[Ord. No. 829, § 1, 7-20-2010; Ord. No. 896, § I, 4-21-2015]
Unless otherwise expressly stated, the following terms shall,
for the purpose of this code, have the meaning indicated in this section:
ACCESS BOX
A steel key vault, mounted on the exterior of a building
that contains keys, floor plans, maps or other items as required by
the AHJ, for access to all portions of the building.
ADULT DAY CARE
Any place, that receives at any time for compensation four
or more adults, for care and supervision, for less than 24 hours a
day.
ADULT FAMILY HOME
Similar to a CBRF except that they are licensed for five
or less tenants.
APPROVED AGENCY
An agency accepted or acceptable to the bureau of fire prevention,
such as Underwriters Laboratories, Inc., the National Institute of
Standards and Technology, the American Gas Association laboratories
or other nationally recognized testing authorities.
ASSEMBLY GROUP A
Group A occupancies includes, among other, the use of a building
or structure, or a portion thereof, for the gathering together of
persons for purposes such as civic, social or religious functions,
recreation, food or drink consumption or awaiting transportation.
A room or space used for assembly purposes by less than 50 persons
and accessory to another occupant shall be included as a part of that
occupancy. Assembly occupancies shall include the following:
(a)
A-1 — Assembly uses, usually with fixed seating, intended
for the production and viewing of performing arts or motion pictures.
(b)
A-2 — Assembly uses intended for food and/or drink consumption.
(c)
A-3 — Assembly uses intended for worship, recreation or
amusement and other assembly uses not classified elsewhere in Group
A.
(d)
A-4 — Assembly uses intended for viewing of indoor sporting
events and activities with spectator seating.
(e)
A-5 — Assembly uses intended for participation in or viewing
outdoor activities.
AUTHORITY HAVING JURISDICTION (AHJ)
The Fire Chief, or designee of the Fire Chief, to enforce
this code, the laws of the State of Wisconsin, as designated in § SPS
314.02(1), [Wis. Adm. Code], pertaining to the prevention of fires
and public safety, and approving equipment installation, or procedures
as outlined in NFPA Standards, Codes and/or Recommended Practices.
AUTOMATIC CLOSING DEVICE
One which functions without human intervention and is actuated
as a result of predetermined temperature rise, rate of rise of temperature,
combustion products or smoke density.
AUTOMATIC FIRE ALARM SYSTEM
A system which automatically detects fire condition and actuates
notification appliances throughout the protected premises.
AUTOMATIC FIRE SPRINKLER SYSTEM
An integrated system of underground and/or overhead piping
designed in accordance with fire protection standards. The system
includes a suitable water supply. The portion of the system above
ground is a network of specially sized or hydraulically designed piping
installed in a structure or area, generally overhead, and to which
automatic sprinklers are connected in a systematic pattern. The system
is usually activated by heat from a fire and discharges water over
the fire area.
AUTOMATIC FIRE-EXTINGUISHING SYSTEM
An approved system of devices and equipment which automatically
detects a fire and discharges an approved fire-extinguishing agent
onto or in the area of fire.
BASEMENT
That portion of a building that is partly or completely below
grade plane. A basement shall be considered as a story.
BOARDING HOUSE
A building arranged or used as lodging for compensation,
with or without meals, not occupied as a single-family unit.
BUREAU OF FIRE PREVENTION
The bureau of fire prevention is made up of the following
personnel: the Fire Chief, the fire marshal and/or fire inspectors,
or any other designee of the chief.
BUSINESS GROUP B
Group B occupancy includes, among others, the use of a building
or structure, or a portion thereof, for office, professional or service-type
transactions, including storage of records and accounts.
CEILING
The upper surface of a space, regardless of height. Areas
with a suspended ceiling would have two ceilings, one visible from
the floor, and one above the suspended ceiling.
CODE
A standard that is an extensive compilation of provisions
covering a broad subject matter or that is suitable for adoption into
law independently of other codes and standards.
COMBUSTIBLE MATERIAL
All material not classified as noncombustible are considered
combustible. This property of a material does not relate to its ability
to structurally perform under fire exposure. The degree of combustibility
is not defined by standard fire test procedures.
COMM
Wisconsin Department of Commerce.
COMMON AREA
Common area refers to any area in a building that can be
accessed by more than one person from different families at one time.
COMMUNITY BASED RESIDENTIAL FACILITY (CBRF)
A community facility where five or more adults who are not
related to the operator or Administrator and who do not require care
above intermediate level nursing care reside and receive care, treatment
or services that are above the level of room and board, but that include
no more than three hours of nursing care per week per resident.
CONDITIONAL APPROVAL
An approval of plans and/or specifications by the AHJ based
upon information provided to the AHJ, including, but not limited to,
any changes required by the AHJ to the above mentioned plans and/or
specifications.
CONSULTANT(S)
A company, individual or agency hired by the bureau of fire
prevention to provide advice to the bureau of fire prevention on fire
related issues. Consultants may provide services, which could include
plan reviews of fire suppression systems, fire alarm systems, witness
tests and/or conduct inspections.
DAY CARE CENTER
Any place which receives at any one time for compensation
four or more children under the age of seven years, for care and supervision,
for less than 24 hours a day or more than 10 days a month, without
the attendance of a parent, relative or legal guardian.
DWELLING or DWELLING UNIT
A single unit providing living facilities for one or more
persons, including permanent provisions for living, sleeping, eating,
cooking and sanitation. For the purpose of this code, dwelling unit
includes apartments and condominiums but does not include hotel and
motel rooms, guest suites, dormitories, boarding rooms, or sleeping
rooms in nursing homes.
(b)
TWO-FAMILY DWELLINGA detached building containing not more than two individual dwelling units which are entirely separated by vertical walls or horizontal floors, unpierced except for access to the outside or common basement.
EDUCATIONAL GROUP E
Group E occupancy includes, among others, the use of a building
or structure, or a portion thereof, by six or more persons at any
one time for educational purposes through the 12th grade.
FACTORY INDUSTRIAL GROUP F
Group F occupancy includes, among others, the use of a building
or structure, or a portion thereof, for assembly, disassembly, fabricating,
finishing, manufacturing, packaging, repair or processing operations
that are not classified as group H occupancy.
(a)
F-1 — Moderate-hazard occupancy.
(b)
F-2 — Low-hazard occupancy.
FALSE ALARM
The willful and knowing initiation or transmission of a signal,
message or other notification of an event of fire when no such danger
exists.
(a)
MALICIOUS ALARMA false alarm of fire deliberately sounded by someone in order to inconvenience the fire department.
(b)
ACCIDENTAL ALARMAn alarm set off and transmitted through accidental operation of an automatic or manual fire alarm device.
FAMILY UNIT
Two or more individuals who are related to each other by
blood, marriage, adoption or legal guardianship. For purposes of this
abode a group of not more than four persons not necessarily related
by blood or marriage, living together in a single living unit will
be considered equivalent to a single family.
FIRE ALARM ANNUNCIATION DEVICE
A device connected to a fire alarm to signal either a fire
or trouble condition. Fire alarm annunciation devices could include
visual devices, horn/strobes, horns, bells, and/or annunciator panels.
FIRE ALARM INITIATING DEVICE
A device connected to a fire alarm system that causes a trouble,
supervisory and/or alarm signal to be initiated. Fire alarm initiating
devices could include: smoke, heat, flame, ionization, or photoelectric
detectors, water flow, low air, low temperature, low water, or supervisory
switches.
FIRE ALARM SYSTEM
A system or portion of a combination system that consists
of components and circuits arranged to monitor and annunciate the
status of the fire alarm or supervisory signal-initiating devices
to activate notification appliances throughout the protected premises
and to initiate the appropriate response to those signals.
FIRE CONTROL SYSTEM
A system designed and constructed with the intent of controlling
or limiting a fire. Fire control systems may be automatic or non-automatic.
Fire control systems could include automatic fire sprinkler systems,
standpipe systems, chemical agent systems, fire hydrants and/or any
other system acceptable to the AHJ.
FIRE DEPARTMENT CONNECTION (FDC)
A part of a sprinkler, standpipe, deluge and/or combination
system to be used by the fire department to pump additional water
into the system(s) it is connected to.
FIRE DOOR ASSEMBLY
Any combination of a fire door, frame, hardware, and other
accessories that together provide a certain degree of fire protection
to the opening.
FIRE RESISTIVE
That property of materials of their assemblies that prevents
or retards the passage of excessive heat, hot gases or flame under
conditions of use. Materials are tested as prescribed in Section 703
of the Wisconsin Enrolled Building Code.
FIREWALL
A fire-resistance-rated wall having protected openings, which
restricts the spread of fire and extends continuously from the foundation
to or through the roof, with sufficient structural stability under
fire conditions to allow collapse of construction on either side without
collapse of the wall.
FLOOR AREA OR SQUARE FOOTAGE OF A BUILDING
Refers to the total square footage of the sums of all basement,
floor levels, balconies and mezzanines.
(a)
The area for basements and floor levels shall be measured from
the outside perimeter of the outside walls.
(b)
The area for mezzanines shall be determined from the product
of the length of the mezzanine multiplied by the width of the mezzanine.
(c)
For the purpose of determining square footage, fire division
walls will not be accepted as outside walls or area dividers.
(d)
Buildings that are in close proximity to each other will have
their buildings square footage added together to arrive at the total
square footage.
(1)
For the purpose of determining close proximity the following
will hold true:
a.
Single story buildings: 30 feet apart or less.
b.
Two-story buildings: 60 feet apart or less.
c.
Three-story buildings: 60 feet apart or less.
d.
All other multiple story buildings: 60 feet apart.
e.
Buildings of variable height next to each other: 30 feet apart
or less.
(e)
For the purpose of determining square footage a firewall which
has a fire-resistance rating of not less than four hours and which
subdivides or separates a building to restrict the spread of fire,
including a three-foot parapet wall is an approved area divider.
FLOOR, GROUND
That level of a building on a sloping or multilevel site
which has a floor line at or not more than three feet above exit discharge
grade for at least one-half of the required exit discharges.
FREQUENTER
Every person, other than an employee, who may go in or be
in a place of employment or public building under circumstances which
render such person other than a trespasser. Such term includes a pupil
or student when enrolled in or receiving instruction at an educational
institution.
GRADE PLANE
A reference plane representing the average of finished ground
level adjoining the building exterior walls. Where the finished ground
level slopes away from the exterior walls, the reference plane shall
be established by the lowest points within the area between the building
and the lot line or, where the lot line is more than six feet from
the building, between the building and a point six feet from the building.
HAZARDOUS GROUP H
Group H occupancy includes, among others, the use of a building
or structure, or a portion thereof, that involves the manufacturing,
processing, generation or storage of materials that constitute a physical
or health hazard in quantities in excess of those found in Tables
307.7(1) through 307.7(4) of the International Building Code.
(a)
H-1 — Buildings and structures which contain materials
that poses a detonation hazard.
(b)
H-2 — Buildings and structures which contain materials
that pose a deflagration hazard or a hazard from accelerated burning.
(c)
H-3 — Buildings and structures which contain materials
that readily support combustion or pose a physical hazard.
(d)
H-4 — Buildings and structures which contain materials
that are health hazards.
(e)
H-5 — Semiconductor fabrication facilities and comparable
research and development areas in which hazardous production materials
are used and the aggregate quantity of materials is in excess of those
listed in Tables 307.7(1) and 307.7(2) of the International Building
Code.
HEIGHT, BUILDING
The vertical distance from the grade plane to the average
height of the highest roof surface.
INSTITUTIONAL GROUP I
Group I occupancy includes, among others, the use of a building
or structure, or a portion thereof, in which people having physical
limitations because of health or age are harbored for medical treatment
or other care or treatment, or in which people are detained for penal
or correctional purposes or in which the liberty of the occupants
is restricted. Institutional occupancies are classified as I-1, I-2,
I-3 or I-4, as described in the International Building Code.
LISTED
Included in a list published by a nationally recognized testing
laboratory, inspection agency, or other organization concerned with
product evaluation, that maintains periodic inspection of production
of listed equipment or materials and whose listing states either that
the equipment or materials meet nationally recognized standards or
has been tested and found suitable for use in a specified manner.
MANUAL FIRE ALARM SYSTEM
A system or portion of a combination system that consists
of components and circuits arranged to initiate the notification appliances
and appropriate response to those signals only after a person manually
activates the fire alarm system.
MERCANTILE GROUP M
Group M occupancy includes, among others, building and structures
or a portion thereof, for the display and sale of merchandise, and
involves stock of goods, wares or merchandise incidental to such purposes
and accessible to the public.
MEZZANINE or MEZZANINE FLOOR
An intermediate level or levels between floor and ceiling
of any story with an aggregate floor area of not more than one-third
of the area of the room or space in which the level or levels are
located.
MISCELLANEOUS GROUP U
Buildings and structures of an accessory character and miscellaneous
structures not classified in any specific occupancy shall be constructed,
equipped and maintained to conform to the requirements of this code
commensurate with the fire and life hazard incidental to their occupancy.
MULTIFAMILY DWELLING
A building or portion thereof containing three or more dwelling
units, such as tenements, apartments, or rooming houses. Row houses
with firewalls extending from the basement to the underside of the
roof separating each living unit are not considered multifamily for
the purpose of this chapter.
NFPA
The National Fire Protection Association.
NONCOMBUSTIBLE MATERIALS
A noncombustible material is one which, in the form in which
it is used, meets one of the requirements listed below. Materials
used adjacent to or in contact with heat producing appliances, warm
air ducts, plenums and chimneys shall be classified as noncombustible
only on the basis of requirement (a). Noncombustible does not apply
to the flame-spread characteristics of interior finish or trim materials.
No material shall be classified as noncombustible building construction
material, which is subject to increase in combustibility or flame-spread
classification (FSC) beyond the limits herein established through
the effects of age, moisture or other atmospheric conditions. (See
flame spread rating in WI. Adm. Code.)
(a)
Materials which pass the test procedure of ASTM E-136 for noncombustibility
of elementary materials when exposed to a furnace temperature of 1,382°
F. for a minimum period of five minutes and do not cause a temperature
rise of the surface or interior thermocouple in excess of 54°
F. above the furnace air temperature at the beginning of the test
and which do not flame after exposure of 30 seconds.
(b)
Materials having structural base of noncombustible material as defined in Subsection
(a), with a surfacing not more than one-eighth-inch thick which has a flame-spread classification (FSC) not greater than 50 when tested in accordance with the method of test for surface burning characteristics of building materials (ASTM E-84).
NOTIFICATION APPLIANCE
A fire alarm system component such as a bell, horn, speaker,
light, or text display that provides audible, tactile, visible outputs,
or any combination thereof.
OCCUPANT(S)
The person or persons who physically reside, work or are
present in a facility.
OTHER TERMS
Other terms not defined herein used in this section shall
be as defined in the International Fire Code Section 202 and are adopted
herein by reference.
OWNER
Includes his duly sworn agent or attorney, a purchaser, devisee,
fiduciary or person having a vested or contingent interest in the
property in question.
PLACES OF EMPLOYMENT
Includes every place, whether indoors or out or underground
and the premises appurtenant thereto where either temporarily or permanently
any industry, trade or business is carried on, or where any process
or operation, directly or indirectly related to any industry, employed
by another for direct or indirect gain or profit, but does not include
any place where persons are employed in private domestic service which
does not involve the use of mechanical power or in farming.
REMODEL
To remodel, alter or both, means to change any building or
structure which affects the structural strength, fire hazard, internal
circulation, or exits of the existing building or structure. This
definition does not apply to maintenance, re-roofing, or alterations
to the heating and ventilating or electrical system.
RESIDENTIAL GROUP R
Group R occupancy includes, among others, the use of a building
or structure, or portion thereof, for sleeping accommodations when
not classed as an institutional group I.
(a)
R-1 — Residential occupancies where the occupants are
primarily transient in nature.
(b)
R-2 — Residential occupancies containing more than two
dwelling units where occupants are primarily permanent in nature.
(c)
R-3 — Residential occupancies where the occupants are
primarily permanent in nature and not classified R-1, R-2 or I, and
where buildings do not contain more than two dwelling units or adult
and child care facilities, that provide accommodations for five or
fewer persons of any age for less than 24 hours.
(d)
R-4 — Residential occupancies shall include buildings
arranged for occupancy as residential care/assisted living facilities
including five but not more than 16 occupants, excluding staff.
ROOF SPACES
Buildings with combustible roofs shall have all roof spaces
subdivided every 3,000 square feet by one-hour rated partitions unless
protected by an approved automatic fire sprinkler system. All openings
must have a minimum of a one-hour rated self-closing door.
ROOMING HOUSE
Any building, which has a room or rooms for sleeping, without
permanent provisions for cooking. Rooming house rooms do not include
any room in a one- or two-family dwelling.
ROUGH INSPECTION
Visual observation from the floor and/or ground level of
any system and/or component thereof required by this code prior to
being concealed in any way by any means.
ROW HOUSE
A place of abode arranged to accommodate three or more attached
side-by-side or back-to-back living units.
SHALL
Indicates a mandatory requirement.
SHOULD
Indicates a recommendation or that which is advised but not
required.
SPACING
A horizontally measured dimension relating to the allowable
coverage limits of fire detectors, automatic sprinkler systems, and
fire alarm visual notification devices.
STANDARD
A document, the main text of which contains only mandatory
requirements using the word "shall" to indicate mandatory requirements
and which is in a form generally suitable for reference by another
standard or code for adoption into law.
STORAGE GROUP S
Group S occupancy includes, among others, the use of a building
or structure, or portion thereof, for storage that is not classed
as hazardous group H.
(a)
S-1 (moderate-hazard storage) — Buildings occupied for
storage uses which are not classified as S-2.
(b)
S-2 (low-hazard storage) — Building used for storage of
noncombustible material such as products on wood pallets or in paper
cartons with or without single thickness divisions or in paper wrappings.
Such products may have negligible amount of plastic trim such as knobs,
handles, or film wrapping.
STORY
That portion of a building included between the upper surface
of a floor and the upper surface of the floor or roof next above.
To determine the number of stories in a building, all floors will
be counted whether they are above grade or below grade, including
basements, sub-basements, and ground floors, but not including penthouses
or mezzanines less than one-third of a story.
THROUGHOUT
For the purpose of this code, throughout shall mean the following:
(a)
Throughout for automatic fire sprinkler systems means providing
fire sprinkler protection in all areas of a structure as required
by NFPA 13.
(b)
Throughout for automatic fire alarm systems means installing
detection, audible and visual notification devices in all areas of
the protected premises installed in accordance with NFPA 72.
(c)
Throughout for manual fire alarm systems means installing audible
and visual notification devices in all areas of the protected premises
installed in accordance with NFPA 72.
WATER FLOW TEST
A test of an available water supply that indicates the quantity
of water flowing out of a specific orifice, at a specific pressure,
at a specific point in time.
WELFARE
Includes comfort, decency and moral well-being.
[Ord. No. 829, § 1, 7-20-2010; Ord. No. 896, § I, 4-21-2015]
The Village of Mukwonago adopts the most current edition of
the following:
NFPA 1 Uniform Fire Code (applies only to the use, maintenance,
operation and testing)
NFPA 10 Standard for Portable Fire Extinguishers
NFPA 11 Standard for Low-, Medium-, and High-Expansion Foam
NFPA 12 Standard on Carbon Dioxide Extinguishing Systems
NFPA 13 Standard for the Installation of Sprinkler Systems
NFPA 13D Sprinkler Systems in One- and Two-Family Dwellings
and Manufactured Homes
NFPA 13R Sprinkler Systems in Residential Occupancies up to
and including Four Stories in Height
NFPA 14 Standard for the Installation of Standpipes, Private
Hydrant, and Hose Systems
NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection
NFPA 16 Standard for the Installation of Foam-Water Sprinkler
and Foam-Water Spray Systems
NFPA 17 Standard for Dry Chemical Extinguishing Systems
NFPA 17A Standard for Wet Chemical Extinguishing Systems
NFPA 20 Standard for the Installation of Stationary Pumps for
Fire Protection
NFPA 22 Standard for Water Tanks for Private Fire Protection
NFPA 24 Standard for the Installation of Private Fire Service
Mains and their Appurtenances
NFPA 25 Standard for the Inspection, Testing, and Maintenance
of Water-Based Fire Protection Systems
NFPA 30 Flammable and Combustible Liquids Code
NFPA 30A Code for Motor Fuel Dispensing Facilities and Repair
Garage's
NFPA 30B Code for the Manufacture and Storage of Aerosol Products
NFPA 33 Standard for Spray Application Using Flammable or Combustible
Materials
NFPA 34 Standard for Standard Dipping and Coating Processes
Using Flammable or Combustible Liquids
NFPA 35 Standard for the Manufacture of Organic Coatings
NFPA 36 Standard for Solvent Extraction Plants
NFPA 37 Standard for the Installation and Use of Stationary
Combustion Engines and Gas Turbines
NFPA 40 Standard for the Storage and Handling of Cellulose Nitrate
Film
NFPA 42 Code for the Storage of Pyroxylin Plastic
NFPA 45 Standard on Fire Protection for Laboratories Using Chemicals
NFPA 51 Standard for the Design and Installation of Oxygen-Fuel
Gas Systems for Welding, Cutting, and Allied Processes
NFPA 51A Standard for Acetylene Cylinder Charging Plants
NFPA 54 National Fuel Gas Code
NFPA 55 Standard for the Storage, Use, and Handling of Compressed
Gases and Cryogenic Fluids in Portable and Stationary Containers,
Cylinders, and Tanks
NFPA 58 Liquefied Petroleum Gas Code
NFPA 59 Utility LP-Gas Plant Code
NFPA 59A Standard for the Production, Storage, and Handling
of Liquefied Natural Gas (LNG)
NFPA 61 Standard for the Prevention of Fires and Dust Explosions
in Agricultural and Food Processing Facilities
NFPA 68 Guide for Venting of Deflagrations
NFPA 69 Standard on Explosion Prevention Systems
NFPA 70 National Electrical Code™
NFPA 72 National Fire Alarm Code
NFPA 75 Standard for the Protection of Information Technology
Equipment
NFPA 76 Standard for the Fire Protection of Telecommunications
Facilities
NFPA 80 Standard for Fire Doors and Fire Windows
NFPA 82 Standard on Incinerators and Waste and Linen Handling
Systems and Equipment
NFPA 85 Boiler and Combustion Systems Hazards Code
NFPA 86 Standard for Ovens and Furnaces
NFPA 88A Standard for Parking Structures
NFPA 91 Standard for Exhaust Systems for Air Conveying of Vapors,
Gases, Mists, and Noncombustible Particulate Solids
NFPA 92B Standard for Smoke Management Systems in Malls, Atria,
and Large Spaces
NFPA 96 Standard for Ventilation Control and Fire Protection
of Commercial Cooking Operations
NFPA 99B Standard for Hypobaric Facilities
NFPA 99C Standard on Gas and Vacuum Systems
NFPA 101 Life Safety Code™
NFPA 101B Code for Means of Egress for Buildings and Structures
NFPA 102 Standard for Grandstands, Folding and Telescopic Seating,
Tents, and Membrane Structures
NFPA 105 Standard for the Installation of Smoke Door Assemblies
NFPA 110 Standard for Emergency and Standby Power Systems
NFPA 111 Standard on Stored Electrical Energy Emergency and
Standby Power Systems
NFPA 115 Standard on Laser Fire Protection
NFPA 160 Standard for the Use of Flame Effects Before an Audience
NFPA 170 Standard for Fire Safety and Emergency Symbols
NFPA 204 Standard for Smoke and Heat Venting
NFPA 214 Standard on Water-Cooling Towers
NFPA 221 Standard for High Challenge Fire Walls, Fire Walls,
and Fire Barrier Walls
NFPA 230 Standard for Fire Protection of Storage
NFPA 232 Standard for the Protection of Records
NFPA 241 Standard for Safeguarding Construction, Alteration,
and Demolition Operations
NFPA 291 Practice for Fire Flow Testing and Marking of Hydrants
NFPA 303 Fire Protection Standards for Marine and Boatyards
NFPA 307 Standards for the construction and Fire Protection
for Marine Terminals, Piers, and Wharves
NFPA 318 Standard for the Protection of Semiconductor Fabrication
Facilities
NFPA 418 Standard for Heliports
NFPA 430 Code for the Storage of Liquid and Solid Oxidizers
NFPA 432 Code for the Storage of Organic Peroxide Formulations
NFPA 434 Code for the Storage of Pesticides
NFPA 484 Standard for Combustible Metals
NFPA 490 Code for the Storage of Ammonium Nitrate
NFPA 495 Explosive Materials Code
NFPA 499 Recommended Practice for the Classification of Combustible
Dusts and of Hazardous (Classified) Locations for Electrical Installations
in Chemical Process Areas
NFPA 560 Standard for the Storage, Handling, and Use of Ethylene
Oxide for Sterilization and Fumigation
NFPA 654 Standard for the Prevention of Fire and Dust Explosions
from the Manufacturing, Processing, and Handling of Combustible Particulate
Solids
NFPA 655 Standard for Prevention of Sulfur Fires and Explosions
NFPA 664 Standard for the Prevention of Fires and Explosions
in Wood Processing and Woodworking Facilities
NFPA 704 Standard System for the Identification of the Hazards
of Materials for Emergency Response
NFPA 720 Standard for the Installation of Carbon Monoxide (CO)
Warning Equipment in Dwelling Units
NFPA 750 Standard on Water Mist Fire Protection Systems
NFPA 780 Standard for the Installation of Lightning Protection
Systems
NFPA 801 Standard for Fire Protection for Facilities Handling
Radioactive Materials
NFPA 804 Standard for Fire Protection for Advanced Light Water
Reactor Electric Generating Plants
NFPA 850 Recommended Practice for Fire Protection for Electric
Generating Plants
NFPA 853 Standard for the Installation of Stationary Fuel Cell
Power Systems
NFPA 1123 Code for Fireworks Display
NFPA 1124 Code for the Manufacture, Transportation, Storage
and Retail Sales of Fireworks and Pyrotechnic Articles
NFPA 1125 Code for the Manufacture of Model Rocket and High
Power Rocket Motors
NFPA 1126 Standard for the Use of Pyrotechnics before a Proximate
Audience
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems
NFPA 2010 Standard for Fixed Aerosol Fire Extinguishing Systems
[Ord. No. 829, § 1, 7-20-2010; Ord. No. 896, § I, 4-21-2015]
The code shall not be construed to affect the responsibility
of any persons owning, operating, or installing equipment, for injury
to persons or damage to property caused by any defect therein, nor
shall the municipality, any person, firm, company or agent(s) for
the municipality be held as assuming such liability by reason of any
inspection or re-inspection authorized herein or the permit issued
herein provided or by reason of the disapproval or approval of any
equipment and/or system authorized herein.