Section 107.2.10 Information for electric vehicle charging stations.
|
Construction documents shall include electric vehicle charging
stations with system installation requirements set forth in Section
107.1 of the International Building Code as amended and adopted by
the City of Vinita Park, and the National Electrical Code as amended
and adopted.
|
Section 406.9.1. Electric vehicle charging stations. Shall be
required, per Tables 406.9.2, 406.9.3, 406.9.4, and 406.9.5. Electric
vehicle charging stations shall be installed and labelled in accordance
with NFPA 70.
|
Electric vehicle charging system equipment shall be listed and
labelled in accordance with UL 2202. Electric vehicle charging system
equipment shall be listed and labelled in accordance with UL 2594.
Accessibility to electric vehicle charging stations shall be provided
in accordance with Chapter 11.
|
Where an EV Ready or EVSE
|
Installed parking space is required, at least one (1) EV Ready
or EV Installed parking space shall be installed adjacent to an ADA
accessible parking space, when an ADA accessible parking space is
also required. Where the calculation of percent served results in
a fractional parking space, it shall be rounded up to the next whole
number if the fraction is .5 (1/2) of a parking space or greater.
This requirement does not apply to buildings without a designated
parking space, nor does this requirement apply to parking spaces located
in the public right-of-way.
|
The following use groups shall require installation of EV Ready
Spaces and Electric Vehicle Supply Equipment (EVSE) in accordance
with Table 406.9.2 through Table 406.9.5:
|
TABLE 406.9.2
NON-RESIDENTIAL USE GROUPS WITH EV READY AND EVSE INSTALLED
REQUIREMENT PER TABLE 406.9.2
| |
---|---|
Use Group
|
Applicability
|
A1
|
All
|
A2
|
Excluding all other uses within A2 including restaurants
|
A3
|
All
|
A4
|
All
|
A5
|
All
|
B
|
All
|
E
|
Excluding daycare uses as defined by Section 305.2
|
M
|
All
|
S2
|
Parking garages, open or enclosed only, excluding all other
uses within S-2
|
TABLE 406.9.3
EV READY AND EVSE INSTALLED SPACE REQUIREMENTS FOR NON-RESIDENTIAL
USE GROUPS
| ||
---|---|---|
Total Number of Parking Spaces
|
Minimum Number of EV Ready Spaces
|
Minimum Numbe
|
10-30 spaces
|
1 space
|
0 spaces
|
31-49 spaces
|
2 spaces
|
1 space
|
50 spaces and greater
|
5% of total parking spaces
|
2% of total parking spaces
|
TABLE 406.9.4
EV READY AND EVSE INSTALLED SPACE REQUIREMENTS FOR RESIDENTIAL
USE GROUPS, JANUARY 1, 2022 THROUGH DECEMBER 31, 2025
| ||
---|---|---|
Total Number of Parking Spaces
|
Minimum Number of EV Ready Spaces
|
Minimum Number of EVSE Installed Spaces
|
5-20 spaces
|
1 space
|
0 spaces
|
21-49 spaces
|
2 spaces
|
1 space
|
50 spaces and greater
|
5% of total parking spaces
|
2% of total parking spaces
|
TABLE 406.9.5
EV READY AND EVSE INSTALLED SPACE REQUIREMENTS FOR RESIDENTIAL
USE GROUPS, JANUARY 1, 2026 AND AFTER
| ||
---|---|---|
Total Number of Parking Spaces
|
Minimum Number of EV Ready Spaces
|
Minimum Number of EVSE Installed Spaces
|
5-20 spaces
|
1 space
|
0 spaces
|
21-49 spaces
|
2 spaces
|
1 space
|
50 spaces and greater
|
10% of total parking spaces
|
2% of total parking spaces
|
[F] 903.3.1.4 Freeze protection. Freeze protection systems for
automatic fire sprinkler systems shall be in accordance with the requirements
of the applicable referenced NFPA standard and this Section.
| |
Attics. Only dry-pipe, *pre-action, or listed antifreeze automatic
fire sprinkler systems shall be allowed to protect attic spaces.
| |
* Pre-action fire sprinkler systems employ the basic
concept of a dry pipe system in that water is not normally contained
within the pipes. The difference, however, is that water is held from
piping by an electrically operated valve, known as a pre-action valve.
Valve operation is controlled by independent flame, heat, or smoke
detection.
| |
Exception: Wet-pipe fire sprinkler systems shall be allowed
to protect non-ventilated attic spaces where:
| |
The attic sprinklers are supplied by a separate floor control
valve assembly to allow ease of draining the attic system without
impairing sprinklers throughout the rest of the building, and
| |
Adequate heat shall be provided for freeze protection as per
the applicable referenced NFPA standard, and
| |
The attic space is a part of the building's thermal, or heat,
envelope, such that insulation is provided at the roof deck, rather
than at the ceiling level.
| |
Heat trace/insulation. Heat trace/insulation shall only be allowed
where approved by the Fire Marshal for small sections of large diameter
water-filled pipe.
|
[F] 909.22 Stairway or ramp pressurization alternative. Where
the building is equipped throughout with an automatic sprinkler system
in accordance with Section 903.3.1.1 and the stair pressurization
alternative is chosen for compliance with Building Code requirements
for a smokeproof enclosure, interior exit stairways or ramps shall
be pressurized to a minimum of ten hundredths (0.10) inches of water
(25 Pa) and a maximum of thirty-five hundredths (0.35) inches of water
(87 Pa) in the shaft relative to the building measured with all interior
exit stairway and ramp doors closed under maximum anticipated conditions
of stack effect and wind effect. Such systems shall comply with Section
909, including the installation of a separate fire-fighter's smoke
control panel as per Section 909.16, and a smoke control permit shall
be required from the Fire District as per Section 105.7.
|
[F] 909.22.1 Ventilating equipment. The activation of ventilating
equipment for the stair or ramp pressurization system shall be by
smoke detectors installed at each floor level at an approved location
at the entrance to the smoke proof enclosure. When the closing device
for the stairway or ramp shaft and vestibule doors is activated by
smoke detection or power failure, mechanical equipment shall activate
and operate at the required performance levels. Smoke detectors shall
be installed in accordance with Section 907.3.
|
[F] 909.22.1.1 Ventilation systems. Smoke proof enclosure ventilation
systems shall be independent of other building ventilation systems.
The equipment, control wiring, power wiring and ductwork shall comply
with one (1) of the following:
|
Equipment, control wiring, power wiring and ductwork shall be
located exterior to the building and directly connected to the smoke
proof enclosure or connected to the smoke proof enclosure by ductwork
enclosed by not less than two-hour fire barriers constructed in accordance
with Section 707 of the Building Code or horizontal assemblies constructed
in accordance with Section 711 of the Building Code, or both.
|
Equipment, control wiring, power wiring and ductwork shall be
located within the smoke proof enclosure with intake or exhaust directly
from and to the outside or through ductwork enclosed by not less than
two-hour barriers constructed in accordance with Section 707 of the
Building Code or horizontal assemblies constructed in accordance with
Section 711 of the Building Code, or both.
|
Equipment, control wiring, power wiring and ductwork shall be
located within the building if separated from the remainder of the
building, including other mechanical equipment, by not less than two-hour
fire barriers constructed in accordance with Section 707 of the Building
Code or horizontal assemblies constructed in accordance with Section
711 of the Building Code, or both.
|
Exceptions:
|
Control wiring and power wiring utilizing a two-hour rated cable
or cable system.
|
Where encased with not less than two (2) inches (51 mm) of concrete.
|
Control wiring and power wiring protected by a listed electrical
circuit protective system with a fire-resistance rating of not less
than two (2) hours
|
[F] 909.22.1.2 Standby power. Mechanical vestibule and stairway
and ramp shaft ventilation systems and automatic fire detection systems
shall be provided with standby power in accordance with Section 2702
of the Building Code.
|
[F] 909.22.1.3 Acceptance and testing. Before the mechanical
equipment is approved, the system shall be tested in the presence
of the Fire Marshal to confirm that the system is operating in compliance
with these requirements.
|
910.2.3; Group H. Buildings and portions thereof used as a Group
H Occupancy as follows:
|
In occupancies classified as Group H-2 or H-3, any of which
are more than fifteen thousand (15,000) square feet (1,394 m2) in single floor area.
|
Exception: Buildings of non-combustible construction containing
only non-combustible materials.
|
In areas of buildings in Group H used for storing Class 2, 3
and 4 liquid and solid oxidizers, Class 1 and unclassified detonable
organic peroxides, Class 3 and 4 unstable (reactive) materials, or
Class 2 or 3 water-reactive materials as required for a high-hazard
commodity classification.
|
Exception: Buildings of non-combustible construction containing
only non-combustible materials.
|
[F] 910.3.4 Vent operation. Smoke and heat vents shall be capable
of being operated by approved automatic and manual means. Automatic
operation of smoke and heat vents shall conform to the provisions
of Sections 910.3.2.1 through 910.3.2.3.
|
[F] 910.3.4.1 Sprinkled buildings. Where installed in buildings
equipped with an approved automatic sprinkler system, smoke and heat
vents shall be designed to operate automatically. The automatic operating
mechanism of the smoke and heat vents shall operate at a temperature
rating at least one hundred degrees Fahrenheit (100° F.) (approximately
38° C.) greater than the temperature rating of the sprinklers
installed.
|
Exception: Manual only system per 910.2.
|
[F] 910.3.4.2 Non-sprinkled buildings. Where installed in buildings
not equipped with an approved automatic sprinkler system, smoke and
heat vents shall operate automatically by actuation of a heat-responsive
device rated at between one hundred degrees Fahrenheit (100° F.)
(56° C.) and two hundred degrees Fahrenheit (220° F.) (122°
C.) above ambient.
|
Exception: Listed gravity-operated drop out vents.
|
1804.4.1 Drainage requirements. Any person, firm, or corporation
who builds or causes to be built any residential dwelling or residential
accessory structure shall be responsible for the execution of the
following site grading requirements and drainage provisions:
|
The slope of the final grading of soils at the side yard of
any residential dwelling or residential accessory structure shall
not exceed a gradient of five percent (5%) when measured from grade
at the side property line to a point of intersection with the elevation
of grade at the foundation wall of the structure.
|
Diversion of surface water shall be contained within the limits
of a residential lot and shall be conveyed by a free, positive, and
uninterrupted means to a point of discharge at the front property
line and/or property line adjacent to an alley. Roof drainage shall
be accomplished by use of a roof guttering system connected to a properly
sized subsurface drainage conduit discharging through the curb at
the street or at the property line adjacent to an alley.
|
If irregular site topography, use of landscaping, or architectural
features such as raised planting beds, retaining walls, fences, or
sidewalks prohibit compliance with provisions of this Section, the
designer shall provide alternate methods and means as may be approved
by the Building Commissioner to assure that the requirements of this
code are met. The drainage plan must be submitted, reviewed, and approved
prior to issuance of a building permit and the work must be approved
prior to final inspection and occupancy of the structure.
|
A drainage system capable of removing excess surface water,
subsurface water, and/or excess moisture shall be provided under all
pier and beam foundations exceeding five hundred (500) square feet
in area and all basements or below grade construction. The subsurface
water drainage system shall be of a type and design as provided by
the owner's registered professional engineer. The designer of the
pier and beam foundation system shall include the subsurface drainage
system design by reference in plan notes or details on the foundation
plan. All subsurface water drainage systems shall be designed and
installed on private property in such a manner as to prohibit backflow
from surface water by means of grading, check valve, air gap, or other
device as may be approved by the Building Commissioner. The drainage
system design for a basement or below grade construction shall be
such that surface water, subsurface water, and/or moisture is not
diverted onto public property or adjacent properties, provided, however,
such water may be drained through enclosed pipe into the MSD storm
water drainage system.
|
Exception: Pier and beam foundation systems and basement or
below grade construction designed and sealed by a registered professional
engineer with a design expertise in structural foundation systems
may incorporate a design for a foundation drainage system as deemed
appropriate.
|
All site drainage requirements shall be installed and approved
prior to final approval of the structure and occupancy thereof. The
Building Commissioner shall inspect and approve all drainage plans,
structures, and work required by this Section.
|
Maximum impermeable surface. It shall be required as a condition
for granting a permit to build, repair, remodel, enlarge or replace
a structure or install additional features such as swimming pools,
drives, patios, etc., which increase impermeable surface, that the
following standards be met and complied with. Impermeable areas of
all lots shall be limited to those specified for the following lot
categories:
|
Lot Category/S.F. of Lot
|
Allowed Impermeable Surface
|
---|---|
Multi-family
|
63%
|
Non-residential lots
|
90%
|
**
|
Exception: Permeable pavers and permeable concrete may be used
provided they are:
|
Installed per manufacturer's requirements.
| |
Materials proposed, manufacturers installation requirements
and proposed location are provided with submitted plans City Inspection
required for manufacturer's subsurface requirements.
|
Exceptions:
|
Elevators wholly located within atriums complying with Section
404 shall not require hoistway enclosure protection.
|
Elevators in open or enclosed parking garages that serve only
the parking garage, and complying with Sections 406.5 and 406.6, respectively,
shall not require hoistway enclosure protection.
|
Section R115 Building site requirements.
|
R115.1 General. All building sites shall be maintained in such
a manner as to be kept free of construction debris, garbage, trash,
or any unsanitary condition.
|
R115.2 Toilet facilities. During construction, all projects
covered by a building permit shall have sanitation facilities located
either in a building or in the rear yard. Portable toilets shall not
be located in any required front or side yard
|
R115.3 Sanitation. All garbage and trash, as those terms are
defined in Section 11.101 of the Code of Ordinances, shall be deposited
in an approved container or containers on each residential construction
site on a daily basis. Such containers shall meet the requirements
of Section 11.101 of the Code of Ordinances and shall be placed for
collection on the construction site.
|
R115.4 Construction debris. During new residential construction
or major residential remodeling, the Building Commissioner may require
that a commercial dumpster or trash container be provided for construction
debris, due to the size of the job or area of the lot. Such dumpster
or container shall not be used to discard garbage or trash as defined
in Section 11.101 of the Code of Ordinances, but only debris generated
as a result of the construction materials used for the project. The
dumpster or container must be emptied regularly. The dumpster or container
may not be placed on public right-of-way at any time, including "staging"
to replace a full container with an empty one (1), which staging shall
be performed on private property, provided, however, the Public Works
Director may, upon written application by the builder, grant an exception
for a period not to exceed thirty (30) minutes where the size, topography,
or existing trees, of a lot prevent staging thereon, and provided
the builder agrees in writing to be responsible for any damage caused
to public property during such staging.
|
R115.5 Construction fence. A fence is required around all-residential
new construction sites and major residential remodeling or alteration
projects. If, in the opinion of the Building Commissioner, the proposed
remodeling or alteration would not adversely impact adjoining properties
due to construction debris, traffic, or other associated conditions,
the Building Commissioner may waive the requirement of the construction
fence or any portion thereof. The minimum height for a construction
fence shall be six (6) feet and openings therein shall not exceed
six (6) square inches. Gates, when open, shall not obstruct public
sidewalks or alleys and shall be locked when daily activities are
shut down. On any construction site where, in the opinion of the Building
Commissioner, a solid fence would ensure the safety of the public,
a solid fence shall be required. Where the complete demolition of
a residence is taking place, the Building Commissioner may require
a construction fence around the property in order to ensure public
safety.
|
R115.6 Site grading. After demolition or during construction,
residential sites shall be graded such that surface water shall be
contained within the limits of the lot in which the construction is
taking place, and shall be conveyed by a free, uninterrupted means
to a point of discharge at the front property line and/or property
line adjacent to an alley. In order to prevent the runoff of water,
mud, or soil onto an adjacent property, public street, alley, or sidewalk,
the Building Commissioner may require various methods, such as silt
fencing, regrading, or other erosion protection procedures, to be
implemented to prevent such runoff.
|
R115.7 Demolition. Prior to demolition or salvage of any structure
Item's 1 thru 3 below must be achieved. Salvage on sites is not allowed
until demolition permit has been issued. The Building Commissioner
may require the permittee to submit plans and a complete schedule
for demolition, rat elimination, pedestrian protection structures,
and dust control measures. Where such plans and schedules are required,
no work shall be done until they are approved by the Building Commissioner
and the following methods and procedures are in place:
|
For the purpose of eliminating or controlling rats in a building
scheduled for demolition, the owner or demolition contractor shall
be required to submit a plan to exterminate, bait, trap, poison or
fumigate for rats prior to demolition. Such methods may include "rodent
stations" around the property. If traps are used, they shall be kept
set and freshly baited at frequent intervals and maintained in good
working order and shall be inspected daily for a minimum of seven
(7) days immediately prior to the beginning of demolition. If the
plan includes poisoning or fumigating, it must be conducted in a manner
approved by the Health Department or any other authorized agency of
the City, State, or United States. To the extent required by State
law, all such methods shall be carried out by licensed pest control
operators.
|
The work of demolishing any building shall not be commenced
until the required dust control procedures are in place. The Building
Commissioner may require the applicant to submit plans and a complete
schedule for demolition and dust control measures. Where such measures
are required, no work shall be done until such plans or schedule,
or both, are approved by the Building Commissioner. All precautions
shall be taken to prevent dust from becoming airborne at and near
the demolition site. The applicant shall provide for the adequate
use of water for dust suppression on the demolition site so as to
prevent a public nuisance, health hazard or safety hazard.
|
On any demolition site a construction fence shall be required.
The minimum height for a construction fence shall be six (6) feet
and openings therein shall not exceed six (6) square inches. Gates,
when open, shall not obstruct public sidewalks or alleys and shall
be locked when daily activities are shut down. Fences are to be removed
upon demolition final.
|
R115.9 Removal of Structures. Where demolition or removal of
any primary structure is done, the lot shall be completely cleaned
of all structures and appurtenances and also be properly graded so
as to ensure proper drainage of the entire lot including proper leveling.
Erosion control must be established. Any exception to this requirement
shall be determined by the Building Commissioner.
|
R115.10 Jobsite dust and material containment. To prevent dust
from being airborne, a wet saw shall be used when cutting masonry,
brick, stone, or concrete. Measures must be taken to contain blowing
trash or building material.
|
Ground Snow Load
|
Wind Design
|
Seismic Design Categoryf
| |
---|---|---|---|
Speedd
(mph)
|
Topographic Effectsk
| ||
5 lb/ft2
|
115 (3-sec-gust)/76 fastest mile
|
No
|
A
|
Subject to Damage From:
| |||
Weatheringa
|
Frost line depthb -
|
Termitec -
| |
moderate
|
6"
|
very heavy
|
Winter Design Tempe
|
Ice Barrier Underlayment - Requiredh
|
Flood Hazardsg
|
Air Freezing Indexi
|
Mean Annual Tempj
|
---|---|---|---|---|
22° F.
|
No
|
local code
|
150
|
64.9° F
|
{No change to footnotes}
|
Exceptions:
| |
5. Townhouses separated by a common two-hour fire-resistance-rated
wall, or one-hour fire-resistant-rated wall when equipped with an
automatic sprinkler system, {remainder unchanged}.
|
Exceptions:
| |
1.
|
{existing language unchanged.}
|
2.
|
{existing language unchanged.}
|
3.
|
Two-family dwelling units that are also divided by a property
line through the structure shall be separated as required for townhouses.
|
Exception: The glazed areas shall not be required where artificial
light and a mechanical ventilation system, complying with one (1)
of the following, are provided.
|
The minimum ventilation rates shall be fifty (50) cfm (24 L/s)
for intermittent ventilation or twenty (20) cfm (10 L/s) for continuous
ventilation. Ventilation air from the space shall be exhausted directly
to the outside.
|
Bathrooms that contain only a water closet, a lavatory, or water
closet and a lavatory may be ventilated with an approved mechanical
recirculating fan or similar device designed to remove odors from
the air.
|
R324 Fire sprinklers. An approved automatic fire sprinkler system
shall be installed in all new one- and two-family dwellings and townhouses
in accordance with Section 903.3.1.3 of the International Fire Code.
|
R324.1. Existing Buildings. The owner of any one- and two-family
dwelling or townhouse shall be required to install an automatic sprinkler
system to protect the existing building and new additions at such
time as the owner(s) constructs an addition or enlargement to the
building if the total square footage of such an addition, when combined
with the total square footage of all previous additions and enlargements
to the building after August 1, 2008:
|
Causes the building to exceed four thousand square feet (4,000)
(371.6 m2) of total floor area; and
|
The total square footage of all such additions exceeds the *existing
under roof floor area of the building by more than thirty percent
(30%), regardless of fire area, area separation walls, or fire walls.
|
Foundations for one- and two-family dwellings shall be designed
to meet one (1) of the following criteria:
|
Concrete pier and beam foundation, designed by a registered
Missouri engineer; or
|
Slab foundation supported by piers, designed in accordance with
WRI/CRSI Design of Slab-on-Ground Foundations, and sealed by a registered
Missouri engineer; or
|
Post-tensioned foundation, designed in accordance with PTI Design
and Construction of Post-Tensioned Slab-on-Ground Foundations, and
sealed by a registered Missouri engineer; or
|
Exception: Piers shall not be required for detached accessory
structures unless existing soil conditions are determined to mandate
such design.
|
The height of the exterior grade beam, on either a slab or a
pier and beam foundation, shall be no higher than the average of the
heights of the grade beams of the residences located on the adjacent
properties. In cases where the average height will not allow for positive
drainage of the subject site because of existing topography, the Building
Commissioner may allow up to twelve (12) inches to be added to the
height of the exterior grade beam so as to achieve positive drainage,
consistent with the requirements set out under Subsection R401.3.1
below.
|
In cases where the addition to the height of the exterior grade
beam, as described in four (4) above, will not provide for positive
drainage of the subject site because of existing topography, the developer
shall submit a drainage plan, prepared and sealed by a Missouri registered
professional engineer, which will establish the grading, drainage,
grade beam height and minimum finished floor elevations in compliance
with Section R401.3.1.
|
The exposed height of the exterior grade beam shall not exceed
twelve (12) inches.
|
R401.3.1 Drainage requirements. Any person, firm, or corporation
who builds or causes to be built any residential dwelling or residential
accessory structure shall be responsible for the execution of the
following site grading requirements and drainage provisions:
|
The slope of the final grading of soils at the side yard of
any residential dwelling or residential accessory structure shall
not exceed a gradient of five percent (5%) when measured from grade
at the side property line to a point of intersection with the elevation
of grade at the foundation wall of the structure.
|
Diversion of surface water shall be contained within the limits
of a residential lot and shall be conveyed by a free, positive, and
uninterrupted means to a point of discharge at the front property
line and/or property line adjacent to an alley. Roof drainage shall
be accomplished by use of a roof guttering system connected to a properly
sized subsurface drainage conduit discharging through the curb at
the street or at the property line adjacent to an alley.
|
If irregular site topography, use of landscaping, or architectural
features such as raised planting beds, retaining walls, fences, or
sidewalks prohibit compliance with provisions of this Section, the
designer shall provide alternate methods and means as may be approved
by the Building Commissioner to assure that the requirements of this
code are met. The drainage plan must be submitted, reviewed, and approved
prior to issuance of a building permit and the work must be approved
prior to final inspection and occupancy of the structure.
|
A drainage system capable of removing excess surface water,
subsurface water, and/or excess moisture shall be provided under all
pier and beam foundations exceeding five hundred (500) square feet
in area and all basements or below grade construction. The subsurface
water drainage system shall be of a type and design as provided by
the owner's registered professional engineer. The design of the pier
and beam foundation system shall include the subsurface drainage system
design by reference in plan notes or details on the foundation plan.
All subsurface water drainage systems shall be designed and installed
on private property in such a manner as to prohibit back flow from
surface water by means of grading, check valve, air gap, or other
device as may be approved by the Building Commissioner. The drainage
system design for a basement or below grade construction shall be
such that surface water, subsurface water, and/or moisture is not
diverted onto public property or adjacent properties, provided however,
such water may be drained through enclosed pipe into the MSD storm
water drainage system.
|
Exception: Pier and beam foundation systems and basement or
below grade construction designed and sealed by a registered professional
engineer with design expertise in structural foundation systems may
incorporate a design for a foundation drainage system as deemed appropriate.
|
All site drainage requirements shall be installed and approved
prior to final approval of the structure and occupancy thereof. The
Building Commissioner shall inspect and approve all drainage plans,
structures, and work required by this Section.
|
Lot Category/S.F. of Lot
|
Allowed Impermeable Surface
| |
---|---|---|
Single-family
| ||
0 — 6,000 square feet
|
3,600 square feet
| |
6,001 — 7,500 square feet
|
60%
| |
7,501 — 10,000 square feet
|
52% or 4,500 square feet, whichever is greater
| |
10,001 — 12,000 square feet
|
48% or 5,200 square feet, whichever is greater
| |
12,001 — 35,000 square feet
|
40% or 5,760 square feet, whichever is greater
| |
35,001 square feet and greater
|
35% or 14,000 square feet, whichever is greater
| |
Single-family attached and two-family
|
63%
|
**
|
Exception: Permeable pavers and permeable concrete may be used
provided they are:
|
Installed per manufacturer's instructions materials proposed,
manufacturers installation requirements and proposed location are
provided with submitted plans City inspection required for manufacturer's
subsurface requirements.
|
In stud framed exterior walls, all ties shall be anchored to
studs as follows:
|
When studs are sixteen (16) inches (407 mm) o.c., stud ties
shall be spaced no further apart than twenty-four (24) inches (737
mm) vertically starting approximately twelve (12) inches (381 mm)
from the foundation; or
|
When studs are twenty-four (24) inches (610 mm) o.c., stud ties
shall be spaced no further apart than sixteen (16) inches (483 mm)
vertically starting approximately eight (8) inches (254 mm) from the
foundation.
|
M1305.1.3 Appliances in attics. Attics containing appliances
requiring access shall be provided . . . {bulk of paragraph unchanged}
. . . sides of the appliance where access is required. The clear access
opening dimensions shall be a minimum of twenty (20) inches by thirty
(30) inches (508 mm by 762 mm), or larger where such dimensions are
not large enough to allow removal of the largest appliance. As a minimum,
access to the attic space shall be provided by one (1) of the following:
|
A permanent stair.
|
A pull-down stair.
|
An access door from an upper floor level.
|
Access panel may be used in lieu of Items 1, 2, and 3 if appliance
is serviceable from access opening and opening is large enough to
remove the largest piece of equipment
|
Exceptions:
|
The passageway and level service space are not required where
the appliance is capable of being serviced and removed through the
required opening.
|
Where the passageway is unobstructed . . .[remainder unchanged].
|
M1411.3 Condensate disposal. Condensate from all cooling coils
or evaporators shall be conveyed from the drain pan outlet to a sanitary
sewer through a trap, by means of a direct or indirect drain. {Remainder
unchanged.}
|
M1503.4 Makeup air required. Exhaust hood systems capable of
exhausting in excess of four hundred (400) cubic feet per minute (0.19
m3/s) shall be provided with makeup air at a rate approximately equal
to the difference between the exhaust air rate and four hundred (400)
cubic feet per minute. Such makeup air systems shall be equipped with
a means of closure and shall be automatically controlled to start
and operate simultaneously with the exhaust system.
|
Exception: Where all appliances in the house are of sealed combustion,
power-vent, unvented, or electric, the exhaust hood system shall be
permitted to exhaust up to six hundred (600) cubic feet per minute
(0.28 m3/s) without providing makeup air.
|
Exhaust hood systems capable of exhausting in excess of six
hundred (600) cubic feet per minute (0.28 m3/s) shall be provided
with a makeup air at a rate approximately equal to the difference
between the exhaust air rate and six hundred (600) cubic feet per
minute.
|
Section P2804.6.1 Requirements for discharge piping. The discharge
piping serving a pressure relief valve, temperature relief valve or
combination thereof shall:
|
Not be directly connected to the drainage system.
|
Discharge through an air gap located in the same room as the
water heater.
|
Not be smaller than the diameter of the outlet of the valve
served and shall discharge full size to the air gap.
|
Serve a single relief device and shall not connect to piping
serving any other relief device or equipment.
|
Exception: Multiple relief devices may be installed to a single
T & P discharge piping system when approved by the administrative
authority and permitted by the manufactures installation instructions
and installed with those instructions.
|
Discharge to the floor, to an indirect waste receptor or to
the outdoors.
|
[remainder unchanged.]
|
Cross-linked polyethylene (PEX) plastic tubing;
|
Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe;
|
Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-PEX) pipe;
|
Polybutylene (PB) plastic pipe and tubing;
|
Polyethylene (PE) plastic pipe and tubing;
|
Polypropylene (PP) plastic pipe and tubing. Section P3001.4
is changed to read as follows:
|
P3001.4. Protection of sanitary sewer systems
|
All roofs, paved areas, yards, courts, courtyards, subsurface
drainage, sump pumps, or similar areas having rain water drainage
shall discharge to the outside of the building, or directly to the
storm sewer system where required.
|
P3003.9. Solvent cementing. Joint surfaces shall be clean and
free from moisture. A purple primer that conforms to ASTM F 656 shall
be applied. Solvent cement not purple in color and conforming to ASTM
D 2564, CSAB137.3, CSA B181.2 or CSA B182.1 shall be applied to all
joint surfaces. The joint shall be made while the cement is wet and
shall be in accordance with ASTM D 2855. Solvent cement joints shall
be permitted above or below ground.
|
Exception: A primer is not required where both of the following
conditions apply:
|
The solvent cement is used only for joining PVC drain, waste,
and vent pipe and fittings not in pressure applications in sizes up
to and including four (4) inches (102 mm) in diameter.
|
Appendix Q. Swimming Pools, Spas and Hot Tubs. Section AQ101.2.1
or AQ101.2.2.
|
AQ101.1 General. The provisions of this appendix shall control
the design and construction of swimming pools, spas and hot tubs installed
in or on the lot of a one- or two-family dwelling.
|
AQ101.2 Pools in flood hazard areas. Pools that are located
in flood hazard areas established by Table R301.2(1), including above-ground
pools, on-ground pools and in-ground pools that involve placement
of fill, shall comply with
|
Exception: Pools located in riverine flood hazard areas which
are outside of designated floodways.
|
AQ101.2.1 Pools located in designated floodways.
|
Where pools are located in designated floodways, documentation
shall be submitted to the Building Commissioner which demonstrates
that the construction of the pool will not increase the design flood
elevation at any point within the jurisdiction.
|
AQ101.2.2 Pools located where floodways have not been designated.
Where pools are located where design flood elevations are specified
but floodways have not been designated, the applicant shall provide
a floodway analysis that demonstrates that the proposed pool will
not increase the design flood elevation more than one (1) foot (305
mm) at any point within the jurisdiction.
|
Section AQ102 Definitions AQ102.1 General.
|
For the purposes of these requirements, the terms used shall
be defined as follows and as set forth in Chapter 2.
|
ABOVE-GROUND/ON-GROUND POOL. See "Swimming pool."
|
BARRIER. A fence, wall, building wall or combination thereof
which completely surrounds the swimming pool and obstructs access
to the swimming pool.
|
HOT TUB. See "Swimming pool."
|
IN-GROUND POOL. See "Swimming pool."
|
RESIDENTIAL. That which is situated on the premises of a detached
one- or two-family dwelling, or a one-family townhouse not more than
three (3) stories in height.
|
SPA, NON-PORTABLE. See "Swimming pool."
|
SPA, PORTABLE. A non-permanent structure intended for recreational
bathing, in which all controls, water-heating and water-circulating
equipment are an integral part of the product.
|
SWIMMING POOL. Any structure intended for swimming or recreational
bathing that contains water more than twenty-four (24) inches (610
mm) deep. This includes in-ground, above-ground and on-ground swimming
pools, hot tubs and spas.
|
SWIMMING POOL, INDOOR. A swimming pool which is totally contained
within a structure and surrounded on all four (4) sides by the walls
of the enclosing structure.
|
SWIMMING POOL, OUTDOOR. Any swimming pool which is not an indoor
pool.
|
SECTION AG103 SWIMMING POOLS
|
AQ103.1 In-ground pools.
|
In-ground pools shall be designed and constructed in compliance
with ANSI/NSPI-5.
|
AQ103.2 Above-ground and on-ground pools.
|
Above-ground and on-ground pools shall be designed and constructed
in compliance with ANSI/NSPI-4.
|
AQ103.3 Pools in flood hazard areas.
|
In flood hazard areas established by Table R301.2(1), pools
in coastal high-hazard areas shall be designed and constructed in
compliance with ASCE 24.
|
Section AQ104 Spas And Hot Tubs.
|
AQ104.1 permanently installed spas and hot tubs. Permanently
installed spas and hot tubs shall be designed and constructed in compliance
with ANSI/NSPI-3.
|
AQ104.2 Portable spas and hot tubs.
|
Portable spas and hot tubs shall be designed and constructed
in compliance with ANSI/NSPI-6.
|
Section AQ105 Barrier Requirements.
|
AQ105.1 Application. The provisions of this appendix shall control
the design of barriers for residential swimming pools, spas and hot
tubs. These design controls are intended to provide protection against
potential drownings and near-drownings by restricting access to swimming
pools, spas and hot tubs.
|
AQ105.2 Outdoor swimming pool. An outdoor swimming pool, including
an in-ground, above-ground or on-ground pool, hot tub or spa shall
be surrounded by a barrier which shall comply with the following:
|
The top of the barrier shall be at least forty-eight (48) inches
(1,219 mm) above grade measured on the side of the barrier, which
faces away from the swimming pool. The maximum vertical clearance
between grade and the bottom of the barrier shall be two (2) inches
(51 mm) measured on the side of the barrier, which faces away from
the swimming pool. Where the top of the pool structure is above grade,
such as an above-ground pool, the barrier may be at ground level,
such as the pool structure, or mounted on top of the pool structure.
Where the barrier is mounted on top of the pool structure, the maximum
vertical clearance between the top of the pool structure and the bottom
of the barrier shall be four (4) inches (102 mm).
|
Openings in the barrier shall not allow passage of a four (4)
inch diameter (102 mm) sphere.
|
Solid barriers which do not have openings, such as a masonry
or stone wall, shall not contain indentations or protrusions except
for normal construction tolerances and tooled masonry joints.
|
Where the barrier is composed of horizontal and vertical members
and the distance between the tops of the horizontal members is less
than forty-five (45) inches (1,143 mm), the horizontal members shall
be located on the swimming pool side of the fence. Spacing between
vertical members shall not exceed one and seventy-five hundredths
(1.75) inches (44 mm) in width. Where there are decorative cutouts
within vertical members, spacing within the cutouts. Where the barrier
is composed of horizontal and vertical members and the distance between
the tops of the horizontal members is forty-five (45) inches (1,143
mm) or more, spacing between vertical members shall not exceed four
(4) inches (102 mm). Where there are decorative cutouts within vertical
members, spacing within the cutouts shall not exceed one and seventy-five
hundredths (1.75) inches (44 mm) in width.
|
Maximum mesh size for chain link fences shall be a two and twenty-five
hundredths (2.25) inch (57 mm) square unless the fence is provided
with slats fastened at the top or the bottom which reduce the openings
to not more than one and seventy-five hundredths (1.75) inches (44
mm).
|
Where the barrier is composed of diagonal members, such as a
lattice fence, the maximum opening formed by the diagonal members
shall not be more than one and seventy-five hundredths (1.75) inches
(44 mm).
|
Access gates shall comply with the requirements of Section AQ105.2,
Items 1 through 7, and shall be equipped to accommodate a locking
device. Pedestrian access gates shall open outward away from the pool
and shall be self-closing and have a self-latching device. Gates other
than pedestrian access gates shall have a self-latching device. Where
the release mechanism of the self-latching device is located less
than fifty-four (54) inches (1,372 mm) from the bottom of the gate,
the release mechanism and openings shall comply with the following:
|
The release mechanism shall be located on the pool side of the
gate at least three (3) inches (76 mm) below the top of the gate,
and the gate and barrier shall have no opening greater than five-tenths
(0.5) inch (13 mm) within eighteen (18) inches (457 mm) of the release
mechanism.
|
Where a wall of a dwelling serves a part of the barrier one
(1) of the following conditions shall be met:
|
The pool shall be equipped with a powered safety cover in compliance
with ASTM F1346; or doors with direct access to the pool through that
wall shall be equipped with an alarm which produces an audible warning
when the door and/or its screen, if present, are opened. The alarm
shall be other means of protection, such as self-closing doors with
self-latching devices, which are approved by the governing body, shall
be acceptable as long as the degree of protection afforded is not
less than the protection afforded by Item 9.1 or 9.2 described above.
|
Where an above-ground pool structure is used as a barrier or
where the barrier is mounted on top of the pool structure, and the
means of access is a ladder or steps, then:
|
The ladder or steps shall be capable of being secured, locked
or removed to prevent access, or the ladder or steps shall be surrounded
by a barrier which meets the requirements of Section AQ105.2, Items
1 through 9. When the ladder or steps are secured, locked or removed,
any opening created shall not allow the passage of a four (4) inch
diameter (102 mm) sphere.
|
AQ105.3 Indoor swimming pool. Walls surrounding an indoor swimming
pool shall comply with Section AQ105.2, Item 9.
|
AQ105.4 Prohibited locations. Barriers shall be located so as
to prohibit permanent structures, equipment or similar objects from
being used to climb them.
|
AQ105.5 Barrier exceptions. Spas or hot tubs with a safety cover
which complies with ASTM F 1346, as listed in Section AQ107, shall
be exempt from the provisions of this appendix
|
Section AQ106 Entrapment Protection For Swimming Pool And Spa.
|
Section 106.1 General. Suction outlets shall be designed and
installed in accordance with ANSI/APSP-7.
|
Section AQ107 Abbreviations
|
AQ107.1 General.
|
ANSI — American National Standards Institute 11 West 42nd
Street, New York, NY 10036
|
APSP — Association of Pool and Spa Professionals NSPI
— National Spa and Pool Institute 2111 Eisenhower Avenue, Alexandria,
VA 22314
|
ASCE — American Society of Civil Engineers 1801 Alexander
Bell Drive, Reston, VA 98411-0700
|
ASTM — ASTM International 100 Barr Harbor Drive, West
Conshohocken, PA 19428
|
UL — Underwriters Laboratories, Inc. 333 Pfingsten Road,
Northbrook, IL 60062-2096
|
Table R402.3.2
| ||
---|---|---|
SHGC Multipliers for Permanent Projections a Projection Factor
|
SHGC Multiplier
(all Other Orientation)
|
SHGC Multiplier
(North Oriented)
|
>0 — 0.10
|
1.00
|
1.00
|
>0.10 — 0.20
|
0.91
|
0.95
|
>0.20 — 0.30
|
0.82
|
0.91
|
>0.30 — 0.40
|
0.74
|
0.87
|
>0.40 — 0.50
|
0.67
|
0.84
|
>0.50 — 0.60
|
0.61
|
0.81
|
>0.70 — 0.80
|
0.56
|
0.78
|
>0.80 — 0.90
|
0.51
|
0.76
|
>0.90 — 1.00
|
0.47
|
0.75
|
0.44
|
0.73
| |
a. North oriented means within forty-five degrees (45°)
of true north.
|
Table R406.4(1) Maximum Energy Rating Index
| |
---|---|
Climate Zone
|
Energy Rating Index
|
3
|
65
|
This table is effective until August 31, 2019.
|
Table R406.4 (2) Maximum Energy Rating Index
| |
---|---|
Climate Zone
|
Energy Rating Index
|
3
|
63
|
The table is effective from September 1, 2019 to August 31,
2022.
|
Table R406.4 (3) Maximum Energy Rating Index
| |
---|---|
Climate Zone
|
Energy Rating Index
|
3
|
59
|
This table is effective on or after September 1, 2022.
|
306.3 Appliances in attics. Attics containing appliances requiring
access shall be provided . . . (bulk of paragraph unchanged). . .
side of the appliance. The clear access opening dimensions shall be
a minimum of twenty (20) inches by thirty (30) inches (508 mm by 762
mm), or larger where such dimensions are not large enough to allow
removal of the largest appliance. As a minimum, for access to the
attic space, provide one (1) of the following:
|
A permanent stair.
|
A pull-down stair.
|
An access door from an upper floor level.
|
Access panel may be used in lieu of Items 1, 2, and 3 if the
appliance is capable of being serviced from the access panel and opening
is large enough to remove the largest piece of equipment
|
Exceptions:
|
The passageway and level service space are not required where
the appliance is capable of being serviced and removed. . . (remainder
of Section unchanged).
|
501.3 Exhaust discharge. The air removed by every mechanical
exhaust system shall be discharged outdoors at a point where it will
not cause a nuisance and not less than the distances specified in
Section 501.3.1. The air shall be discharged to a location from which
it cannot again be readily drawn in by a ventilating system. Air shall
not be exhausted into an attic or crawl space.
|
Exceptions:
|
Whole-house ventilation-type attic fans shall be permitted to
discharge into the attic space of dwelling units having private attics.
|
Commercial cooking re-circulating systems.
|
Where installed in accordance with the manufacturer's instructions
and where mechanical or natural ventilation is otherwise provided
in accordance with Chapter 4, listed and labeled domestic ductless
range hoods shall not be required to discharge to the outdoors.
|
Toilet room exhaust ducts may terminate in a warehouse or shop
area when infiltration of outside air is present.
|
Section 714 Engineered Drainage Design
|
67
|
403.1 Minimum number of fixtures. Plumbing fixtures shall be
provided for the type of occupancy and in the minimum number as follows:
|
Assembly Occupancies: At least one (1) drinking fountain shall
be provided at each floor level in an approved location.
|
Exception: A drinking fountain need not be provided in a drinking
or dining establishment.
|
Groups A, B, F, H, I, M and S Occupancies: Buildings or portions
thereof where persons are employed shall be provided with at least
one (1) water closet for each sex except as provided for in Section
403.2.
|
Group E Occupancies: Shall be provided with fixtures as shown
in Table 403.1.
|
Group R Occupancies: Shall be provided with fixtures as shown
in Table 403.1.
|
It is recommended, but not required, that the minimum number
of fixtures provided also comply with the number shown in Table 403.1.
Types of occupancies not shown in Table 403.1 shall be considered
individually by the Building Commissioner. The number of occupants
shall be determined by the International Building Code. Occupancy
classification shall be determined in accordance with the International
Building Code.
|
504.6 Requirements for discharge piping. The discharge piping
serving a pressure relief valve, temperature relief valve or combination
thereof shall:
|
Not be directly connected to the drainage system. Discharge
through an air gap.
|
Not be smaller than the diameter of the outlet of the valve
served and shall discharge full size to the air gap.
|
Serve a single relief device and shall not connect to piping
serving any other relief device or equipment.
|
Exception: Multiple relief devices may be installed to a single
T & P discharge piping system when approved by the administrative
authority and permitted by the manufactures installation instructions
and installed with those instruction.
|
Discharge to an indirect waste receptor or to the outdoors.
Where discharging to the outdoors in areas subject to freezing, discharge
piping shall be first piped to an indirect waste receptor through
an air gap located in a conditioned area.
|
Discharge in a manner that does not cause personal injury or
structural damage.
|
Discharge to a termination point that is readily observable
by the building occupants.
|
Not be trapped.
|
Be installed so as to flow by gravity.
|
Not terminate less than six (6) inches or more than twenty-four
(24) inches (152 mm) above grade nor more than six (6) inches above
the waste receptor.
|
Not have a threaded connection at the end of such piping.
|
Not have valves or tee fittings.
|
Be constructed of those materials listed in Section 605.4 or
materials tested, rated and approved for such use in accordance with
ASME A112.4.1.
|
"Cross-linked polyethylene (PEX) plastic tubing."
|
"Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe."
|
"Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-PEX) pipe."
|
"Polybutylene (PB) plastic pipe and tubing." "Polyethylene (PE)
plastic pipe and tubing."
|
"Polypropylene (PP) plastic pipe and tubing." Section 606.1;
delete items #4 and #5.
|
Section 606.2; Delete #2.
|
on the fixture supply to each plumbing fixture other than bathtubs
and showers in one- and two-family residential occupancies, and other
than in individual sleeping units that are provided with unit shutoff
valves in hotels, motels, boarding houses and similar occupancies.
|
Deleted.
|
on the water supply pipe to each appliance or mechanical equipment.
|
610.1 General. New or repaired potable water systems shall be
purged of deleterious matter and disinfected prior to utilization.
The method to be followed shall be that prescribed by the health authority
or water purveyor having jurisdiction or, in the absence of a prescribed
method, the procedure described in either AWWA C651 or AWWA C652,
or as described in this Section. This requirement shall apply to "on-site"
or "in plant" fabrication of a system or to a modular portion of a
system.
|
The pipe system shall be flushed with clean, potable water until
dirty water does not appear at the points of outlet.
|
The system or part thereof shall be filled with a water/chlorine
solution containing at least fifty (50) parts per million (50 mg/L)
of chlorine, and the system or part thereof shall be valved off and
allowed to stand for twenty-four (24) hours; or the system or part
thereof shall be filled with a water/chlorine solution containing
at least two hundred (200) parts per million (200 mg/L) of chlorine
and allowed to stand for three (3) hours.
|
Following the required standing time, the system shall be flushed
with clean potable water until the chlorine is purged from the system.
|
The procedure shall be repeated where shown by a bacteriological
examination that contamination remains present in the system.
|
Exception: With prior approval the Building Commissioner may
wave this requirement when deemed unnecessary by the Building Commissioner.
|
Appliances in attics. Attics containing appliances requiring
access shall be provided. . . . (bulk of paragraph unchanged) . .
. side of the appliance. The clear access opening dimensions shall
be a minimum of twenty (20) inches by thirty (30) inches (508 mm by
762 mm), and/or larger where such dimensions are not large enough
to allow removal of the largest appliance. As a minimum, for access
to the attic space, provide one (1) of the following:
|
A permanent stair.
|
A pull-down stair.
|
An access door from an upper floor level.
|
Access panel may be used in lieu of Items 1, 2, and 3 if the
appliance is capable of being serviced from the access panel and opening
is large enough to remove the largest piece of equipment
|
Exceptions:
|
The passageway and level service space are not required where
the appliance is capable of being serviced and removed through the
required opening.
|
Where the passageway is not less than . . . (bulk of Section
to read the same).
|
Water heaters above ground or floor. When the attic, roof, mezzanine
or platform in which a water heater is installed is more than eight
(8) feet (2,438 mm) above the ground or floor level, it shall be made
accessible by a stairway or permanent ladder fastened to the building.
|
Exception: A max ten-gallon water heater (or larger with approval)
is capable of being accessed through a lay-in ceiling and a water
heater is installed is not more than ten (10) feet (3,048 mm) above
the ground or floor level and may be reached with a portable ladder.
|
Whenever the mezzanine or platform is not adequately lighted
or access to a receptacle outlet is not obtainable from the main level,
lighting and a receptacle outlet shall be provided in accordance with
Section 306.3.1.
|
The use of corrugated stainless-steel tubing (CSST) is subject
to the following procedure:
|
Community development department approval is required before
installation;
|
Letter verifying pressure from Gas Company;
|
No hybrid systems allowed;
|
Steel casings on all drop and risers;
|
Letter from manufacturer's representative verifying that product
has been installed in accordance with specifications.
|
Test pressure. The test pressure to be used shall be no less
than 3 psig (20 kPa gauge), or at the discretion of the Building Commissioner,
the piping and valves may be tested at a pressure of at least six
(6) inches (152 mm) of mercury, measured with a manometer or slope
gauge.
|
For tests requiring a pressure of 3 psig, diaphragm gauges shall
utilize a dial with a minimum diameter of three and one-half (3 1/2)
inches, a set hand, 1/10 pound incrementation and pressure range not
to exceed 6 psi for tests requiring a pressure of 3 psig.
|
For tests requiring a pressure of 10 psig, diaphragm gauges
shall utilize a dial with a minimum diameter of three and one-half
(3 1/2) inches, a set hand, a minimum of 2/10 pound incrementation
and a pressure range not to exceed 20 psi.
|
For welded piping, and for piping carrying gas at pressures
in excess of fourteen (14) inches water column pressure (3.48 kPa)
(1/2 psi) and less than two hundred (200) inches of water column pressure
(52.2 kPa) (7.5 psi), the test pressure shall not be less than ten
(10) pounds per square inch (69.6 kPa).
|
For piping carrying gas at a pressure that exceeds two hundred
(200) inches of water column (52.2 kPa) (7.5 psi), the test pressure
shall be not less than one and one-half (1 1/2) times the proposed
maximum working pressure.
|
Diaphragm gauges used for testing must display a current calibration
and be in good working condition. The appropriate test must be applied
to the diaphragm gauge used for testing.
|
Fire Escape access and details -. . .
| |
Access to a new fire escape shall be through a door . . .
| |
Strike whole Section.
| |
5. In all building of Group E Occupancy up to and including
the 12th grade, building of Group I Occupancy, boarding houses, and
childcare centers, ladders of any type are prohibited on fire escapes
used as a required means of egress.
|
Section 101.1.
|
Insert:
|
City of Vinita Park.
|
Section 101.2.1
|
Insert:
|
Adopts Appendices B — J
|
Section 103.1
|
Insert:
|
The Department of Fire Prevention shall mean Fire District.
|
Section 105.1.1
|
Insert:
|
Appendix A — Schedule of Fees.
|
Section 106.2
|
Change:
|
Title: Inspections Required
|
Section 113.2
|
Insert:
|
Appendix A — Schedule of Fees
|
Section 113.3
|
Insert:
|
Work commencing before permit issuance shall be charged an administrative
triple fee.
|
Section 113.4
|
Insert:
|
Appendix A — Schedule of Fees.
|
Section 113.5
|
Insert:
|
Refund policy shall comply with Appendix A: Schedule of Fees.
|
The provisions of this Article shall apply to all activity involving
the installation, servicing, repair, replacement, additions, modification,
and/or maintenance of electrical systems, conductors, equipment, fittings,
devices, motors, appliances, fixtures, signs and all other electrical
equipment within or on public or private buildings and premises.
|
80-2 Application to existing electrical systems and equipment.
|
Additions, alterations or repairs. Additions, alterations or
repairs may be made to any electrical system and equipment without
requiring the existing electrical system and equipment to comply with
all the requirements of this Code, provided that addition, alteration
or repair conforms to that required for a new electrical system and
equipment and provided further that no hazard to life, health or safety
will be created by such additions, alterations or repairs. Minor additions,
alterations and repairs to existing electrical system and equipment
may be made in accordance with the law in effect at the time the original
installation was made, when approved by the Building Commissioner.
|
Existing installations. Electrical systems and equipment lawfully
in existence at the time of the adoption of this Code may have their
use, maintenance or repair continued if the use, maintenance or repair
is in accordance with the original design and no hazard to life, health
or property has been created by such electrical system and equipment.
|
Change in building occupancy. Electrical systems and equipment
which are a part of any building or structure undergoing a change
in use or occupancy, as defined in the Building Code, shall comply
with the requirements of this code which are applicable to the new
use or occupancy.
|
Maintenance. All electrical systems and equipment, both existing
and new, and all parts thereof shall be maintained in a proper operating
condition in accordance with the original design and in a safe and
hazard free condition. All devices or safeguards which are required
by this code shall be maintained in conformance with this code. The
owner or his/her designated agent shall be responsible for the maintenance
of the electrical system. To determine compliance with this Subsection,
the Building Commissioner may cause any electrical system to be re-inspected.
|
Moved building. Electrical systems and equipment which are a
part of buildings or structures moved into or within the City of Vinita
Park shall comply with the provisions of this code for new installations.
|
Conflicting provisions.
|
Where, in any specific case, different Sections of this code
specify different materials, methods of construction or other requirements,
the most restrictive shall govern.
|
Modifications.
|
Whenever there are practical difficulties involved in carrying
out the provisions of this code, the Building Commissioner may grant
modifications for individual cases, provided he/she shall first find
that a special individual reason makes the strict letter of this code
impractical and the modification is in conformity with the intent
and purpose of this code, and that such modification does not lessen
health, life and fire safety requirements.
|
Tests.
|
Whenever there is insufficient evidence of compliance with any
of the provisions of this code or evidence that materials or construction
do not conform to the requirements of this code, the Building Commissioner
may require tests as evidence of compliance to be made at the sole
expense of the person providing such materials or performing such
construction.
|
Test methods shall be as specified by this code or by other
recognized test standards. In the absence of recognized and accepted
test methods for the proposed alternate, the Building Commissioner
may determine test procedures.
|
All tests shall be made by an approved agency. Reports of such
tests shall be retained by the Building Commissioner for a period
deemed appropriate by the Building Commissioner.
|
Unsafe electrical systems or equipment.
|
All electrical systems or equipment regulated by this code which
are unsafe, or which constitute a fire hazard, or are otherwise dangerous
to human life are, for the purpose of this Section, unsafe. Any use
of electrical systems or equipment regulated by this code constituting
a hazard to safety, health or public welfare by reason of inadequate
maintenance, dilapidation, obsolescence, fire hazard, disaster, damage
or abandonment is, for the purpose of this Section, an unsafe use.
All such unsafe electrical systems or equipment are hereby declared
to be public nuisances and shall be abated by repair, rehabilitation,
demolition or removal in accordance with the procedures set forth
in Article 3.03 "Abatement of Dangerous Buildings and Premises" of
the Vinita Park Code of Ordinances or such alternate procedure as
may be adopted by this jurisdiction. As an alternative, the Building
Commissioner or other employee or Commissioner of the City as designated
by the governing body may institute any other appropriate action to
prevent, restrain, correct or abate the violation.
|
Violations.
|
It shall be unlawful for any person, firm or corporation to
erect, construct, enlarge, alter, repair, move, improve, remove, convert
or demolish, equip, use or maintain any electrical system or equipment
or cause or permit the same to be done in violation of this Code.
The issuance or granting of a permit or approval of plans and specifications
or the completion or approval of an inspection shall not be deemed
or construed to be a permit for, or an approval of, any violation
of any of the provisions of this code. No permit presuming to give
authority to violate or cancel the provisions of this code shall be
valid, except insofar as the work or use which is authorized is lawful.
|
85-1 Powers and duties of Building Commissioner General. The
Building Commissioner is hereby authorized to enforce all the provisions
of this Code. He shall cause a record to be kept of all permits issued
and inspections made.
|
Deputies. In accordance with prescribed procedures and with
the approval of the appointing authority, the Building Commissioner
may appoint a Chief Electrical Inspector and other related technical
officers and inspectors and other employees as shall be authorized
from time to time. Reference to the "Inspector" and "Electrical Inspector"
in this code shall mean the Chief Electrical Inspector or other electrical
inspectors, or the Chief Building Commissioner.
|
Right of entry. Whenever necessary to make an inspection to
enforce any of the provisions of this code, or whenever the Building
Commissioner or his/her authorized representative has reasonable cause
to believe that there exists in any building or upon any premises
any condition or violation which makes such building or premises unsafe,
dangerous or hazardous, the Building Commissioner or his/her authorized
representative may enter such building or premises at all reasonable
times to inspect the same or to perform any duty imposed upon the
Building Commissioner by such codes, provided that if such building
or premises be occupied, he/she shall first present proper credentials
and request entry. If such building or premises is unoccupied, he/she
shall first make a reasonable effort to locate the owner or other
persons having charge or control of the building or premises and request
entry. If entry be refused, the Building Commissioner or his/her authorized
representative shall have recourse to every remedy provided by law
to secure entry. When the Building Commissioner or his/her authorized
representative shall have first obtained a proper inspection warrant
or other remedy provided by law to secure entry, no owner or occupant
or any other persons having charge, care or control of any building
or premises shall fail or neglect, after proper request is made as
herein provided, to promptly permit entry therein by the Building
Commissioner or his/her authorized representative for the purpose
of inspection and examination pursuant to this Code.
|
Notice. When any order or notice is issued pursuant to the provisions
of this code to any person who cannot be found after a reasonable
search, such order or notice may be served by posting it in a conspicuous
place upon the premises occupied by him/her or upon the premises where
the defects are alleged to exist. Such posting of the notice shall
be considered equivalent to personal service of such order or notice.
An order sent by mail in a sealed envelope with postage prepaid and
directed to the address of the electrical contractor, owner, lessee,
or occupant of the premises shall be equivalent to personal service
of such order. Electrical Inspectors are hereby empowered to attach
to the nearest electrical cabinet or equipment feeding defective or
hazardous wiring, any commissioner notice or seal to prevent use of
electricity in that area, and it shall be unlawful for any other person
to place or attach such seal, or to break, change, destroy, tear,
mutilate, cover or otherwise deface or injure any such commissioner
notice or seal posted by an Electrical Inspector.
|
Stop orders. Whenever any work is being done contrary to the
provisions of this code, the Building Commissioner may order the work
stopped by notice in writing served on any persons engaged in the
doing or causing such work to be done, and any such persons shall
forthwith stop such work until authorized by the Building Commissioner
to proceed with the work.
|
Authority to disconnect utilities in emergencies. The Building
Commissioner or his/her authorized representative shall have the authority
to disconnect any electric power or energy service supplied to the
building, structure or building service equipment therein regulated
by this code in case of emergency where necessary to eliminate an
immediate hazard to life or property. The Building Commissioner shall
whenever possible notify the serving utility, the owner and occupant
of the building, structure or building service equipment, in writing,
of such disconnection immediately thereafter.
|
Authority to condemn electrical system and equipment. Whenever
the Building Commissioner ascertains that any electrical system or
equipment regulated in this code has become hazardous to life, health
or property, he/she may order in writing that such electrical system
or equipment either be removed or restored to a safe condition, whichever
is appropriate. The written notice itself shall fix a time limit for
compliance with such order. No person shall use or maintain defective
electrical system or equipment after receiving such notice. When such
equipment or installation is to be disconnected, a written notice
of such disconnection and causes therefore shall be given within twenty-four
(24) hours of the order to disconnect to the serving utility, the
owner and occupant of such building, structure or premises. When any
electrical system or equipment is maintained in violation of this
code and in violation of any notice issued pursuant to the provisions
of this Section, the Building Commissioner shall institute any appropriate
action to prevent, restrain, correct or abate the violation.
|
Connection after order to disconnect. No person shall make connections
from any energy or power supply nor supply power to any electrical
system or equipment which has been disconnected or ordered to be disconnected
by the Building Commissioner or the use of which has been ordered
to be discontinued by the Building Commissioner until the Building
Commissioner authorizes the reconnection and use of such electrical
system or equipment.
|
Liability. The Building Commissioner, or his/her authorized
representative charged with the enforcement of this code, acting in
good faith and without malice in the discharge of his/her duties,
shall not thereby render himself/herself personally liable for any
damage that may accrue to persons or property as a result of any act
or by reason of any act or omission in the discharge of his/her duties.
Any suit brought against the Building Commissioner or employee because
of such act or omission performed by him/her in the enforcement of
any provision of this code shall be defended by legal counsel provided
by this jurisdiction until final termination of such proceedings.
This code shall not be construed to relieve from or lessen the responsibility
of any person owning, operating or controlling any building, structure
or building service equipment therein for any damages to persons or
property caused by defects, nor shall the code enforcement agency
or its parent jurisdiction be held as assuming any such liability
by reason of the inspections authorized by the code or approvals issued
under this code.
|
Cooperation of other Commissioners and officers. The Building
Commissioner may request and shall receive so far as is required in
the discharge of his/her duties, the assistance and cooperation of
other Commissioners of this jurisdiction.
|
Appeals. Any person, firm or corporation may file an appeal
with the Board of Adjustment for review of any decision of the Building
Commissioner, provided that such appeal is made in writing within
five (5) days after notification by the Electrical Inspector. The
Board of Adjustment shall meet within ten (10) days of receipt of
such appeal to hear the appeal and render a decision and findings
in writing to the appellant with a duplicate copy to the Building
Commissioner.
|
Requirements of electrical contractor.
|
Registration required. It shall be unlawful for any person,
firm, or corporation who is not registered as a qualified electrician
in the City of Vinita Park to engage in work regulated by this code.
Prior to the approval of any permit to do work regulated by this code,
the applicant for such permit must first register in person with the
Building Inspection Division.
|
Application for registration. A person, firm, or corporation
who desires to register as an electrical contractor's master electrician
or journeyman electrician in the City of Vinita Park shall complete
the appropriate application and provide the following information:
|
A current, electrical license issued by a municipality and accompanied
by a reciprocal letter or evidence of satisfactory performance on
master or journeyman electrician's certification conducted by the
St. Louis County, Missouri Department of Public Works Electrical,
Communications, Industrial and Elevator Contractor Licenses Requirements
and Regulations.
|
A form of picture identification.
|
Business identification to include the business name, business
owner(s), address, and telephone number.
|
Issuance and term of registration. Upon satisfactory completion
of the requirements of County licensing and payment of applicable
fees as specified in Appendix A for registration as an electrical
contractor, master electrician or journeyman electrician, the Building
Commissioner may approve such registration. An approved registration
is valid for a period of not more than one (1) year and shall terminate
at the end of each calendar year.
|
Transfer of registration. It shall be unlawful for any person,
firm, or corporation to lend, rent, or transfer an electrical registration
issued by the City of Vinita Park to another other person firm, or
corporation for any purpose.
|
Revocation of registration. An electrical registration issued
by the City of Vinita Park may be revoked by the Building Commissioner
for the following:
|
Falsification of any portion of an application for registration
with intent to defraud.
|
Any person, firm or corporation who, after being found guilty
in Municipal Court of violations of this code, is unwilling to make
appropriate corrections to the satisfaction of the Building Commissioner
or his/her designee shall be denied registration as an electrical
contractor, master or journeyman electrician.
|
Transfer of registration as stipulated in Section 85-2(d) of
this code.
|
Notice of revocation of electrical registration. The Building
Commissioner shall provide proper notice in writing to the person,
firm or corporation holding a defective electrical registration of
the decision to revoke an electrical registration. Notice shall be
deemed effective on the post date of certified mail and/or acceptance
by hand delivery.
|
Appeal of revocation. In the event that any person, firm or
corporation shall appeal the decision of the Building Commissioner
to revoke an electrical registration, a request for a public hearing
of the matter shall be made in writing to the Chairman of the Board
of Adjustment within five (5) days of receipt of notice of revocation
as specified in this Section. The Board of Adjustment shall meet to
consider an appeal of revocation within ten (10) days of receipt of
a written request.
|
False representation as to registration unlawful. It shall be
unlawful for any person, firm, or corporation to represent himself/herself
or a business as an electrician or electrical contractor in the City
of Vinita Park without having first properly registered with the Building
Inspection Division. Electrical company vehicles to be marked. All
electrical contractors' vehicles engaged in doing work in the City
of Vinita Park shall have signs permanently affixed to both sides
of the vehicle indicating the company name of the electrical contractor.
|
Supervision. The actual work of installing, maintaining, altering,
or repairing of electrical work for which a permit is required by
this code shall have supervision by a licensed master or journeyman
electrician as provided by this code. In the event the owner of electrical
contracting business is not a licensed master electrician, a master
electrician shall be designated by the owner of such place of business
to the Building Commissioner as the person responsible for, and supervising,
the electrical work done by such electrical contractor. Such designated
master electrician shall be the supervisory electrician for only one
(1) electrical contractor within the City at any one time. Should
such supervision not be constantly provided, the Electrical Inspector
may order the work being done by such electrical contractor to be
discontinued until proper supervision and control has been provided
and the name of the new master electrician disclosed to Building Commissioner.
|
License display. Each holder of a master, journeyman or specialist
license shall carry evidence of proper license on his/her person at
all times while doing electrical work and shall produce and exhibit
same when requested by an inspector or officer of the City.
|
Exception from licensing and registration.
|
Persons who are not registered electricians may carry out the
following classes of work:
|
The replacement of lamps, fuses and the connection of portable
devices to suitable receptacles which have been permanently installed.
|
The installation, alteration, or repairing of any wiring, devices,
or equipment for signaling, remote control, or the transmission of
information, provided such are inherently power limited and have a
maximum nameplate rating not exceeding one volt-ampere.
|
The installation, alteration or repair of the electric wiring,
devices, appliances and equipment installed by or for an electrical
public service corporation legally operating in the City when for
the use of such corporation in the generation, transmission, distribution
or metering of the electrical energy or for the use of such a corporation
in the operation of street railways, signals or the transmission of
information.
|
Any work involved in the manufacture or test of electrical materials,
devices, appliances or apparatus, but not including any installation
of wiring other than that required for testing purposes unless such
equipment as complete is approved by the Electrical Inspector before
it is installed or used.
|
Permits.
|
Permits required. Except as specified in Subsection (c) of this
Section, no electrical system regulated by this code shall be installed,
altered, repaired, replaced or remodeled unless a separate electrical
permit for each building or structure has first been obtained from
the Building Commissioner. It shall be unlawful for any person, firm
or corporation who is not registered by the City as an electrical
contractor to secure permits except as provided in Section 85-3. It
shall be unlawful for any person to lend, rent, or transfer an electrical
permit, or permit a person without proper license or registration
to do the work, or for any person to make use of any such permit which
is not actually his own, and any such permit obtained or submitted
under these conditions shall be null and void.
|
Exempt work. An electrical permit shall not be required for
the following:
|
Portable motors or other portable appliances energized by means
of a cord or cable having an attachment plug end to be connected to
an approved receptacle when that cord or cable is permitted by this
code.
|
Repair or replacement of fixed motors, transformers or fixed
approved appliances of the same type and rating in the same location.
|
Temporary decorative lighting.
|
Repair or replacement of current-carrying parts of any switch,
contactor or control device.
|
Reinstallation of attachment plug receptacles, but not the outlets
therefor.
|
Repair or replacement of any over current device of the required
capacity in the same location.
|
Repair or replacement of electrodes or transformers of the same
size and capacity for signs or gas tube systems.
|
Taping joints.
|
Removal of electrical wiring.
|
Temporary wiring for experimental purposes in suitable experimental
laboratories.
|
Electrical wiring, devices, appliances, apparatus or equipment
operating at less than twenty-five (25) volts and not capable of supplying
more than fifty (50) watts of energy.
|
A permit shall not be required for the installation, alteration
or repair of electrical wiring, apparatus or equipment or the generation,
transmission, distribution or metering of electrical energy or in
the operation of signals or the transmission of intelligence by a
public or private utility in the exercise of its function as a serving
utility.
|
Exemption from the permit requirements of this code shall not
be deemed to grant authorization for any work to be done in violation
of the provisions of this code or any other laws or ordinances.
|
Application for permit. To obtain a permit, the applicant shall
first file an application therefore in writing on a form furnished
by the City agency for that purpose. Every such application shall:
|
Identify and describe the work to be covered by the permit for
which application is made.
|
Describe the land on which the proposed work is to be done by
legal description, street address or similar description that will
readily identify and definitely locate the proposed building or work.
|
Indicate the use or occupancy for which the proposed work is
intended.
|
Be accompanied by plans, diagrams, computations and specifications
and other data as required in Subsection (d) of this Section.
|
Be signed by permittee, or his/her authorized agent.
|
Give such other data and information as may be required by the
Building Commissioner.
|
Plans and specifications. With each application for a permit,
and where required by the Building Commissioner for enforcement of
any provision of this code, plans, specifications and calculations
shall be submitted in the quantity deemed necessary by the Building
Commissioner. When deemed necessary by the Building Commissioner to
ensure code compliance, the Building Commissioner may require plans
and specifications to be prepared and designed by an engineer licensed
by the State of Missouri. All drawings, specifications and accompanying
data involved with the practice of engineering, such as structural,
mechanical, plumbing, electrical, heating and cooling, fire, life
and safety systems, shall comply with State and local laws governing
the practice of engineering as required by the Missouri Statutes.
|
Information on plans and specifications. Plans and specifications
shall be drawn to scale upon substantial paper or cloth and shall
be of sufficient clarity to indicate the location, nature and extent
of the work proposed and show in detail that it will conform to the
provisions of this code and all relevant laws, ordinances, rules and
regulations.
|
Permits issuance. The applications, plans and specifications,
and other data, filed by an applicant for permit may be reviewed by
other departments of the City to determine compliance with any applicable
laws under their jurisdiction. If the work described in an application
for a permit and the plans, specifications and other data filed therewith
conforms to the requirements of this code and other pertinent laws
and ordinances, and the fees specified by the City of Vinita Park
fee schedule have been paid, the Building Commissioner may issue a
permit therefor to the applicant. When the Building Commissioner issues
the permit where plans are required, he/she shall endorse in writing
or stamp the plans and specifications "APPROVED." Such approved plans
and specifications shall not be changed, modified or altered without
authorizations from the Building Commissioner, and all work shall
be done in accordance with the approved plans. The Building Commissioner
may issue a permit for the construction of part of an electrical system
before the entire plans and specifications for the whole system have
been submitted or approved, provided adequate information and detailed
statements have been filed complying with all pertinent requirements
of this code. The holder of such permit shall proceed at his/her own
risk with assurance that the permit for the entire building, structure
or building service will be granted.
|
Retention of plans. One (1) set of approved plans and specifications
shall be returned to the applicant and shall be kept on the site of
the building or work at all times during which the work authorized
thereby is in progress. One (1) set of approved plans, specifications
and computations shall be retained by the Building Commissioner until
final approval of the work.
|
Validity of permit. The issuance of a permit or approval of
plans and specifications shall not be construed to be a permit for,
or an approval of, any violation of any of the provisions of this
code, or of any other ordinance of the City, nor shall the issuance
of a permit or approval of plans be construed as representing or warranting
the safety or lack of defects of any electrical work described therein.
No permit presuming to give authority to violate or cancel the provisions
of these codes shall be valid. The issuance of a permit based upon
plans, specifications and other data shall not prevent the Building
Commissioner from thereafter requiring the correction of errors in
said plans, specifications and other data, or from preventing building
operations being carried on thereunder when in violation of these
codes or of any other ordinances of the City.
|
Expiration. Every permit issued by the Building Commissioner
under the provisions of this code shall expire by limitation and become
null and void, if the building or work authorized by such permit is
not commenced within sixty (60) days from the date of such permit,
or if the building or work authorized by such permit is suspended
or abandoned at any time after the work is commenced for a period
of sixty (60) days or more.
|
Before such work can be recommenced, a new permit shall be first
obtained, and the fee therefore shall be one-half (1/2) the amount
required for a new permit for such work, provided no changes have
been made or will be made in the original plans and specifications
for such work; and provided, further, that such suspension or abandonment
has not exceeded one (1) year. In order to renew action on a permit
after expiration, the permittee shall pay a new full permit fee. Any
permittee holding an unexpired permit may apply for an extension of
the time within which he/she may commence work under that permit when
he/she is unable to commence work within the time required by this
Section for good and satisfactory reasons. The Building Commissioner
may extend the time for action by the permittee for a period not exceeding
one hundred eighty (180) days upon written request by the permittee
showing that circumstances beyond the control of the permittee have
prevented action from being taken. No permit shall be extended more
than once.
|
Suspension or revocation. The Building Commissioner may, in
writing, suspend or revoke a permit issued under the provisions of
this code whenever the permit is issued in error or on the basis of
incorrect information supplied, or in violation of any ordinance or
regulation of the City.
|
Fees. Permit fees shall be levied in the amounts specified by
the City of Vinita Park in Appendix A. For fee calculation purposes,
the building area is the total floor area expressed in square feet
of all stories devoted to human occupancy, including halls, stairways,
elevators, and other uses measured to the outside face of exterior
walls, except for attached garages, carports, porches, patios and
other like roofed areas shall contribute one-half (1/2) of their total
area in square footage for the purpose of electrical permit fee calculation.
The total building area for fee calculation purposes shall be stated
on the application for electrical permit. Work started without a permit
shall be charged an administrative triple fee along with regular permit
fee.
|
Inspections.
|
General. All electrical systems and equipment for which a permit
is required by this code shall be subject to inspection by the Building
Commissioner. No portion of any electrical system intended to be concealed
shall be concealed until inspected and approved. Neither the Building
Commissioner nor the City shall be liable for expense entailed in
the removal or replacement of any material necessary to allow inspection.
When the installation of an electrical system and equipment is complete,
an additional and final inspection shall be made. Electrical systems
and equipment regulated by this code shall not be connected to the
energy source until authorized by the Building Commissioner.
|
Inspection requests. It shall be the duty of the person doing
the work authorized by a permit to schedule required inspections at
least one (1) working day before such inspection is desired. It shall
be the duty of the person requesting inspections required by this
code to provide access to and means for proper inspection of such
work.
|
Operation of electrical equipment. The requirements of this
Section shall not be construed to prohibit the operation of any electrical
system or equipment installed to replace existing equipment. The request
for inspection of such equipment must have been filed with the Building
Commissioner not more than forty-eight (48) hours after such replacement
work is completed and before any portion of such electrical system
is concealed by any permanent portion of the building.
|
Other inspections. In addition to the called inspections required
by this code, the Building Commissioner may make or require other
inspections of any work to ascertain compliance with the provisions
of this code and other laws which are enforced by the code enforcement
agency.
|
Re-inspections. A re-inspection fee may be assessed for each
inspection or re-inspection when such portion of work for which inspection
is called is not complete or when required corrections are not made.
This provision is not to be interpreted as requiring re-inspection
fees the first time a job is rejected for failure to comply with the
requirements of this code, but as controlling the practice of calling
for inspections before the job is ready for such inspection or re-inspection
or when required corrections are not made. Re-inspection fees may
be assessed when the approved plans are not readily available to the
inspector, for failure to provide access on the date for which inspection
is requested, or for deviating from plans requiring the approval of
the Building Commissioner. In instances where re-inspection fees have
been assessed, no additional inspection of the work will be performed
until the required fees have been paid.
|
General. For the purpose of these provisions, certain terms,
phrases, words and their derivatives shall be construed as specified
in this Section. Where terms are not defined, they shall have their
ordinarily accepted meanings within the context with which they are
used. Webster's Third New International Dictionary of the English
Language, Unabridged, 2002, shall be considered as providing ordinarily
accepted meanings.
|
Approved as to materials, equipment and method of construction.
Refers to approval by the Building Commissioner as the result of investigation
and tests conducted by him/her, or by reason of accepted principles
or tests by recognized authorities, technical or scientific organizations.
|
Approved Agency. An established and recognized agency regularly
engaged in conducting tests or furnishing inspection services, when
such agency has been approved by the Building Commissioner or Fire
Chief, or their designee.
|
Board of Appeals. Shall be the Board of Adjustment as appointed
by the Board of Aldermen of the City of Vinita Park.
|
Building Code. The Building Code as adopted by the City of Vinita
Park.
|
Building Commissioner. The designated authority charged with
the administration and operation of the Community Development Department
|
Building Commissioner. The officer charged with the administration
and enforcement of this code, or his/her duly authorized representative,
and is the authority having jurisdiction for this code.
|
Chief Electrical Inspector or Electrical Inspector. Shall be
the person providing expertise for the Building Commissioner in the
area of electrical regulations.
|
Code Enforcement Agency. The department, division or agency
of the City of Vinita Park charged with the function of code enforcement
and shall be under the administration and operational control of the
Public Works Department.
|
Electrical Contractor. Any person, firm, or corporation to whom
a valid, current electrical contractor's registration has been issued
by the City of Vinita Park.
|
Electrical Code. The National Electrical Code promulgated by
the National Fire Protection Association, as adopted by the City of
Vinita Park.
|
Engineering Supervision. Supervision by a qualified State of
Missouri licensed professional engineer engaged primarily in the design
or maintenance of electrical installations.
|
Firewall. The same as an area separation wall as used in the
Building Code.
|
Intersystem Bonding Termination. A device that provides a means
for connecting intersystem bonding conductors for communication systems
and other systems such as metallic gas piping systems to the grounding
electrode system. Bonding conductors for other systems shall not be
larger than 6 AWG.
|
Journeyman Electrician. A person to whom a valid, current journeyman
electrician's registration has been issued by the City of Vinita Park.
|
Master Electrician. A person to whom a valid, current master
electrician's registration has been issued by the City of Vinita Park.
|
Multiple Occupancy Building. A building having more than one
(1) tenant and may be of single or mixed-use groups as classified
by the Building Code.
|
Occupancy. The purpose for which a building, or part thereof,
is used or intended to be used.
|
(a)
|
NM, NMC, and NMS. Types NM, NMC, and NMS cables shall not be
permitted as follows:
|
(11)
|
In non-residential metal frame structures.
|
500.8 Equipment.
|
Articles 500 through 504 require equipment construction and
installation that ensure safe performance under conditions of proper
use and maintenance.
|
Informational Note No. 1: It is important that inspection authorities
and users exercise more than ordinary care with regard to installation
and maintenance.
|
Informational Note No. 2: Since there is no consistent relationship
between explosion properties and ignition temperature, the two (2)
are independent requirements.
|
Informational Note No. 3: Low ambient conditions require special
consideration. Explosion proof or dust-ignition proof equipment may
not be suitable for use at temperatures lower than -25° C. (-3°
F.) unless they are identified for low-temperature service. However,
at low ambient temperatures, flammable concentrations of vapors may
not exist in a location classified as Class I,
|
Division 1 at normal ambient temperature.
|
Suitability. Suitability of identified equipment shall be determined
by one (1) of the following:
|
Equipment listing or labeling.
|
Evidence of equipment evaluation from a qualified testing laboratory
or inspection agency concerned with product evaluation.
|
Evidence acceptable to the authority having jurisdiction such
as a manufacturer's self-evaluation or an engineering judgment signed
and sealed by a qualified licensed professional engineer in the State
of Missouri.
|
Informational Note: Additional documentation for equipment may
include certificates demonstrating compliance with applicable equipment
standards, indicating special conditions of use, and other pertinent
information.
|
505.7 Special Precaution.
| |
Article 505 requires equipment construction and installation
that ensures safe performance under conditions of proper use and maintenance.
| |
Informational Note No. 1: It is important that inspection authorities
and users exercise more than ordinary care with regard to the installation
and maintenance of electrical equipment in hazardous (classified)
locations.
| |
Informational Note No. 2: Low ambient conditions require special
consideration. Electrical equipment depending on the protection techniques
described by 505.8(A) may not be suitable for use at temperatures
lower than -20° C. (-4° F.) unless they are identified for
use at lower temperatures. However, at low ambient temperatures, flammable
concentrations of vapors may not exist in a location classified Class
I, Zones 0, 1, or 2 at normal ambient temperature.
| |
(A) Implementation of Zone Classification System. Classification
of areas, engineering and design, selection of equipment and wiring
methods, installation, and inspection shall be performed by a qualified
person(s), registered licensed professional engineer in the State
of Missouri.
|
Coordination. Over-current protective devices serving the equipment
branch of the essential electrical system shall be coordinated for
the period of time that a fault's duration extends beyond 0.1 second.
|
Exception No. 1: Between transformer primary and secondary over-current
protective devices, where only one (1) over-current protective device
or set of over-current protective devices exists on the transformer
secondary.
|
Exception No. 2: Between over-current protective devices of
the same size (ampere rating) in series.
|
Informational Note: The terms coordination and coordinated as
used in this Section do not cover the full range of over-current conditions.
|
Selective Coordination. Over-current protective devices serving
the life safety, and critical branches of the essential electrical
system shall be selectively coordinated with all supply-side over-current
protective devices.
|
Exception No. 1: Between transformer primary and secondary over-current
protective devices, where only one (1) over-current protective device
or set of over-current protective devices exists on the transformer
secondary.
|
Exception No. 2: Between over-current protective devices of
the same size (ampere rating) in series.
|
Informational Note: The terms coordination and coordinated as
used in this Section do not cover the full range of over-current conditions.
|
680.25 Feeders.
|
These provisions shall apply to any feeder on the supply side
of panel boards supplying branch circuits for pool equipment covered
in Part II of this Article and on the load side of the service equipment
or the source of a separately derived system.
|
Wiring Methods.
|
Feeders. Feeders shall be installed in rigid metal conduit,
intermediate metal conduit. The following wiring methods shall be
permitted if not subject to physical damage:
|
Liquid-tight flexible non-metallic conduit.
|
Rigid polyvinyl chloride conduit.
|
Reinforced thermosetting resin conduit.
|
Electrical metallic tubing where installed on or in a building.
|
Electrical non-metallic tubing where installed within a building.
|
Type MC Cable where installed within a building and if not subject
to corrosive environment.
|
Non-metallic-sheathed cable.
|
Type SE cable.
|