Unless otherwise expressly stated, the following terms shall,
for the purpose of this Code, have the meaning indicated in this section.
ACCESS BOX
A steel key vault, mounted on the exterior of a building
that contains keys, floor plans, maps or other items as required by
the AHJ, for access to all portions of the building.
ADULT DAY CARE
Any place that receives at any time for compensation four
or more adults, for care and supervision, for less than 24 hours a
day.
ADULT FAMILY HOME
Similar to a CBRF except that they are licensed for five
or less tenants.
APPROVED AGENCY
An agency accepted or acceptable to the Bureau of Fire Prevention,
such as Underwriters Laboratories, Inc., the National Institute of
Standards and Technology, the American Gas Association laboratories
or other nationally recognized testing authorities.
ASSEMBLY GROUP A
Group A occupancies includes, among other, the use of a building
or structure, or a portion thereof, for the gathering together of
persons for purposes such as civic, social or religious functions,
recreation, food or drink consumption or awaiting transportation.
A room or space used for assembly purposes by less than 50 persons
and accessory to another occupant shall be included as a part of that
occupancy. Assembly occupancies shall include the following:
A.
A-1: Assembly uses, usually with fixed seating, intended for
the production and viewing of performing arts or motion pictures.
B.
A-2: Assembly uses intended for food and/or drink consumption.
C.
A-3: Assembly uses intended for worship, recreation or amusement
and other assembly uses not classified elsewhere in Group A.
D.
A-4: Assembly uses intended for viewing of indoor sporting events
and activities with spectator seating.
E.
A-5: Assembly uses intended for participation in or viewing
outdoor activities.
AUTHORITY HAVING JURISDICTION (AHJ)
Shall be the Fire Chief, or designee of the Fire Chief, to
enforce this Code, the laws of the State of Wisconsin, as designated
in § SPS 314.02(1), Wis. Adm. Code, pertaining to the prevention
of fires and public safety, and approving equipment installation,
or procedures as outlined in NFPA Standards, Codes and/or Recommended
Practices.
AUTOMATIC CLOSING DEVICE
Means one which functions without human intervention and
is actuated as a result of predetermined temperature rise, rate of
rise of temperature, combustion products or smoke density.
AUTOMATIC FIRE ALARM SYSTEM
A system which automatically detects fire condition and actuates
notification appliances throughout the protected premises.
AUTOMATIC FIRE SPRINKLER SYSTEM
An integrated system of underground and/or overhead piping
designed in accordance with fire protection standards. The system
includes a suitable water supply. The portion of the system above
ground is a network of specially sized or hydraulically designed piping
installed in a structure or area, generally overhead, and to which
automatic sprinklers are connected in a systematic pattern. The system
is usually activated by heat from a fire and discharges water over
the fire area.
AUTOMATIC FIRE-EXTINGUISHING SYSTEM
An approved system of devices and equipment which automatically
detects a fire and discharges an approved fire-extinguishing agent
onto or in the area of fire.
BASEMENT
That portion of a building that is partly or completely below
grade plane. A basement shall be considered as a story.
BOARDING HOUSE
A building arranged or used as lodging for compensation,
with or without meals, not occupied as a single-family unit.
BUREAU OF FIRE PREVENTION
The Bureau of Fire Prevention is made up of the following
personnel: the Fire Chief, the Fire Marshal and/or Fire Inspectors,
or any other Designee of the Chief.
BUSINESS GROUP B
Group B occupancy includes, among others, the use of a building
or structure, or a portion thereof, for office, professional or service-type
transactions, including storage of records and accounts.
CARBON MONOXIDE (CO) DETECTOR
An electric powered or battery-operated device that sounds
an alarm when an unsafe level of carbon monoxide is in the air.
CEILING
The upper surface of a space, regardless of height. Areas
with a suspended ceiling would have two ceilings, one visible from
the floor, and one above the suspended ceiling.
CODE
A standard that is an extensive compilation of provisions
covering a broad subject matter or that is suitable for adoption into
law independently of other codes and standards.
COMBUSTIBLE MATERIAL
All materials not classified as "noncombustible" are considered
combustible. This property of a material does not relate to its ability
to structurally perform under fire exposure. The degree of combustibility
is not defined by standard fire test procedures.
COMMON AREA
Any area in a building that can be accessed by more than
one person from different families at one time.
COMMUNITY-BASED RESIDENTIAL FACILITY (CBRF)
A community facility where five or more adults who are not
related to the operator or administrator and who do not require care
above intermediate level nursing care reside and receive care, treatment
or services that are above the level of room and board, but that include
no more than three hours of nursing care per week per resident.
CONDITIONAL APPROVAL
An approval of plans and/or specifications by the AHJ based
upon information provided to the AHJ, including, but not limited to,
any changes required by the AHJ to the abovementioned plans and/or
specifications.
CONSULTANT(S)
A company, individual or agency hired by the Bureau of Fire
Prevention to provide advice to the Bureau of Fire Prevention on fire-related
issues. Consultants may provide services, which could include plan
reviews of fire suppression systems, fire alarm systems, witness tests
and/or conduct inspections.
DAY-CARE CENTER
Any place which receives at any one time for compensation
four or more children under the age of seven years, for care and supervision,
for less than 24 hours a day or more than 10 days a month, without
the attendance of a parent, relative or legal guardian.
DWELLING or DWELLING UNIT
A single unit providing living facilities for one or more
persons, including permanent provisions for living, sleeping, eating,
cooking and sanitation. For the purpose of this Code, "dwelling unit"
includes apartments and condominiums but does not include hotel and
motel rooms, guest suites, dormitories, boarding rooms, or sleeping
rooms in nursing homes.
B.
TWO-FAMILY DWELLINGA detached building containing not more than two individual dwelling units which are entirely separated by vertical walls or horizontal floors, unpierced except for access to the outside or common basement.
EDUCATIONAL GROUP E
Group E occupancy includes, among others, the use of a building
or structure, or a portion thereof, by six or more persons at any
one time for educational purposes through the 12th grade.
FACTORY INDUSTRIAL GROUP F
Group F occupancy includes, among others, the use of a building
or structure, or a portion thereof, for assembly, disassembly, fabricating,
finishing, manufacturing, packaging, repair or processing operations
that are not classified as Group H occupancy.
A.
F-1: Moderate-hazard occupancy.
B.
F-2: Low-hazard occupancy.
FALSE ALARM
The willful and knowing initiation or transmission of a signal,
message or other notification of an event of fire when no such danger
exists.
A.
MALICIOUS ALARMA false alarm of fire deliberately sounded by someone in order to inconvenience the Fire Department.
B.
ACCIDENTAL ALARMAn alarm set off and transmitted through accidental operation of an automatic or manual fire alarm device.
FAMILY UNIT
Two or more individuals who are related to each other by
blood, marriage, adoption or legal guardianship. For purposes of this
abode a group of not more than four persons not necessarily related
by blood or marriage, living together in a single living unit, will
be considered equivalent to a single family.
FIRE ALARM ANNUNCIATION DEVICE
A device connected to a fire alarm to signal either a fire
or trouble condition. Fire alarm annunciation devices could include
visual devices, horn/strobes, horns, bells, and/or annunciator panels.
FIRE ALARM INITIATING DEVICE
A device connected to a fire alarm system that causes a trouble,
supervisory and/or alarm signal to be initiated. Fire alarm initiating
devices could include: smoke, heat, flame, ionization, or photoelectric
detectors, water flow, low air, low temperature, low water, or supervisory
switches.
FIRE ALARM SYSTEM
A system or portion of a combination system that consists
of components and circuits arranged to monitor and annunciate the
status of the fire alarm or supervisory signal-initiating devices
to activate notification appliances throughout the protected premises
and to initiate the appropriate response to those signals.
FIRE CONTROL SYSTEM
A system designed and constructed with the intent of controlling
or limiting a fire. Fire control systems may be automatic or nonautomatic.
Fire control systems could include automatic fire sprinkler systems,
standpipe systems, chemical agent systems, fire hydrants and/or any
other system acceptable to the AHJ.
FIRE DEPARTMENT CONNECTION (FDC)
A part of a sprinkler, standpipe, deluge and/or combination
system to be used by the Fire Department to pump additional water
into the system(s) it is connected to.
FIRE DOOR ASSEMBLY
Any combination of a fire door, frame, hardware, and other
accessories that together provide a certain degree of fire protection
to the opening.
FIRE RESISTIVE
That property of materials of their assemblies that prevents
or retards the passage of excessive heat, hot gases or flame under
conditions of use. Materials are tested as prescribed in Section 703
of the Wisconsin Enrolled Building Code.
FIREWALL
A fire-resistance-rated wall having protected openings, which
restricts the spread of fire and extends continuously from the foundation
to or through the roof, with sufficient structural stability under
fire conditions to allow collapse of construction on either side without
collapse of the wall.
FLOOR AREA OR SQUARE FOOTAGE OF A BUILDING
Refers to the total square footage of the sums of all basement,
floor levels, balconies and mezzanines.
A.
The area for basements and floor levels shall be measured from
the outside perimeter of the outside walls.
B.
The area for mezzanines shall be determined from the product
of the length of the mezzanine multiplied by the width of the mezzanine.
C.
For the purpose of determining square footage, fire division
walls will not be accepted as outside walls or area dividers.
D.
Buildings that are in close proximity to each other will have
their building square footage added together to arrive at the total
square footage.
(1)
For the purpose of determining close proximity the following
will hold true:
(a)
Single-story buildings: 30 feet apart or less.
(b)
Two-story buildings: 60 feet apart or less.
(c)
Three-story buildings: 60 feet apart or less.
(d)
All other multiple-story buildings: 60 feet apart.
(e)
Buildings of variable height next to each other: 30 feet apart
or less.
(2)
For the purpose of determining square footage, a fire wall which
has a fire resistance rating of not less than four hours and which
subdivides or separates a building to restrict the spread of fire,
including a three-foot parapet wall is an approved area divider.
FLOOR, GROUND
That level of a building on a sloping or multilevel site
which has a floor line at or not more than three feet above exit discharge
grade for at least 1/2 of the required exit discharges.
FOSSIL FUEL
Means coal, natural gas, oil, wood, propane or kerosene.
FREQUENTER
Means every person, other than an employee, who may go in
or be in a place of employment or public building under circumstances
which render such person other than a trespasser. Such term includes
a pupil or student when enrolled in or receiving instruction at an
educational institution.
GRADE PLANE
A reference plane representing the average of finished ground
level adjoining the building exterior walls. Where the finished ground
level slopes away from the exterior walls, the reference plane shall
be established by the lowest points within the area between the building
and the lot line or, where the lot line is more than six feet from
the building, between the building and a point six feet from the building.
HAZARDOUS GROUP H
Group H occupancy includes, among others, the use of a building
or structure, or a portion thereof, that involves the manufacturing,
processing, generation or storage of materials that constitute a physical
or health hazard in quantities in excess of those found in Tables
307.7(1) through 307.7(4) of the International Building Code.
A.
H-1: Buildings and structures which contain materials that pose
a detonation hazard.
B.
H-2: Buildings and structures which contain materials that pose
a deflagration hazard or a hazard from accelerated burning.
C.
H-3: Buildings and structures which contain materials that readily
support combustion or pose a physical hazard.
D.
H-4: Buildings and structures which contain materials that are
health hazards.
E.
H-5: Semiconductor fabrication facilities and comparable research
and development areas in which hazardous production materials are
used and the aggregate quantity of materials is in excess of those
listed in Tables 307.7(1) and 307.7(2) of the International Building
Code.
HEIGHT, BUILDING
The vertical distance from the grade plane to the average
height of the highest roof surface.
INSTITUTIONAL GROUP I
Group I occupancy includes, among others, the use of a building
or structure, or a portion thereof, in which people having physical
limitations because of health or age are harbored for medical treatment
or other care or treatment, or in which people are detained for penal
or correctional purposes or in which the liberty of the occupants
is restricted. Institutional occupancies are classified as I-1, I-2,
I-3 or I-4, as described in the International Building Code.
LISTED
Means included in a list published by a nationally recognized
testing laboratory, inspection agency, or other organization concerned
with product evaluation, that maintains periodic inspection of production
of listed equipment or materials and whose listing states either that
the equipment or materials meet nationally recognized standards or
has been tested and found suitable for use in a specified manner.
MANUAL FIRE ALARM SYSTEM
A system or portion of a combination system that consists
of components and circuits arranged to initiate the Notification Appliances
and appropriate response to those signals only after a person manually
activates the fire alarm system.
MERCANTILE GROUP M
Group M occupancy includes, among others, building and structures
or a portion thereof, for the display and sale of merchandise, and
involves stock of goods, wares or merchandise incidental to such purposes
and accessible to the public.
MEZZANINE or MEZZANINE FLOOR
An intermediate level or levels between floor and ceiling
of any story with an aggregate floor area of not more than one-third
of the area of the room or space in which the level or levels are
located.
MISCELLANEOUS GROUP U
Buildings and structures of an accessory character and miscellaneous
structures not classified in any specific occupancy shall be constructed,
equipped and maintained to conform to the requirements of this Code
commensurate with the fire and life hazard incidental to their occupancy.
MULTIFAMILY DWELLING
A building or portion thereof containing three or more dwelling
units, such as tenements, apartments, or rooming houses. Row houses
with fire walls extending from the basement to the underside of the
roof separating each living unit are not considered multifamily for
the purpose of this chapter.
NFPA
The National Fire Protection Association.
NONCOMBUSTIBLE MATERIALS
A noncombustible material is one which, in the form in which
it is used, meets one of the requirements listed below. Materials
used adjacent to or in contact with heat producing appliances, warm
air ducts, plenums and chimneys shall be classified as noncombustible
only on the basis of the requirement in Subsection A. Noncombustible
does not apply to the flame-spread characteristics of interior finish
or trim materials. No material shall be classified as noncombustible
building construction material, which is subject to increase in combustibility
or Flame-Spread Classification (FSC) beyond the limits herein established
through the effects of age, moisture or other atmospheric conditions.
(See flame spread rating in Wis. Adm. Code.)
A.
Materials which pass the test procedure of ASTM E-136 for noncombustibility
of elementary materials when exposed to a furnace temperature of 1,382°
F. for a minimum period of five minutes and do not cause a temperature
rise of the surface or interior thermocouple in excess of 54°
F. above the furnace air temperature at the beginning of the test
and which do not flame after exposure of 30 seconds.
B.
Materials having structural base of noncombustible material as defined in Subsection
A, with a surfacing not more than 1/8 inch thick which has a Flame-Spread Classification (FSC) not greater than 50 when tested in accordance with the method of test for surface burning characteristics of building materials (ASTM E-84).
NOTIFICATION APPLIANCE
A fire alarm system component such as a bell, horn, speaker,
light, or text display that provides audible, tactile, visible outputs,
or any combination thereof.
OCCUPANT(S)
The person or persons who physically reside, work or are
present in a facility.
OTHER TERMS
Other terms not defined herein used in this section shall
be as defined in the International Fire Code section 202 and are adopted
herein by reference.
OWNER
Includes his duly sworn agent or attorney, a purchaser, devisee,
fiduciary or person having a vested or contingent interest in the
property in question.
PLACES OF EMPLOYMENT
Includes every place, whether indoors or out or underground
and the premises appurtenant thereto where either temporarily or permanently
any industry, trade or business is carried on, or where any process
or operation, directly or indirectly related to any industry, employed
by another for direct or indirect gain or profit, but does not include
any place where persons are employed in private domestic service which
does not involve the use of mechanical power or in farming.
REMODEL
To remodel, alter or both, means to change any building or
structure which affects the structural strength, fire hazard, internal
circulation, or exits of the existing building or structure. This
definition does not apply to maintenance, reroofing, or alterations
to the heating and ventilating or electrical system.
RESIDENTIAL GROUP R
Group R occupancy includes, among others, the use of a building
or structure, or portion thereof, for sleeping accommodations when
not classed as an Institutional Group I.
A.
R-1: Residential occupancies where the occupants are primarily
transient in nature.
B.
R-2: Residential occupancies containing more than two dwelling
units where occupants are primarily permanent in nature.
C.
R-3: Residential occupancies where the occupants are primarily
permanent in nature and not classified R-1, R-2 or I, and where buildings
do not contain more than two dwelling units or adult and child care
facilities, that provide accommodations for five or fewer persons
of any age for less than 24 hours.
D.
R-4: Residential occupancies shall include buildings arranged
for occupancy as residential care/assisted living facilities including
five but not more than 16 occupants, excluding staff.
ROOF SPACES
Buildings with combustible roofs shall have all roof spaces
subdivided every 3,000 square feet by one-hour rated partitions unless
protected by an approved automatic fire sprinkler system. All openings
must have a minimum of a one-hour rated self-closing door.
ROOMING HOUSE
Means any building which has a room or rooms for sleeping,
without permanent provisions for cooking. Rooming house rooms do not
include any room in a one- or two-family dwelling.
ROUGH INSPECTION
Visual observation from the floor and/or ground level of
any system and/or component thereof required by this Code prior to
being concealed in any way by any means.
ROW HOUSE
A place of abode arranged to accommodate three or more attached
side-by-side or back-to-back living units.
SHALL
Indicates a mandatory requirement.
SHOULD
Indicates a recommendation or that which is advised but not
required.
SPACING
A horizontally measured dimension relating to the allowable
coverage limits of fire detectors, automatic sprinkler systems, and
fire alarm visual notification devices.
SPS
State of Wisconsin Department of Safety and Professional
Services.
STANDARD
A document, the main text of which contains only mandatory
requirements using the word "shall" to indicate mandatory requirements
and which is in a form generally suitable for reference by another
standard or code for adoption into law.
STORAGE GROUP S
Group S occupancy includes, among others, the use of a building
or structure, or portion thereof, for storage that is not classed
as Hazardous Group H.
A.
S-1: (Moderate-Hazard Storage) Buildings occupied for storage
uses which are not classified as S-2.
B.
S-2: (Low-Hazard Storage) Building used for storage of noncombustible
material such as products on wood pallets or in paper cartons with
or without single thickness divisions or in paper wrappings. Such
products may have negligible amount of plastic trim such as knobs,
handles, or film wrapping.
STORY
That portion of a building included between the upper surface
of a floor and the upper surface of the floor or roof next above.
To determine the number of stories in a building, all floors will
be counted whether they are above grade or below grade, including
basements, sub-basements, and ground floors, but not including penthouses
or mezzanines less than 1/3 of a story.
THROUGHOUT
For the purpose of this Code, "throughout" shall mean the
following:
A.
For automatic fire sprinkler systems, providing fire sprinkler
protection in all areas of a structure as required by NFPA 13.
B.
For automatic fire alarm system, installing detection, audible
and visual notification devices in all areas of the protected premises
installed in accordance with NFPA 72.
C.
For manual fire alarm systems, installing audible and visual
notification devices in all areas of the protected premises installed
in accordance with NFPA 72.
WATER FLOW TEST
A test of an available water supply that indicates the quantity
of water flowing out of a specific orifice, at a specific pressure,
at a specific point in time.
WELFARE
Includes comfort, decency and moral well-being.
Unless otherwise indicated or referenced in Ch. SPS 314, Wis.
Stats., the latest edition of the following NFPA publications published
on or before the effective date of this Code are adopted by reference,
enforced and incorporated into this Code as if fully set forth herein.
This list is not meant to be all inclusive.
NFPA 1
|
Fire Code
|
NFPA 10
|
Standard for Portable Fire Extinguishers
|
NFPA 11
|
Standard for Low-, Medium- and, High-Expansion Foam
|
NFPA 12
|
Standard on Carbon Dioxide Extinguishing Systems
|
NFPA 13
|
Standard for the Installation of Sprinkler Systems
|
NFPA 13D
|
Standard for the Installation of Sprinkler Systems in One and
Two-Family Dwellings and Manufactured Homes
|
NFPA 13R
|
Standard for the Installation of Sprinkler Systems in Low-Rise
Residential Occupancies
|
NFPA 14
|
Standard for the Installation of Standpipes, and Hose Systems
|
NFPA 15
|
Standard for Water Spray Fixed Systems
|
NFPA 16
|
Standard for the Installation of Foam-Water Sprinkler and Foam-Water
Spray Systems
|
NFPA 17
|
Standard for Dry Chemical Extinguishing Systems
|
NFPA 17A
|
Standard for Wet Chemical Extinguishing Systems
|
NFPA 20
|
Standard for the Installation of Stationary Pumps
|
NFPA 22
|
Standard for Water Tanks for Private Fire Protection
|
NFPA 24
|
Standard for the Installation of Private Fire Service Mains
|
NFPA 25
|
Standard for Water-Based Fire Protection Systems
|
NFPA 30
|
Flammable and Combustible Liquids Code
|
NFPA 30A
|
Code for Motor Fuel Dispensing Facilities and Repair Garages,
|
NFPA 30B
|
Code for the Manufacture and Storage of Aerosol Products
|
NFPA 33
|
Standard for Spray Application Using Flammable or Combustible
Materials
|
NFPA 34
|
Standard for Dipping, Coating and Printing Processes Using Flammable
or Combustible Liquids
|
NFPA 35
|
Standard for the Manufacture of Organic Coatings
|
NFPA 36
|
Standard for Solvent Extraction Plants
|
NFPA 37
|
Standard for Stationary Combustion Engines and Gas Turbines
|
NFPA 40
|
Standard for the Storage and Handling of Cellulose Nitrate Film
|
NFPA 45
|
Standard on Fire Protection for Laboratories Using Chemicals,
|
NFPA 51
|
Standard for the Design and Installation of Oxygen-Fuel Gas
Systems for Welding, Cutting, and Allied Processes
|
NFPA 51B
|
Standard for Welding, Cutting, and Other Hot Work
|
NFPA 54
|
National Fuel Gas Code
|
NFPA 55
|
Compressed Gases and Cryogenic Fluids Code
|
NFPA 58
|
Liquefied Petroleum Gas Code
|
NFPA 59
|
Utility LP-Gas Plant Code
|
NFPA 59A
|
Standard for Liquefied Natural Gas (LNG)
|
NFPA 61
|
Standard for Fires and Dust Explosions in Agricultural and Food
Processing Facilities
|
NFPA 68
|
Standard on Explosion Protection by Deflagration Venting
|
NFPA 69
|
Standard on Explosion Prevention Systems
|
NFPA 70
|
National Electrical Code®
|
NFPA 72
|
National Fire Alarm and Signaling Code
|
NFPA 75
|
Standard on Information Technology Equipment
|
NFPA 76
|
Standard on Telecommunications Facilities
|
NFPA 80
|
Standard for Fire Doors and Other Opening Protectives
|
NFPA 82
|
Standard on Incinerators and Waste and Linen Handling Systems
and Equipment
|
NFPA 85
|
Standard on Boiler and Combustion Systems Hazards
|
NFPA 86
|
Standard for Ovens and Furnaces
|
NFPA 88A
|
Standard for Parking Structures
|
NFPA 91
|
Standard for Exhaust Systems for Air Conveying of Gases, etc.
|
NFPA 96
|
Standard for Ventilation Control and Fire Protection of Commercial
Operations
|
NFPA 99
|
Health Care Facilities Code
|
NFPA 99B
|
Standard for Hypobaric Facilities
|
NFPA 101
|
Life Safety Code®
|
NFPA 102
|
Standard for Grandstands, Folding and Telescopic Seating, Tents,
and Membrane Structures
|
NFPA 105
|
Standard on Smoke Door Assemblies and Other Opening Protective
|
NFPA 110
|
Standard for Emergency and Standby Power Systems
|
NFPA 111
|
Standard on Stored Electrical Energy Emergency and Standby Power
Systems
|
NFPA 115
|
Standard on Laser Fire Protection
|
NFPA 160
|
Standard on Flame Effects Before an Audience
|
NFPA 170
|
Standard for Fire Safety and Emergency Symbols
|
NFPA 204
|
Standard for Smoke and Heat Venting
|
NFPA 211
|
Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning
Appliances
|
NFPA 214
|
Standard on Water-Cooling Towers
|
NFPA 221
|
Standard for High Challenge Fire Walls, Fire Walls, and Fire
Barrier Walls
|
NFPA 232
|
Standard for the Protection of Records
|
NFPA 241
|
Standard on Construction, Alteration, and Demolition Operations
|
NFPA 291
|
Standard on Fire Flow Testing and Marking of Hydrants
|
NFPA 303
|
Standard on Marinas and Boatyards
|
NFPA 307
|
Standard on Marine Terminals, Piers, and Wharves
|
NFPA 318
|
Standard on Semiconductor Fabrication Facilities
|
NFPA 400
|
Hazardous Materials Code
|
NFPA 418
|
Standard on Heliports
|
NFPA 484
|
Standard on Combustible Metals
|
NFPA 495
|
Explosive Materials Code
|
NFPA 499
|
Standard on Combustible Dusts and Hazardous (Classified) Locations
for Electrical Installations in Chemical Process Areas
|
NFPA 654
|
Standard on Fire and Dust Explosions from Manufacturing Combustible
Particulate Solids
|
NFPA 655
|
Standard on Sulfur Fires and Explosions
|
NFPA 664
|
Standard on Fires and Explosions in Wood Processing and Woodworking
Facilities
|
NFPA 704
|
Standard on the Identification of Hazards of Materials for Emergency
Response
|
NFPA 720
|
Standard on Carbon Monoxide Detection and Warning Equipment
|
NFPA 750
|
Standard on Water Mist Fire Protection Systems
|
NFPA 780
|
Standard on Lightning Protection Systems
|
NFPA 801
|
Standard for Facilities Handling Radioactive Materials
|
NFPA 804
|
Standard for Advanced Light Water Reactor Electric Generating
Plants
|
NFPA 850
|
Standard on Electric Generating Plants
|
NFPA 853
|
Standard on Stationary Fuel Cell Power Systems
|
NFPA 1123
|
Standard on Fireworks Display
|
NFPA 1124
|
Standard on Fireworks and Pyrotechnic Articles
|
NFPA 1125
|
Code for the Manufacture of Model Rocket and High Power Rocket
Motors
|
NFPA 1126
|
Standard on Pyrotechnics Before a Proximate Audience
|
NFPA 2001
|
Standard on Clean Agent Fire Extinguishing Systems
|
NFPA 2010
|
Standard for Fixed Aerosol Fire Extinguishing Systems
|
The Code shall not be construed to affect the responsibility
of any persons owning, operating, or installing equipment, for injury
to persons or damage to property caused by any defect therein, nor
shall the municipality, any person, firm, company or agent(s) for
the municipality be held as assuming such liability by reason of any
inspection or reinspection authorized herein or the permit issued
herein provided or by reason of the disapproval or approval of any
equipment and/or system authorized herein.
At the adoption of this Code all CBRFs, adult family homes,
adult day-care centers and child day-care centers (group) will be
inspected not less than once a year by the Fire Department. A courtesy
fire inspection is recommended for all family child day cares.
Fees shall be established for certificates, approvals, and other
functions performed under this code and shall be payable to the municipality.
Such fees shall accompany each application for such approval, certificate,
or other fee related code provision. Fees are subject to change. All
fees pertain to new construction and the remodeling of existing building
or occupancies.
Any person who violates any of the provisions of this Code,
or who fails to comply with any order made hereunder, or who builds
in violation of any detailed statement of specifications or plans
submitted and conditionally approved hereunder, or any certificate
or permit herein from which no such appeal has been taken, or who
fails to comply with such an order as affirmed or modified by a court
of competent jurisdiction within the time fixed herein, shall for
each and every violation and noncompliance be subject to the following:
A. Imposition by forfeiture of $200 per day by the Municipal Court.
B. Imposition of a penalty for each such violation shall not excuse
the violation or permit it to continue and such violations or defects
shall be corrected or remedied within the time stated in the order.
Each and every day that a violation of this Code occurs constitutes
a separate offense.
C. False alarms. In one calendar year, if the Fire Department responds to three or more false alarms as described in the definition of "false alarms" in §
27.02, the Fire Department may:
(1) Introduce a fine to the building owner or occupant to reimburse the
Fire Department for the cost of equipment and personnel that was used
to respond to the alarm.
(2) Require that the fire alarm be serviced, upgraded, or replaced to
bring the system into compliance with current code in order to prevent
future false alarms.