(a) This Article applies to oil-burning equipment for installation in
furnaces and boilers used for heating dwellings and for various commercial
and industrial applications. Note: For the installation of oil burners
in stoves and ranges originally designed for solid fuels, see separately
published regulations.
(b) This Article is intended to prescribe reasonable provisions for the
installation of oil-burning equipment, based on minimum requirements
for safety to life and property from fire. It covers the installation
of the oil burners and all equipment connected thereto, including
tanks, piping, pumps, control devices and all accessories. Careful
attention to the maintenance and proper operation of the equipment
is necessary for the continued safety of oil-burning equipment
(c) Definitions. Wherever the word "approved" appears in this Article,
it shall mean equipment, accessories, etc., as approved and in compliance
with the requirements of the National Board of Fire Underwriters.
[Ord. No. 27A,
§ II, 4-26-1935]
(a) No person shall install or operate or remodel an oil-heating burner
and/or no person shall store fuel oil in or on his or any premises
in the Village of Tuckahoe without having first applied for and obtained
a permit to do so from the Village Clerk. This permit shall be in
duplicate.
(b) Immediately upon being issued, one copy of the permit shall be framed
and protected by glass and be displayed in the room where the burner
is located, and it shall be prohibited for anyone to operate an oil
burner or supply fuel to the burner or place fuel in a tank connected
to a burner unless the permit is so displayed and in effect. A duplicate
copy of the permit shall be filed at the headquarters of the Eastchester
Fire Department.
[Ord. No. 27A,
§ III, 4-26-1935; Ord. of 7-29-1969]
An applicant for such permit shall pay to the Village Clerk
at the time of applying the sum of $10, which shall be retained whether
or not a permit is granted.
[Ord. No. 27A,
§ IV, 4-26-1935]
The application shall state the following information:
(1) Name and address of the applicant.
(2) Location where oil-burning equipment or fuel oil is to be stored.
(3) Maximum quantity of fuel oil to be stored.
(4) Dimensions of storage tank.
(7) Name of company installing.
(9) Whether or not the burner has been approved by the National Board
of Fire Underwriters.
[Ord. No. 27A,
§ V, 4-26-1935]
The Village Clerk shall make out an application in duplicate,
and forward this information to the Chief of the Fire Department who,
after inspection of the premises, shall endorse his recommendations
which he believes to be necessary for carrying out the provisions
of this Article. If in the opinion of the Fire Chief it is deemed
necessary to file and furnish a detailed plan, the same shall be drawn
to a scale of 1/4 inch to the foot showing clearly thereon the following:
(1) Location of building or buildings where burner or burners are to
be located.
(2) Nature of construction, dimensions of buildings and purpose for which
occupied.
(3) Size and layout of all piping connected with the installation.
[Ord. No. 27A,
§ VI, 4-26-1935]
Upon the filing of the application as required in §
8-38 and its approval by the Chief of the Fire Department, the Village Clerk may, upon his approval of the application, issue a permit for the installation of the equipment.
[Ord. No. 27A,
§ VII, 4-26-1935]
(a) Oil burners shall be of a type approved by the Laboratories of the
National Board of Fire Underwriters specifically for use in house
heating furnaces and boilers.
(b) Oil burners for which a competent attendant will not be constantly
on duty in the room where the burner is located, while the burner
is in operation, shall be arranged to prevent abnormal discharge of
oil at the burner by means of equipment specifically approved for
the burner with which it is used. Note: Burners so equipped are listed
by Underwriters' Laboratories as domestic oil burners.
(c) Oil burners for which a competent attendant will be constantly on
duty in the room where the burner is located, while the burner is
in operation, are not required to be equipped with automatic means
for preventing abnormal discharge of oil at the burner. When automatic
features are installed in connection with oil burners of this type,
such automatic devices shall be specifically approved for use with
the burner to which they are attached. Note: Oil burners of this type
are listed by Underwriters' Laboratories as industrial oil-burning
systems.
[Ord. No. 27A,
§ VIII, 4-26-1935]
(a) Fuel oil used with the burners to which these regulations apply shall
have a flash point of not less than 135° F., and shall be a hydrocarbon
oil, free from acid, grit and fibrous or other foreign matter likely
to clog or injure the burners or valves. The flash point shall be
determined by the Pensky-Martens Closed Tester, in accordance with
the method of test adopted by the American Society for Testing Materials
(ASTM) Designation D93-22), except that the Tag Closed Tester (ASTM
Designation D56-21) shall be authoritative in case of dispute concerning
oils having a flash point in the vicinity of 135° F.
(b) The grade of fuel oil used with any burner shall be one approved
by the list of inspected oil burners issued by Underwriters'
Laboratories which gives, for each burner, the minimum grade of fuel
oil for which the burner is suitable.
[Ord. No. 27A,
§ IX, 4-26-1935]
(a) Gravity feed shall be used only with burners arranged to prevent
abnormal discharge of oil at the burner by automatic means specifically
approved for the burner with which it is used.
(b) Gravity supply tanks shall not exceed 275 gallons' individual
capacity. Where more than one gravity supply tank is used, such tanks
shall be connected to the feed pipe leading to the burner through
a manually operated, approved three-way valve in such a way that only
one tank can discharge its contents at a time.
(c) Where oil is supplied to the burner by gravity and a constant level
device is not incorporated in the burner assembly or in an auxiliary
tank used in connection with an automatic pump, an approved constant
level device shall be installed in the oil feed line at the gravity
tank or as close thereto as practicable, to insure uniform delivery
of oil to the burner. The vent opening of such constant level device
shall be connected by piping or tubing to the gravity tank vent pipe.
[Ord. No. 27A,
§ X, 4-26-1935]
(a) Oil supply tanks shall preferably be located outside of buildings
and underground with the top of the tank below the level of all piping
to which the tank is connected to prevent discharge of oil through
a broken pipe or connection by syphoning.
(b) Underground tanks shall be so buried as to have a cover of earth
not less than two feet thick or shall be covered with not less than
one foot of earth, on top of which shall be placed a slab of reinforced
concrete not less than four inches thick. The slab shall be set on
a firm, well-tamped earth foundation and shall extend at least one
foot beyond the tank in all directions. Where tanks are buried underneath
buildings, such a concrete slab shall be provided in every instance.
[Ord. No. 27A,
§ XI, 4-26-1935; Ord. of 9-2-1952]
(a) Oil supply tanks larger than 60 gallons' capacity shall not
be located in buildings above the lowest story, cellar or basement.
(b) Unenclosed inside storage tanks not to exceed 275 gallons' capacity
shall not be located within seven feet, horizontally, of any fire
or flame.
(c) Oil supply tanks exceeding 275 gallons' individual capacity
in an individual building or in a section of a building separated
by firewalls shall be installed in an enclosure constructed as follows:
The walls of the enclosure shall be constructed of reinforced concrete
at least six inches thick or of brick at least eight inches thick.
Such enclosures shall be installed only on concrete or other fire-resistive
floors and shall be bonded to the floor. Enclosures shall have tops
of reinforced concrete at least five inches thick or equivalent fire-resistive
construction, except when the floor or roof construction above the
enclosure is concrete or other fire-resistive construction, the walls
may be extended to and bonded to the underside of the construction
above in lieu of the provision of a separate top. Any openings to
such enclosures shall be provided with fire doors or other approved
closures and six-inch noncombustible liquidtight sills or ramps. Provision
shall be made for adequate ventilation of such enclosures prior to
entering for inspection on or repairs to tanks. In buildings of ordinary
construction, the nominal gross capacity of tanks shall not exceed
5,000 gallons. In fire-resistive buildings, the nominal gross capacity
of tanks shall not exceed 15,000 gallons. In any building, if in a
fire-resistive or detached room cut off vertically and horizontally
in an approved manner from other floors of the main building, the
nominal gross capacity of tanks shall not exceed 50,000 gallons, with
an individual tank capacity not exceeding 25,000 gallons.
[Ord. No. 27A,
§ XII, 4-26-1935]
Outside aboveground tanks shall not be located within the fire
limits as defined in the building code of the Village of Tuckahoe.
[Ord. No. 27A,
§ XIII, 4-26-1935]
(a) Underground tanks shall be set on a firm foundation and surrounded
with soft earth or sand well-tamped in place. Where necessary to prevent
floating, they shall be securely anchored or weighted.
(b) Inside storage and auxiliary tanks shall be securely supported by
substantial incombustible supports to prevent settling, sliding or
lifting.
(c) Inside storage tanks shall be installed with the bottom pitched to
the draw-off or drain opening with a slope of not less than 1/4 inch
per foot of length. The draw-off or the drain opening shall be provided
with suitable piping connections in a form to provide a sump from
which water or sediment can be readily drained at regular intervals.
(d) Outside aboveground tanks shall be set on a firm foundation. Those
more than one foot above the ground shall have supports of masonry
or protected steel, except that wooden cushions may be used. No combustible
material shall be stored under or within 10 feet of outside aboveground
tanks.
[Ord. No. 27A,
§ XIV, 4-26-1935]
(a) Underground tanks and tanks inside buildings shall be constructed
of steel or wrought iron of a minimum gauge (U.S. Standard) in accordance
with the following table:
|
Capacity
(gallons)
|
Minimum Thickness
|
Weight
(pounds per square foot)
|
---|
|
7 to 560
|
14-gauge
|
3.125
|
|
561 to 1,110
|
12-gauge
|
4.375
|
|
1,001 to 4,000
|
7-gauge
|
7.50
|
|
4,001 to 12,000
|
1/4 inch (nominal)
|
10.00
|
|
12,001 to 20,000
|
5/16 inch
|
12.50
|
|
20,001 to 30,000
|
3/8 inch (nominal)
|
15.00
|
|
If an adequate internal bracing is provided, tanks of 12,001
to 30,000 gallons' capacity may be built of one-fourth-inch plate.
|
|
For tanks larger than 1,100 gallons' capacity, a tolerance
of 10% in capacity is permitted.
|
(b) Outside aboveground tanks, including tops, shall be constructed of
steel or wrought iron of a thickness in accordance with the following
requirements.
(1) Horizontal or vertical tanks not over 1,100 gallons' capacity:
|
Capacity
(gallons)
|
Minimum Thickness of Material
|
---|
|
1 to 560
|
14-gauge U.S. Standard
|
|
561 to 1,100
|
12-gauge U.S. Standard
|
(2) Horizontal tanks over 1,100 gallons' capacity:
a. Tanks having a diameter of not over six feet shall be made of at
least 3/16 inch steel or wrought iron.
b. Tanks having a diameter of over six feet and less than 11 1/2
feet shall be of at least 1/4 inch steel or wrought iron.
(c) Joints shall be riveted and caulked, brazed, welded or made tight
by some equally satisfactory process. Tanks shall be tight and sufficiently
strong to bear without injury the most severe strains to which they
may be subjected in practice. Shells of tanks shall be properly reinforced
where connections are made. All connections to storage tanks, other
than outside aboveground storage tanks, shall be made through the
top of tank above the liquid level, except that tanks of not over
275 gallons' capacity may have one bottom connection for gravity
feed and one opening for an approved key stem gate valve to facilitate
cleaning or for a scavenging line to be run to the outside and capped
oil tight when not in use.
(d) Tanks shall be thoroughly coated on the outside with tar, asphaltum
or other suitable rust-resisting paint. Where placed in corrosive
soil, special protection may be required.
[Ord. No. 27A,
§ XV, 4-26-1935]
(a) Storage tanks shall (except for hydraulic or inert gas systems) be
equipped with an open vent or an approved automatically operated vent,
arranged to discharge to the open air. Vent openings and vent pipes
shall be of ample size to prevent abnormal pressure in the tank during
filling but not smaller than two-inch pipe size.
(b) Vent pipes shall be arranged to drain to the tank. The lower end
of the vent pipe shall not extend through the top into the tank for
a distance of more than one inch.
(c) Vent pipes shall terminate outside of buildings at a point not less
than three feet measured horizontally from any window or other building
opening and not less than four feet vertically above filling pipe.
Outer ends of vent pipes shall be provided with a weatherproof hood.
Vent pipes should terminate sufficiently above the ground to prevent
their being obstructed with snow and ice. Vent pipes of tanks containing
heaters shall be extended to a location where oil vapors discharging
from the vent will be readily diffused without danger of ignition.
Vent pipes must be visible from point of fill.
(d) Vent pipes shall not be cross-connected with fill pipes or return
lines from burners.
(e) Vent openings on outside aboveground tanks shall be provided with
approved flame arresters.
(f) With the exception of vertical, cone-roof tanks having a roof slope
less than 2 1/2 inches in 12 inches and in which the strength
of the joint between roof and shell is no greater than that of the
weakest vertical joint in the shell, all aboveground tanks shall have
some form of relief for preventing the development of excessive internal
pressure in case of exposure to fire surrounding the tank. The method
of relief shall be acceptable to the inspection department having
jurisdiction.
[Ord. No. 27A,
§ XVI, 4-26-1935]
(a) Storage tanks, other than outside aboveground tanks, shall be filled
only through fill pipes terminating outside of buildings at the curbline,
except that, where this is impractical, the inspector may permit it
to terminate not less than 25 feet from any building, provided that
the hose from the filling truck shall not extend across the sidewalk.
Fill terminals shall be closed tight, when not in use, by a metal
cover designed to prevent tampering. In tanks containing heaters the
tank end of the fill pipe should be sealed by a trap or should be
extended to a point below the lower end of the suction pipe.
(b) Auxiliary tanks shall be filled by pumping from storage tanks.
(c) Cross connections permitting gravity flow from one tank to another
shall be prohibited. This, however, shall not be construed as prohibiting
the filling of an outside service tank by gravity, provided that filling
is through an open connection located within a dike surrounding the
service tank, and provided further that such dike shall have a capacity
equal to 1 1/2 times the capacity of the tank being filled.
(d) Auxiliary tanks other than vacuum tanks shall be equipped with an
overflow pipe draining to the storage tank, at least one size larger
than the supply pipe.
(e) Overflow pipes of auxiliary gravity tanks shall have no valves or
obstructions. Overflow pipes of auxiliary pressure tanks shall be
provided with interconnected valves or other means of automatically
venting the tank during filling.
[Ord. No. 27A,
§ XVII, 4-26-1935]
(a) All tanks in which a constant oil level is not maintained by an automatic
pump shall be equipped with an approved method of determining the
oil level.
(b) Test wells shall not be installed inside buildings and where permitted
for outside service shall be closed tight, when not in use, by a metal
cover designed to prevent tampering. The gauging of inside tanks by
means of measuring sticks shall not be permitted.
(c) Gauging devices such as liquid level indicators or signals shall
be installed so that oil or vapor will not be discharged into the
building from the fuel supply system.
[Ord. No. 27A,
§ XVIII, 4-26-1935]
(a) Oil pumps shall be approved type, secure against leaks and shall
be rigidly fastened in place.
(b) Automatic pumps not an integral part of the burner shall be arranged
to stop the flow of oil automatically in case of total breakage of
the supply line to the burner.
[Ord. No. 27A,
§ XIX, 4-26-1935]
(a) All piping shall be standard full weight wrought iron, steel or brass
pipe with standard fittings except that approved flexible metal hose
may be used for reducing the effects of jarring and vibration or where
rigid connections are impracticable.
(b) Pipe used in the installation of domestic type burners shall not
be smaller than 1/2 inch iron pipe size; pipe used in the installation
of industrial-type burners shall not be smaller than 1/2 inch iron
pipe size. Flexible metal hose shall be installed strictly in accordance
with the limitations of its approval.
(c) Piping shall be rigidly secured in place and protected from injury
in a workmanlike manner and, where necessary, shall be protected against
corrosion. Where practicable, oil piping shall be buried underground
or in a concrete floor or placed in a metal covered pipe trench. Oil
piping shall not be located close to other piping or in the same trench
with other piping, except steam or hot-water lines intended for heating
the oil.
(d) Pipe joints and connections shall be made tight in a workmanlike
manner. Union fittings shall be of an approved type. Unions requiring
gaskets or packing and right and left couplings shall not be used
in oil lines.
(e) Proper allowances shall be made for expansion, contraction, jarring
and vibration. Pipelines connected to underground tanks, except fill
lines and test wells, shall be provided with double swing joints arranged
to permit the tank to settle without impairing the efficiency of the
pipe connections.
(f) Where storage tanks are set below the level of the burner, the oil
piping should preferably be so laid as to pitch toward the storage
tank without traps.
(g) Openings for pipes through outside walls below the ground level shall
be made oiltight by securely packing with flexible material.
(h) Oil supply lines to burners shall be provided with approved strainers.
(i) All oil burners fed by oil pumps drawing from supply tanks located
above the level of the burner shall be equipped with an approved anti-syphoning
device at the highest point in the suction line.
[Ord. No. 27A,
§ XX, 4-26-1935]
(a) Readily accessible shutoff valves of approved type shall be installed
in oil supply lines near each burner and close to the supply tanks.
Shutoff valves of approved type shall be installed on each side of
oil strainers which are not a part of the oil burner unit, and on
the discharge and suction side of oil pumps which pump directly to
the burner but which are not a part of the burner unit.
(b) Where a shutoff valve is installed in the discharge line of an oil
pump, an approved pressure relief valve shall be connected into the
discharge line between the pump and the shutoff valve and arranged
to return surplus oil to the storage tank or to bypass it around the
pump.
(c) Control valves shall be of approved type provided with stuffing box
of liberal size, containing a removable cupped gland designed to compress
a packing against the valve stem and arranged so as to facilitate
removal. The valve shall be designed to close against the supply and
to prevent withdrawal of stem by continued operation of the handwheel.
Packing affected by the oil or heat shall not be used.
(d) An automatic shutoff valve controlled by a fusible link designed
to fuse at an approved temperature shall be installed at a location
immediately adjacent to the burner.
[Ord. No. 27A,
§ XXI, 4-26-1935]
(a) Preheating of oil, where necessary, shall be done by steam, hot water
or approved electric heaters. Heaters shall be substantially constructed
with all joints made oiltight. Thermometers shall be installed at
suitable locations to indicate temperature of the heated oil.
(b) Heaters shall be bypassed or provided with suitable means to prevent
abnormal pressure.
[Ord. No. 27A,
§ XXII, 4-26-1935]
After installation and before being covered, tanks and piping
shall be tested hydrostatically, or with equivalent air pressure,
at a pressure not less than 1 1/2 times the maximum working pressure
but not less than 10 pounds per square inch at the highest point of
the system. Tests should continue for at least 30 minutes without
a noticeable drop in pressure. The test shall be conducted in the
presence of an authorized representative of the Eastchester Fire Department
and at no expense to the Village.
[Ord. No. 27A,
§ XXIII, 4-26-1935]
(a) Oil-burning equipment shall be provided with some means for manually
stopping the flow of oil to the burner, from a conveniently located
point at a safe distance from the burner. With electrically driven
equipment this may be accomplished by an approved safety switch in
the motor supply circuit, placed near the entrance to the room where
the burner is located. A quick-closing valve in the oil supply line,
preferably located outside the building, may also be used.
(b) Automatically operated oil burners used in connection with hot-water,
steam or warm-air heating systems shall be equipped with approved
automatic devices to shut down the burner in the event of undue pressure
in a steam boiler or overheating within a hot-water boiler or warm
air furnace.
|
Oil burners used in connection with steam heating systems shall
be equipped with approved automatic devices for shutting down the
burner in the event of low water in the boiler. The device shall require
manual resetting or it shall prevent operation until the safe water
level is resumed.
|
(c) Limiting controls and low water shutoffs intended to disconnect the
burner from the electric power supply should be connected into the
burner supply circuit on the supply side of all other burner circuits.
(d) In systems where either steam or air is used for atomizing the oil,
the oil and atomizing supply shall be interlocked in an approved manner
so that in case of interruption of the atomizing supply, the oil supply
will be immediately shut off.
[Ord. No. 27A,
§ XXIV, 4-26-1935]
(a) Electric wiring and equipment in connection with oil-burning equipment
shall be installed in accordance with the Electrical Code of the Village
of Tuckahoe.
(b) An externally operated safety switch of a type approved by the Eastchester
Fire Department shall be provided and it shall be located at a point
designated by an authorized representative of the Eastchester Fire
Department.
[Ord. No. 27A,
§ XXV, 4-26-1935]
(a) Oil burners shall be securely installed in a workmanlike manner,
in accordance with the instructions of the manufacturer, by qualified
mechanics experienced in making such installations.
(b) Where oil burners are installed in furnaces originally designed for
solid fuel, the ash door of the furnace shall be removed or bottom
ventilation otherwise provided to prevent the accumulation of vapors
in the ash pit, unless the burner is of a type which mechanically
purges the ash pit.
(c) Boilers and furnaces in which oil burners are installed shall be
connected to flues having sufficient draft at all times to assure
safe operation of the burner. Smoke pipe dampers, if any, shall be
such that they cannot close off more than 80% of the internal cross
section area of the smoke pipe.
(d) Rooms in which oil burners are located shall be provided with adequate
ventilation to assure continuous complete combustion of the oil.
(e) Complete instructions for the care and operation of the oil-burning
equipment shall be conspicuously posted near the oil burner and maintained
in readable condition.
(f) Contractors installing industrial oil-burning systems shall furnish
diagram showing the main oil lines and controlling valves, one of
which shall be posted near the oil-burning equipment and another at
some point which will be accessible, in case of fire, at the burners.
[Ord. No. 27A,
§ XXV, 4-26-1935]
Any person who himself or itself or by his or its agents or employee shall violate any of the provisions of this Article or any order, rule or regulation made in pursuance thereof, shall, upon conviction thereof, be subject to a penalty prescribed in §
1-7, and each day on which such violation continues shall constitute a separate offense and such violation shall constitute disorderly conduct and the person so offending shall be deemed a disorderly person.