Exciting enhancements are coming soon to eCode360! Learn more 🡪
Township of Vanport, PA
Beaver County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[HISTORY: Adopted by the Board of Commissioners of the Township of Vanport as indicated in article histories. Amendments noted where applicable.]
GENERAL REFERENCES
Construction standards — See Ch. 83.
Excavating, filling and grading — See Ch. 95.
Inspections, sewer and water — See Ch. 106.
Sewers — See Ch. 145.
[Adopted 9-14-1998 by Ord. No. 282]
A. 
Purpose. The purpose of this article is to:
(1) 
Protect the public water supply system from contamination or pollution by isolating within the consumer's water system contaminants or pollutants which could backflow through the service connection into the public water supply system.
(2) 
Promote the elimination or control of existing cross-connections, actual or potential, between the public or consumer's potable water system and nonpotable water systems, plumbing fixtures and sources or systems containing process fluids.
(3) 
Provide for the maintenance of a continuing program of cross-connection control which will systematically and effectively prevent the contamination or pollution of the public and consumer's potable water system.
B. 
Application. This article shall apply to all premises served by the public water supply system maintained and operated by the Vanport Township Municipal Authority within the Township of Vanport.
C. 
Policy. The public water supplier and the consumer have the joint responsibility for protection of the public water supply system from contamination due to backflow of contaminants through the water service connection. If, in the judgment of the public water supplier or its authorized representative, an approved backflow prevention device is required, the supplier shall give notice to the consumer to install such approved backflow prevention device at each service connection to his premises. The consumer shall immediately install such approved device or devices at his own expense and failure, refusal or inability on the part of the consumer to install such device or devices shall constitute grounds for discontinuing water service to the premises until such device or devices have been installed.
For the purpose of this article, the following words shall have the meanings indicated unless clearly indicated otherwise in the text:
ACCEPTABLE CROSS-CONNECTION
A cross-connection having all of the following characteristics:
A. 
The source of the supply other than the lines of the Vanport Township Municipal Authority, directly connected, is a source approved by the Pennsylvania Department of Environmental Protection as an acceptable, safe and sanitary source of public water supply and which continues as such at all times when the cross-connection is in existence.
B. 
It is installed or continued in existence with the knowledge and specific consent of the Authority, and, when installed on the premises of a customer or installed by a customer, such consent shall be evidenced by proper written agreements or approval.
C. 
It is installed or continued in existence and operated at all times in strict compliance with all applicable laws, ordinances, rules and regulations.
ACT or THE ACT
The Federal Water Pollution Control Act, also known as the "Clean Water Act," as amended, 33 U.S.C. § 1251 et seq.
AIR GAP
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture or to other devices and the flood level rim of said vessel. An approved air gap shall be at least double the diameter of the supply pipe, measured vertically, above the top of the rim of the vessel and, in no case, less than one inch. When an air gap is used at the service connection to prevent the contamination or pollution of the public potable water system, it is required that an emergency bypass be installed around the air gap system and an approved reduced pressure principle device shall be installed in the bypass system.
APPROVED
A. 
Accepted by the Vanport Township Municipal Authority as meeting an applicable specification stated or cited in its rules and regulations or as suitable for the proposed use. The term "approved" used in reference to a backflow prevention device shall mean a backflow prevention device that meets the requirements of the American Water Works Association's standard C506-69 and the Foundation for Cross-Connection Control and Hydraulic Research of the University of Southern California and is acceptable to the Vanport Township Municipal Authority. Competent testing laboratories other than the Foundation for Cross-Connection Control may be qualified by the Authority to approve backflow preventers.
B. 
That a backflow prevention device or method has been accepted by the Vanport Township Municipal Authority as suitable for the proposed use.
ATMOSPHERIC VACUUM BREAKER (also known as the NON-EXPRESSURE-TYPE VACUUM BREAKER)
A device containing a shutoff valve followed by a valve body containing a float-check, a check seat and an air inlet port. When the shutoff valve is open, the flow of water causes the float to close the air inlet port. When the shutoff valve is closed, the float falls and forms a check valve against back siphonage and at the same time opens the air inlet port.
AUTHORIZED REPRESENTATIVE OF INDUSTRIAL USER
A. 
A principal executive officer of at least the level of vice president if the industrial user is a corporation.
B. 
A general partner or proprietor if the industrial user is a partnership or proprietorship, respectively.
C. 
A duly authorized representative of the individual designated above if such representative is responsible for the overall operation of the facilities from which the indirect discharge originates.
AUXILIARY WATER SYSTEM
Any water source or system on the premises of or available to the customer except connections to other approved community water supply systems.
BACKFLOW
The flow of water or other liquids, mixtures or substances into the potable water distribution system of Vanport Township Municipal Authority from any source or sources other than its intended source. Back siphonage and back pressure are two types of backflow specifically contemplated by these rules and regulations.
BACKFLOW PREVENTION DEVICE
Types, uses, advantages and limitations. There are three types of devices: reduced-pressure principle device (RPPD); double-check valve assembly (DCVA); and air gap (AG) which are designed to prevent the occurrence of backflow.
BACKSIPHONAGE
The backflow of water or mixture of water and other liquids, gases or other substances from a plumbing fixture or other customer source into a public water supply system main due to a temporary negative or subatmospheric pressure within the public water supply system.
COMMUNITY WATER SYSTEM OR DISTRIBUTION SYSTEM
The water distribution system that furnishes water for general use, owned and operated by the Vanport Township Municipal Authority of Beaver County, Pennsylvania, and is recognized by regulatory agencies as a community potable water supply system.
CONSUMER
The owner or person in control of any premises supplied by or in any manner connected to a public water supply system.
CONSUMER'S WATER SYSTEM
Any water system, located on the consumer's premises, supplied by or in any manner connected to a public water supply system. A household plumbing system is considered to be a consumer's water system.
CONTAINMENT
Cross-connection control which isolates the customer's entire facility from the public water supply system so as to provide the protection necessary to prevent contamination of the public water supply in the event of backflow from the customer's facility.
CONTAMINATION
The degradation of the quality of the drinking water by wastewaters, processed fluids or any water of a quality less than accepted drinking water quality to a degree which would create an actual hazard to the public health through poisoning or through the spread of disease.
CROSS-CONNECTION
A physical arrangement whereby a public water supply system is connected with another water system, public or private, in such a manner that a flow of water into such public water supply system from such other water system is possible. Specifically, it is the intent of these regulations to regulate any system containing water or substances, the quality and quantity of which cannot be approved by county, state or federal regulatory agencies.
DEGREE OF HAZARD
An evaluation of the potential risk to health and the adverse effect upon the public water supply system.
DOUBLE-CHECK VALVE ASSEMBLY
An assembly composed of two single, independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable connections for testing the water tightness of each check valve.
HEALTH HAZARD
Any condition, device or practice in a water system or its operation that creates or may create a danger to the health and well being of its users. The word "severe" as used to qualify "health hazard" means a hazard to the health of the user that could reasonably be expected to result in the significant morbidity or death.
INTERCHANGEABLE CONNECTION
An arrangement or device that will allow alternate but not simultaneous use of two sources of water.
INTERCONNECTION
A plumbing arrangement, other than a cross-connection, by which contamination might be admitted to or drawn into the distribution system of the Authority or into lines connected therewith used for the conveyance of potable water. For the purposes of these rules and regulations, when the term "cross-connection" is used for regulatory purposes, it shall be meant to include interconnection in all instances.
MAIN EXTENSIONS
Extensions of distribution pipelines beyond existing facilities and exclusive of service connections.
MAINS
Distribution pipelines which are located in streets, highways, etc., public ways or private rights-of-way and which are used to serve the general public.
METER INSTALLATION
An installation, including one or more meters placed at one or more locations for the purpose of serving one or more premises in a building or a related group of buildings, in a facility or related group of facilities, in an area or a related group of areas, and in such other properties. More than one meter may be provided to allow flexibility of operation, or furnish adequate capacity, or to permit more accurate measurement of water, or due to the physical layout of the property.
NONPOTABLE WATER
Water not safe for drinking, personal or culinary use.
OWNER
The person, whether a natural person, partnership or corporation, in whom is vested ownership, dominion or title, of any premises which is or is about to be supplied with water by the Vanport Township Municipal Authority. Whenever used herein, the singular will include the plural and the plural the singular.
PERSON
Any individual, partnership, association, company, corporation, municipality, municipal authority, political subdivision or any agency of the federal or state governments. The term includes the officers, employees and agents of any partnership, association, company, corporation, municipality, municipal authority, political subdivision or an agency of federal or state government.
POLLUTION
The presence of any foreign substance (organic, inorganic or biological) in water which tends to degrade its qualities so as to constitute a hazard or impair the usefulness or quality of the water to a degree which does not create an actual public health hazard but which does adversely or unreasonably affect such water for domestic use.
POTABLE WATER
Water which is safe for human consumption according to recognized state and federal standards.
PRIVATE FIRE PROTECTION
Provision of water to premises exclusively for fire protection.
PROCESS FLUIDS
Any fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, pollutional or system hazard if introduced into the public or a consumer's water system. This includes, but is not limited to:
A. 
Polluted or contaminated waters.
B. 
Process waters.
C. 
Used waters originating from the public water system which may have deteriorated in sanitary quality.
D. 
Cooling waters.
E. 
Contaminated natural waters taken from wells, lakes, streams or irrigation systems.
F. 
Chemicals in solution or suspension.
G. 
Oils, gases, acids, alkalis and other liquid and gaseous fluids used in industrial or other processes or for fire-fighting purposes.
H. 
Heating system waters from boilers or heat pumps.
PUBLIC WATER SUPPLIER
The Vanport Township Municipal Authority.
PUBLIC WATER SUPPLY SYSTEM
Any part of a water supply utility operated by a municipal corporation, company or individual authorized by written permit issued by the Department of Environmental Protection in accordance with the laws of the Commonwealth of Pennsylvania to supply water and extend distribution facilities to the public.
REDUCED-PRESSURE PRINCIPLE DEVICE
A device that shall incorporate two or more check valves and an automatically operating differential relief valve located between the two check valves and two tightly closing shutoff valves and shall be equipped with necessary appurtenances for testing. The device shall operate to maintain the pressure in the zone between the two check valves, less than the pressure on the Vanport Township Municipal Authority potable water supply side of the device. At cessation of the normal flow, the pressure between the check valves shall be less than the supply pressure. In case of leakage of either check valve, the differential relief shall operate to maintain this reduced pressure by discharging to the atmosphere. When the inlet pressure is two pounds per square inch or less, the relief valve shall open and vent to the atmosphere, thereby providing an air gap in the device. To be approved by the Authority or its designated agents, the device must be readily accessible for maintenance and testing and installed in a location where no part of the device will be subject to outside flooding. The device shall be used on the service connections which may be subject to backflow and where there is a possibility of contamination that constitutes an actual or potential health hazard.
SERVICE CONNECTION
The terminal end of a service line from the public water supply system. If a meter is installed at the end of the service, then the "service connection" means the downstream end of the meter.
SYSTEM HAZARD
A condition posing an actual or potential threat of damage to the physical properties of the public water system or the consumer's potable water system.
A. 
The water system shall be considered as made up of two parts: the public water supply system and the consumer's water system.
B. 
The public water supply system shall consist of the source facilities and the distribution system and shall include all those facilities of the public water supply system under the control of the Vanport Township Municipal Authority up to the point where the consumer's water system begins.
C. 
The source shall include all components of the facilities utilized in the production, treatment, storage and delivery of water to the public distribution system.
D. 
The public distribution system shall include the network of conduits used for delivery of water from the source to the consumer's water system.
E. 
The consumer's water system shall include all facilities beyond the service connection which are utilized in conveying water from the public distribution system to points of use.
A. 
No water service connection shall be installed or maintained to any premises where actual or potential cross-connections to the public water supply system or consumer's water system may exist unless such actual or potential cross-connections are abated or controlled to the satisfaction of the public water supplier.
B. 
No connection shall be installed or maintained whereby water from an auxiliary water supply may enter a public or consumer's water system unless such auxiliary water supply and the method of connection and use of such supply shall have been approved.
A. 
The consumer's premises shall be open at all reasonable times to the Vanport Township Municipal Authority or its authorized representative for the purposes of conducting surveys and investigations of water use practices within the consumer's premises to determine whether there are actual or potential cross-connections to the consumer's water system through which contaminants or pollutants could backflow into the public potable water system.
B. 
On request by the Vanport Township Municipal Authority, the consumer shall furnish information on water use practices within his premises.
C. 
It shall be the responsibility of the water consumer to conduct periodic surveys of water use practices on his premises to determine whether there are actual or potential cross-connections to his water system through which contaminants or pollutants could backflow into the public water supply system.
A. 
An approved backflow prevention device shall be installed prior to the first branch line leading off each service line to a consumer's water system where, in the judgment of the Vanport Township Municipal Authority, an actual or potential hazard to the public water supply system exists.
B. 
An approved backflow prevention device shall be installed on each service line to a consumer's water system where the following conditions exist:
(1) 
Systems having an auxiliary water supply, unless such auxiliary supply is accepted as an additional source by the Vanport Township Municipal Authority and approved by the Department of Environmental Protection.
(2) 
Systems where any substance is handled in such a fashion as to create an actual or potential hazard to the public water supply system. This shall include systems having sources or auxiliary systems containing process fluids or waters originating from the Vanport Township Municipal Authority system which are no longer under the sanitary control of the water purveyor.
(3) 
Systems having internal cross-connections that, in the judgement of the Vanport Township Municipal Authority, are not correctable or intricate plumbing arrangements which make it impractical to determine whether or not cross-connections exist.
(4) 
Systems where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross-connection survey.
(5) 
Systems having a repeated history of cross-connections being established or reestablished.
(6) 
Others specified by the public water supplier.
C. 
An approved backflow prevention device shall be installed on each service line to a consumer's water system serving the following types of facilities unless the public water supplier determines that no actual or potential hazard to the public water supply system exists:
(1) 
Hospitals, mortuaries, clinics, nursing homes.
(2) 
Laboratories.
(3) 
Piers, docks, waterfront facilities.
(4) 
Sewage treatment plants, sewage pumping station or stormwater pumping station.
(5) 
Food or beverage processing plants.
(6) 
Chemical plants.
(7) 
Metal plating industries.
(8) 
Petroleum processing or storage plants.
(9) 
Radioactive material processing plants.
(10) 
Car wash or truck wash.
(11) 
Others specified by the Vanport Township Municipal Authority.
The type of protection required under § 178-6A, B and C of this article shall depend on the degree of hazard which exists as follows:
A. 
An approved air gap separation shall be installed where the public water supply system may be contaminated with substances that are dangerous to the public health and could cause a severe health hazard.
B. 
An approved air gap separation or an approved reduced-pressure zone backflow prevention device shall be installed where the public water-supply system may be contaminated with a substance that could cause a system or health hazard.
C. 
An approved air gap separation or an approved reduced-pressure zone backflow prevention device or an approved double-check valve assembly shall be installed where the public water supply system may be polluted with substances that would be objectionable but not dangerous to health.
A. 
Any backflow prevention device required by this article shall be of a model or construction approved by the public water supplier and shall comply with the following:
(1) 
Air gap separation to be approved shall be at least twice the diameter of the supply pipe, measured vertically above the top rim of the vessel, but in no case less than one inch.
(2) 
Double-check valve assembly; AWWA standards.
(a) 
A double-check valve assembly or a reduced pressure zone backflow prevention device shall be approved by the public water supplier and shall mean a device that has been manufactured in full conformance with standards established by the American Water Works Association (AWWA) entitled, "AWWA C506 Standards for Reduced Pressure Principle and Double Check Valve Backflow Prevention Devices."
(b) 
Said AWWA standards are herein adopted by the Vanport Township Municipal Authority. Final approval, however, of the reduced-pressure principle backflow preventer and the double-check valve assembly shall be evidenced by a certificate of full approval issued by an approved testing laboratory certifying full compliance with said AWWA standards.
(3) 
An interchangeable connection to be approved shall be either a swing-type connector or a four-way valve of the lubricated-plug-type that operates through a mechanism which unseats the plug, turns it 90° and reseats the plug. Four-way valves shall not be used as stop valves but must have separate stop valves on each pipe connected to the valve. The telltale port on the four-way valve shall have no piping connected and the threads or flange on this port shall be destroyed so that a connection cannot be made.
B. 
Existing backflow prevention devices approved by the public water supplier at the time of installation and properly maintained shall, except for inspection and maintenance requirements, be excluded from the requirement of § 178-8A of this article, provided that the Vanport Township Municipal Authority is assured that they will satisfactorily protect the public potable supply system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or when the public water supplier finds that the maintenance of the device constitutes a hazard to health, the device shall be replaced by a backflow prevention device meeting the requirements of this article.
A. 
Backflow prevention devices required by this article shall be installed at a location and in a manner approved by the public water supplier and shall be installed by a person properly qualified and at the expense of the water consumer.
B. 
Backflow prevention devices installed on the service line to a consumer's water system shall be located on the consumer's side of the water meter, as close to the meter as is reasonably practical, and prior to any other connection.
C. 
Pits or vaults shall be of watertight construction, be so located and constructed as to prevent flooding and shall be maintained free from standing water by means of either a sump and pump or a suitable drain. Such sump pump or drain shall not connect to a sanitary sewer nor permit flooding of the pit or vault by reverse flow from its point of discharge. An access ladder and adequate natural or artificial lighting shall be provided to permit maintenance inspection and testing of the backflow prevention device.
A. 
It shall be the duty of the consumer at any premises on which backflow prevention devices required by this article are installed to have inspections, tests and overhaul made in accordance with the following schedule or more often where inspections indicate a need:
(1) 
Air separation shall be inspected at time of installation and at least every 12 months thereafter.
(2) 
Double-check valve assemblies shall be inspected and tested for tightness at the time of installation and at least every 12 months thereafter. They shall be dismantled, inspected internally, cleaned and repaired whenever needed and at least every 30 months.
(3) 
Reduced-pressure zone backflow prevention devices shall be inspected and tested for tightness at the time of installation and at least every 12 months thereafter. They shall be dismantled, inspected internally, cleaned and repaired whenever needed and at least every five years.
(4) 
Interchangeable connections shall be inspected at the time of installation and at least every 12 months thereafter.
B. 
Inspections, tests and overhaul of backflow prevention devices shall be made at the expense of the water consumer and shall be performed by the Vanport Township Municipal Authority or a person qualified to inspect, test and overhaul backflow prevention devices.
C. 
Whenever backflow prevention devices required by this article are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay.
D. 
The water consumer must maintain a complete record of each backflow prevention device from purchase to retirement. This shall include a comprehensive listing that includes a record of all tests, inspections and repairs. Records of inspections, tests, repairs and overhaul shall be submitted to the public water supplier upon request.
E. 
Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without specific authorization by the water supplier.
A. 
Where a booster pump has been installed on the service line to or within any premises, such pump shall be equipped with a low-pressure cutoff device designed to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to 10 pounds per square inch gauge or less for a period of 30 seconds or longer.
B. 
It shall be the duty of the water consumer to maintain the low-pressure cutoff device in proper working order and to certify to the public water supplier, at least once a year, that the device is operating properly.
A. 
The Vanport Township Municipal Authority may deny or discontinue, after reasonable notice to the occupants thereof, the water service to any premises wherein any backflow prevention device required by this article is not installed, tested and maintained in a manner acceptable to the public water supplier, or if it is found that the backflow prevention device has been removed or bypassed, or if an unprotected cross-connection exists on the premises, or if a low-pressure cutoff device required by this article is not installed and maintained in working order.
B. 
Water service to such premises shall not be restored until the consumer has corrected or eliminated such conditions or defects in conformance with this article and to the satisfaction of the public water supplier.