[Ord. 603, 2/10/1987, § 901]
Backflow prevention devices required by this Part shall be installed at a location and in a manner approved by the Borough and shall be installed by a person properly qualified and at the expense of the consumer, if approved as such by the Borough.
[Ord. 603, 2/10/1987, § 902]
Backflow prevention devices installed on the service line to a consumer's water system shall be located on the consumer's side of the water meter, as close to the meter as is reasonably practical and prior to any other connection.
[Ord. 603, 2/10/1987, § 903]
Pits or vaults shall be of watertight construction, be so located and constructed as to prevent flooding and shall be maintained free from standing water by means of either a sump pump or a suitable drain. Such sump pump or drain shall not connect to a sanitary sewer nor permit flooding of the pit or vault by reverse flow from its point of discharge. An access ladder and adequate natural or artificial lighting shall be provided to permit maintenance, inspection and testing of the backflow prevention device.