either penalties as prescribed
by law or as set forth in the Village's Annual Fee Resolution."
Add (new section) 115.4 Appeals.
Insert "Any permittee who is served with a stop-work order shall
have the right to appeal the issuance of the stop-work order to the
Village Manager, by filing a written appeal within seven days after
the issuance of the stop-work order. The Village Manager shall, within
seven days after receipt of the properly filed appeal, either (a)
affirm the issuance of the stop-work order, or (b) rescind or modify
the stop-work order. The failure of the Village Manager to render
a decision within seven days shall be deemed as an affirmance by the
Village Manager of the issuance of the stop-work order. All decisions
of the Village Manager made pursuant to this Section 115.4 shall be
final."
Section 202 Definitions. Fire Area.
Delete all and insert "The aggregate floor area bounded by the
exterior walls of a building or structure, regardless of fire walls,
fire barriers or fire-resistance-rated horizontal assemblies."
Section 406.3.5.1 Carport separation.
Delete all.
Section 420.2 Separation walls.
Delete all.
Section 420.3 Horizontal separation.
Delete all.
Add (new section) 503.1.4 Types III-B, IV, and V construction. and insert "Buildings of Types III-B, IV, and V construction are
only permitted for buildings of 1,000 square feet or less in area,
and of no more than one story in height. There are no area, story,
height or sprinkler increases allowed for these building types as
provided for in Section 506, 507 or 508. Type III-A construction is
permitted in accordance with the provisions of this Code."
Section 508.3 Nonseparated occupancies.
After paragraph add "Exception:" and insert "All Group B uses
shall be separated from Group F and Group S uses with minimum one-hour
fire-resistance-rated barrier in accordance with Section 707."
Add (new section) 508.4.4.2 Group B from Group F and S.
Insert "Where the amended Table 508.4 requires a one-hour fire-resistance-rated
barrier between Use Groups B, F-1, M and S-1, the one-hour fire-resistance-rated
barrier shall not be required to separate rooms or areas of the same
use group unless a fire separation is required elsewhere in this code."
Add (new section) 601.1.1 Application of other laws.
Insert "The provisions of this article shall not be deemed to
nullify any provisions of the Zoning Ordinance or any other ordinance,
law or statute of the Village pertaining to the location, or type
of construction of buildings."
Section 602.3 Type III.
Delete all and insert "Type III construction is that type of
construction in which the exterior walls are of noncombustible materials
and the interior building elements are of any material permitted by
this code. Fire-retardant-treated wood framing and sheathing complying
with Section 2303.2 shall be permitted within exterior wall assemblies
of a two-hour rating or less. Type III-B construction is only permitted
for buildings of 1,000 square feet or less in area and no more than
one story in height. Type III-A construction is permitted in accordance
with the provisions of this Code."
Section 602.4 Type IV.
Delete all and insert "Type IV construction is that type of
construction in which the exterior walls are of noncombustible materials
and the interior building elements are of solid wood, laminated wood,
heavy timber (HT) or structural composite lumber (SCL) without concealed
spaces. The minimum dimensions for permitted materials including solid
timber, glued-laminated timber, structural composite lumber (SCL),
and cross-laminated timber and details of Type IV construction shall
comply with the provisions of this section and Section 2304.11. Exterior
walls complying with Section 602.4.1 or 602.4.2 shall be permitted.
Interior walls and partitions not less than one-hour fire-resistance
rating or heavy timber complying with Section 2304.11.2.2 shall be
permitted. Type IV construction is only permitted for buildings of
1,000 square feet or less in area and no more than one story in height."
Section 602.5 Type V.
Delete all and insert "Type V construction is that type of construction
in which the structural elements, exterior walls and interior walls
are of any materials permitted by this code. Type V construction is
only permitted for buildings of 1,000 square feet or less in area
and no more than one story in height."
Section 708.1 General. Number 1
Delete all and insert "The following wall assemblies shall comply
with this section.
"1.
|
Walls separating tenant spaces.
|
"2.
|
Corridor walls as required by Section 1020.1.
|
"3.
|
Enclosed elevator lobby separation as required by Section 3006.2.
|
"4.
|
Egress balconies as required by Section 1021.2.
|
"5.
|
Walls separating Group B uses from Group F uses in accordance
with Section 508.3 Exception."
|
Section 708.3 Fire-resistance rating.
Delete all and insert "Fire partitions shall have a fire-resistance
rating of not less than one hour.
"Exceptions:
"1.
|
Corridor walls permitted to have a one-hour fire-resistance
rating in accordance with Table 1020.1 of this Code."
|
Section 711.2.4.3 Dwelling units and sleeping units.
Delete all and insert "Horizontal assemblies serving as dwelling
or sleeping unit separations in accordance with Section 420.3 shall
be not less than one-hour fire-resistance-rated construction."
Section 903.2.1.1 Group A-1. 1.
Delete and insert "1. A Group A-1 fire area exceeds 5,000 square
feet."
Section 903.2.1.3 Group A-3. 1.
Delete and insert "1. A Group A-3 fire area exceeds 5,000 square
feet."
Section 903.2.1.4 Group A-4. 1.
Delete and insert "1. A Group A-4 fire area exceeds 5,000 square
feet."
Add (new section) 903.2.2.1 Group B.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group B fire area exceeding 5,000 square
feet."
Section 903.2.3 Group E. 1.
Delete and insert "1. A Group E fire area exceeds 5,000 square
feet."
Section 903.2.4 Group F-1.
Delete in its entirety and add (new section) 903.2.4 Group
F-1, F-2.
Section 903.2.4 Group F-1, F-2.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group F-1 or F-2 occupancy where one of
the following conditions exists:
"1.
|
A Group F-1 or F-2 fire area exceeds 5,000 square feet.
|
"2.
|
A Group F-1 or F-2 fire area is located more than three stories
above grade plane.
|
"3.
|
The combined area of all Group F-1 or F-2 fire areas on all
floors, including any mezzanines, exceeds 10,000 square feet.
|
"4.
|
A Group F-1 or F-2 occupancy used for the manufacture of upholstered
furniture or mattresses exceeds 2,500 square feet."
|
Add (new section) 903.2.4.2 Group F "Spec" buildings.
Insert "All 'spec' buildings with a Group F use having
a ceiling or roof height of 25 feet or greater shall be protected
with an ESFR fire sprinkler system or a hydraulically calculated fire
sprinkler system for Class IV commodities with rack storage calculated
to the greatest storage height."
Section 903.2.7 Group M. 1.
Delete and insert "1. A Group M fire area exceeds 5,000 square
feet."
Section 903.2.9 Group S-1.
Delete in its entirety and add (new section) 903.2.9 Group
S-1, S-2.
Section 903.2.9 Group S-1, S-2.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group S-1 or S-2 occupancy where one of
the following conditions exists:
"1.
|
A Group S-1 or S-2 fire area exceeds 5,000 square feet.
|
"2.
|
A Group S-1 or S-2 fire area is located more than three stories
above grade plane.
|
"3.
|
The combined area of all Group S-1 or S-2 fire areas on all
floors, including any mezzanines, exceeds 10,000 square feet.
|
"4.
|
A Group S-1 fire area used for the storage of commercial motor
vehicles where the fire area exceeds 5,000 square feet.
|
"5.
|
A Group S-1 or S-2 occupancy used for the storage of upholstered
furniture or mattresses exceeds 2,500 square feet.
|
"6.
|
A Group S-2 occupancy where there is an enclosed parking garage
located beneath other groups except Group R-3 occupancies."
|
Add (new section) 903.2.9.3 Group S "Spec" buildings.
Insert "All 'spec' buildings with a Group S use having
a ceiling or roof height of 25 feet or greater shall be protected
with an ESFR fire sprinkler system or a hydraulically calculated fire
sprinkler system for Class IV commodities with rack storage calculated
to the greatest storage height."
Section 903.2.10 Group S-2 Enclosed parking garages.
Delete in its entirety.
Section 903.3.5 Water supplies.
Delete all and insert "Water supplies for automatic sprinkler
systems shall comply with this section and the standards referenced
in Section 903.3.1. The potable water supply shall be protected against
backflow in accordance with the requirements of this section and the
International Plumbing Code. For connections to public waterworks
systems, the water supply test used for design of fire protection
systems shall be adjusted to account for seasonal and daily pressure
fluctuations based on information from the water supply authority
and as approved by the fire code official. Hydrant water flow data
used for the design of any fire sprinkler system shall not be more
than one year old."
Section 903.3.5.2 Residential combination services.
Delete all and add (new section) 903.3.5.2 Domestic water
separation.
903.3.5.2 Domestic water separation.
Insert "The domestic water service shall be separated from the
fire service in accordance with the Illinois Plumbing Code, most current
edition."
Add (new section) 903.3.5.3 Design safety factor.
Insert "The design of the fire sprinkler system shall provide
a minimum five psi safety factor in the fire protection system hydraulic
calculation. The system demand shall be minimum five psi below the
seasonal low water flow test supply."
Section 903.3.8.5 Calculations.
Delete all and insert "Provide a minimum 10% but not less than
5 psi minimum safety factor in the fire protection system hydraulic
calculation. The system demand shall be 5 psi minimum below the seasonal
low water flow test supply."
Section 903.4 Sprinkler system supervision and alarms.
Delete all and insert "Valves controlling the water supply for
automatic sprinkler systems, pumps, tanks, water levels and temperatures,
critical air pressures and water flow switches on all sprinkler systems
shall be electrically supervised by a fire alarm system."
Section 903.4.1 Monitoring.
Delete all and insert "Alarm, supervisory and trouble signals
shall be distinctly different and shall be automatically transmitted
to the Fire Department's communication center, via communication
method(s) approved by the Fire Code Official."
Add (new section) 903.4.2.1 Outside alarm indicators.
Insert "For commercial properties and residential buildings
with a Fire Department connection a weatherproof clear 75 cd audio/visual
device shall be mounted on the outside of a building or structure
over the location of the Fire Department connection in the immediate
area of the sprinkler system bell. The weatherproof clear 75 cd audio/visual
device shall activate on all alarms. The sprinkler system bell shall
activate on water flow only."
Add (new section) 903.4.2.2 Interior appliances, audible
and visible alarms.
Insert "Interior appliances, interior audible and visible alarms
supervised by a fire alarm system shall be provided in accordance
with Sections 90."
Add (new section) 903.4.2.3 Inspector test valves.
Insert "Fire sprinkler system inspector test valves shall be
accessible at all times and shall be located no more than six feet
zero inches above the finished floor. For sprinkler systems with multiple
risers, each inspector test valve shall be marked for the riser and
area it serves."
Section 903.4.3 Floor control valves.
Delete all and insert "Indicating control valves and water flow
switches shall be provided at the point of connection to the riser
on each floor in multiple-story buildings."
Add (new section) 903.4.4 Automatic sprinklers.
Insert "When a building has numerous rooms protected by the
zoned sprinkler system, the Fire Department may require additional
smoke detectors for a more rapid means to identify the location of
smoke or fire."
Add (new section) 903.6 Outside access door.
Insert "Provide an outside access door, no less than 36 inches
in width and six feet eight inches in height, at all fire sprinkler
riser valve rooms and fire pump rooms."
Add (new section) 903.7 Sprinkler valve room.
Insert "All fire sprinkler main risers and valves shall be enclosed
within a room constructed with minimum one-hour fire barriers. Said
room shall be sized to maintain all required clearances to maintain,
repair and operate the system and all valves, and shall be sized to
maintain all required door clearances."
Add (new section) 903.8 Fire hydrants.
Insert "Fire hydrants shall be provided around the perimeter
of a building in no more than three-hundred-foot increments, and at
least one fire hydrant shall be located within 100 feet of the Fire
Department connection on the fire protection water supply to the building."
Add (new section) 903.9 Fire flow requirements.
Insert "Appendix B of the 2015 International Fire Code is adopted
in full and shall be made a part of this code."
Add (new section) 903.13 NFPA standards.
Insert "Whenever NFPA standards are listed or referenced within
this code, that entire list of NFPA standards, hereby adopted as Appendix
A, to this Article 2 shall be considered a part of this code."
Section 905.3.1 Height.
Delete all and insert "Class III standpipe systems shall be
installed throughout buildings where more than two stories in height,
or more than two stories below grade."
Add (new section) 905.3.9 Warehouse storage areas.
Insert "In all warehouse storage areas exceeding 20,000 square
feet, and where storage exceeds 12 feet in height, inside two-and-one-half-inch
fire hose valves with a one-and-one-half-inch reducer shall be provided
to a one-and-one-half-inch connection. Said valves shall be located
at each entrance door to the warehouse and/or storage area. Additional
two-and-one-half-inch fire hose valves shall be provided such that
no portion of the warehouse and/or storage area is more than 120 feet
of maximum travel distance to a fire hose valve. The location of all
obstructions and racking shall be clearly identified on the permit
drawings."
Add (new section) 905.3.9.1 Fire hose valve system.
Insert lines (A, 1 through 3) as follows:
"A.
|
The fire hose valve system piping shall:
|
|
"1.
|
Be a separate riser piping system;
|
|
"2.
|
Be supplied by a minimum four-inch supply pipe with two-and-one-half-inch
drops to each two-and-one-half-inch valve; and
|
|
"3.
|
Where system pressures exceed 100 psi, provide Potter reduced
pressure field adjustable type valves."
|
Add (new section) 907.1.4 Addressable fire alarm systems.
Insert "All fire alarm systems shall be of the addressable type."
Section 907.2 Where required - New buildings and structures.
Delete all, including Exceptions, and insert "A fire alarm system
utilizing automatic fire detectors and manual fire alarm devices shall
be provided throughout all buildings and structures not provided with
an automatic sprinkler system complying with NFPA 13 or NFPA 13R."
Section 907.2.1 Group A.
Delete all including Exception.
Section 907.2.1.1 System initiation in Group A occupancies
with an occupant load of 1,000 or more.
Delete all including Exception.
Section 907.2.1.2 Emergency voice/alarm communication
captions.
Delete all including Exception.
Section 907.2.2 Group B.
Delete all including Exception.
Section 907.2.2.1 Ambulatory care facilities.
Delete all including Exception.
Section 907.2.3 Group E. 3.
Delete all.
Section 907.2.4 Group F.
Delete all including Exception.
Section 907.2.7 Group M.
Delete all and insert "A manual fire alarm system that activates
the occupant notification system in accordance with Section 907.5
shall be installed in Group M occupancies."
Section 907.2.8.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.2.9.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.2.10.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.4.2.5 Protective covers.
Delete all and insert "Protective covers. Listed manual fire
alarm box protective covers shall be provided for all installed manual
fire alarm boxes to prevent malicious false alarms or to provide the
manual fire alarm box with protection from physical damage."
Section 907.5 Occupant notification systems.
Delete in its entirety. Insert lines (A, 1 through 4) as follows:
"A.
|
A fire alarm system shall annunciate at the fire alarm control
unit and shall initiate occupant notification upon activation, in
accordance with Sections 907.5.1 through 907.5.2.3.4. Where a fire
alarm system is required by another section of this code, it shall
be activated by: The activation of any of the following devices shall
result in occupant notification:
|
|
"1.
|
Automatic fire detectors.
|
|
"2.
|
Automatic sprinkler system water flow devices.
|
|
"3.
|
Manual fire alarm boxes.
|
|
"4.
|
Automatic fire extinguishing systems when installed in buildings
or structures that are provided with occupant notification."
|
Add (new section) 907.5.2.3.4 In single story multitenant
buildings of all use groups. Insert "Multitenant buildings
shall be designed as ring by tenant, activated by a fire sprinkler
system flow switch for that space or automatic fire detection, and
shall include a weatherproof clear 75 cd audio/visual device mounted
on the outside of the building or structure over the entrance to each
tenant space as directed by the Fire Code Official."
Add (new section) 907.6.7 Fire alarm panel location.
Insert "The fire alarm control panel or full function annunciator
panel shall be installed within 10 feet of the main entrance or in
a location approved by the Fire Code Official."
Add (new section) 912.7.1 Connection type.
Insert "All Fire Department connections shall be a five-inch
Storz connection with a thirty-degree turndown."
Add (new section) 913.4.2 Fire pump test header.
Insert lines (A, 1 through 2) as follows:
"A.
|
For fire pump installations, provide the following:
|
|
"1.
|
An OS&Y control valve on all fire pump test headers; and
|
|
"2.
|
An outside test header."
|
Section 1008.3.3 Rooms and spaces.
Insert line "6. All rooms and areas containing the building
fire sprinkler riser(s), fire pump(s) and fire alarm control panel(s)."
TABLE 1020.1
CORRIDOR FIRE-RESISTANT RATING (HOURS)
|
---|
Occupancy
|
Occupant Load Served By Corridor
|
Required Fire-Resistance Rating
(hours)
|
---|
Without Sprinkler System
|
With Sprinkler Systemc
|
---|
H-1, H-2, H-3
|
All
|
Not Permitted
|
1
|
H-4, H-5
|
Greater than 30
|
Not Permitted
|
1
|
A, B, E, F, M, S, U
|
Greater than 30
|
1
|
0
|
R
|
Greater than 10
|
Not Permitted
|
2
|
1-2a, 1-4
|
All
|
Not Permitted
|
0
|
1-1, 1-3
|
All
|
Not Permitted
|
1b
|
a.
|
For requirements for occupancies in Group 1-2, see Sections
407.2 and 407.3.
|
b.
|
For a reduction in the fire-resistance rating for occupancies
in Group 1-3, see Section 408.8.
|
c.
|
Buildings equipped throughout with an automatic sprinkler system
in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed.
|
Add (new section) "1030.5.3 Covers.
Insert "Protect well openings with metal gratings or other approved
covers."
Chapter 11 Accessibility.
Delete in its entirety.
Section 1403.1 Scope.
Delete all and insert "Materials used for the construction of exterior walls shall comply with the provisions of this section. Materials not prescribed herein shall be permitted, provided that any such alternative has been approved. All exterior walls shall be constructed in accordance with the applicable standards set forth in the Village of Lincolnwood Zoning Ordinance Chapter
15 as follows:
"1.
|
Section 15.6.04, Commercial, institutional and civic building
design standards
|
"2.
|
Section 15.6.05, Multifamily residential building design standards
|
"3.
|
Section 15.6.06, Industrial building design standards."
|
Section 1404.11 Exterior insulation and finish system.
Delete all.
Section 1408 Exterior insulation and finish systems (EIFS).
Delete in its entirety.
Section 1612.3 Establishment of flood hazard areas.
Delete all and insert "To establish flood hazard areas, the
applicable governing authority shall adopt a flood hazard map and
supporting data. The flood hazard map shall include, at a minimum,
areas of special flood hazard as identified by the Federal Emergency
Management Agency in an engineering report entitled 'The Flood
Insurance Study for the Village of Lincolnwood,' most recent
edition, as amended or revised with the accompanying Flood Insurance
Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related
supporting data along with any revisions thereto. The adopted flood
hazard map and supporting data are hereby adopted by reference and
declared to be part of this section."
Section 1803.5.4 Ground water table. Exception:
Delete all
Chapter 27 Electrical
Delete in its entirety.
Chapter 28 Mechanical.
Delete in its entirety.
Chapter 29 Plumbing.
Delete in its entirety.
Section 3001.2 Referenced standards.
Delete all and insert "Referenced Standards to be as stringent
and comply with current Illinois Elevator Safety Act (225 ILCS 312/1
et seq.) and its Rules. For private residential conveyance application,
the Act does not apply; however, the IBC code shall for new installation,
permits, final acceptance. For applications not covered by the Illinois
Elevator Safety Act, those conveyance applications shall be covered
under the IBC code by the Building Official for new installation,
permits, final acceptance, periodic inspections and testing, unsafe
conditions, power to seal equipment, put conveyance out of service,
and certificate compliance as well as owner/agent responsibility for
contractor, maintenance, accident/injury responsibility.
"Referenced Standard from IBC 2015: Safety Code for Elevators
and Escalators (ASME A17.1), Performance Based Safety Code for Elevators
and Escalators (A17.7), Safety Standard for Platform Lifts and Stairway
Chairlifts (ASME A18.1), Safety Standard for Belt Manlifts (A90.1),
Safety Standard for Conveyors and Related Equipment (B20.1)
"Referenced Standards from (225 ILCS 312/1 et seq.): Safety
Code for Elevators and Escalators (ASME A17.1), the Standard for the
Qualification of Elevator Inspectors (ASME QEI-1), the Automated People
Mover Standards (ANSI/ASCE/T&DI 21), and the Safety Standard for
Platform Lifts and Stairway Chairlifts (ASME A18.1)."
Section 3001.3 Accessibility.
Delete all and insert "Accessibility shall conform to the 2018
State of Illinois Accessibility Code and ICC A117.1"
Section 3002.4. Elevator car to accommodate ambulance
stretcher.
Delete all and insert "Where elevators are provided in buildings,
not fewer than one elevator, shall be provided for fire department
emergency access to all floors regardless of rise.
"Such elevator car shall be of such size and arrangement to
accommodate a minimum twenty-four-inch by 84-inch ambulance stretcher
in the horizontal open position and shall be identified by the International
Symbol for emergency medical services (Star of Life).
"The symbol shall not be less than 3 x 3 inches high and wide
(76 mm x 76 mm) and shall be placed inside on both sides of the main
lobby hoistway door frame."
Section 3003.3 Standardized fire service elevator keys.
Delete all and insert "All elevators shall be equipped to operate
with a standardized fire service elevator key in accordance with the
International Fire Code for new and modernized elevators only."
Section 3004.4 Personnel and material hoists.
Delete all and insert "Personnel and material hoists shall be
designed utilizing an approved method that accounts for the conditions
imposed during the intended operation of the hoist device. The design
shall include, but is not limited to, anticipated loads, structural
stability, impact, vibration, stresses and seismic restraint. The
design shall account for the construction, installation, operation
and inspection of the hoist tower, car, machinery and control equipment,
guide members and hoisting mechanism. Additionally, the design of
personnel hoists shall include provisions for field testing and maintenance
that will demonstrate that the hoist device functions in accordance
with the design. Field tests shall be conducted upon the completion
of an installation or following a jump of a personnel hoist. All miscellaneous
hoisting and elevating equipment shall be subjected to tests and inspections
as required by the AHJ to ensure safe operation."
Section 3005.1 Access.
Insert after sentence "This means is not to be used as a passageway
through the space to other areas of the building."
Section 3005.4 Machine rooms, control rooms, machinery
spaces, and control spaces. Exception 2.
Delete all.
Add (new section) 3009.1 Certificate of compliance.
Insert "The operation of all equipment governed by the provisions
of this chapter and hereafter installed, relocated or altered shall
be unlawful by persons other than the installer until such equipment
has been inspected and tested as herein required and a final certificate
of compliance has been issued by the Building Official."
Add (new section) 3009.2 Posting certificate of compliance.
Insert "The owner or lessee shall post the current-issued certificate
of compliance in a conspicuous place inside the conveyance. A copy
of the current issued certificate is acceptable. Please refer to Illinois
Elevator Safety Act."
Chapter 32 Encroachments into the public right-of-way.
Delete in its entirety.
Section 3303.4 Vacant lot.
Insert after last sentence "The lot shall be maintained free
from the accumulation of rubbish and all other unsafe or hazardous
conditions which endanger the life or health of the public."
Add (new section) "3303.8 Removal of waste materials.
Insert "Removal of waste materials. Material shall not be dropped
by gravity or thrown outside the exterior walls of a building during
demolition or erection. Wood or metal chutes shall be provided for
the removal of such materials. Where the removal of any material will
cause an excessive amount of dust, such material shall be wet down
to prevent the creation of a nuisance."
Add (new section) 3307.2 Bracing, shoring and reinforcement
requirements.
Insert "For any excavation greater than three feet in depth
occurring within five feet of any property line or right-of-way, the
owner of the property to be excavated shall reinforce or brace adjacent
land, buildings and structures so as to prevent any sagging, settling,
cracking or collapse occurring to the adjacent land, sidewalks, fences,
structures, foundations or walls. Where bracing, shoring or reinforcement
is required because of the depth of excavation and distance to the
property line or right-of-way and where that excavation is less than
five feet in depth, an Illinois-licensed architect or professional
engineer shall design such bracing, shoring or reinforcement, and
shall stamp and seal the plans therefor. Where that excavation is
five feet or greater in depth, an Illinois-licensed structural engineer
shall design such bracing, shoring or reinforcement, and shall stamp
and seal the plans therefor. Installation of the bracing, shoring
or reinforcement shall be in accordance with such design requirements
and as directed by the structural or professional engineer. The owner
of the property to be excavated shall be responsible for the cost
of any required bracing, shoring or reinforcement."
Section 3310.1 Stairways required.
Delete all and insert "Where a new building is under construction
or where an existing building is being altered, at least one temporary
stairway shall be provided unless one or more of the permanent stairways
are erected as the construction progresses. Every required temporary
stairway that has three or more risers shall be provided with a handrail
for the full length of the run of the steps on at least one side."
Chapter 35 Referenced Standards: NFPA.
Delete all and insert "Reference the Village of Lincolnwood
Appendix A, List of Adopted NFPA Codes."