[R.O. 1996 § 500.010; CC 1968 § 5-1; Ord. No. 530 § 1, 3-1-1971; Ord. No. 607 § 1, 4-17-1972; Ord. No. 860 § 1, 10-18-1976; Ord. No. 1410 § 1, 6-3-1985; Ord. No. 1713 § 1, 4-4-1988; Ord. No. 2255 § 1, 9-21-1992; Ord. No. 2428 §§ 1 — 2, 3-7-1994; Ord. No. 3079 §§ 1 — 2, 9-21-1998; Ord. No. 3487 § 1, 7-15-2002; Ord. No. 3557 § 1, 4-7-2003; Ord. No. 3797 § 1, 7-7-2004; Ord. No. 4028 § 1, 2-5-2007; Ord. No. 4396 § 1, 7-2-2012; Ord. No. 5021, 7-19-2021]
A.
There is hereby adopted by the City Council of the City of Blue Springs, Missouri; the following Uniform Codes, subject to the exceptions set forth herein and in Section 500.020, for the purpose of prescribing, regulating and governing the erection, construction, enlargement, alteration, repair, moving, removal, demolition, conversion, occupancy, equipment, use, height, area, maintenance and all matters relating thereto for the prevention of conditions hazardous to life and property, and for the common welfare, protection and benefit of the residents of the City.
1.
International Building Code 2018, with a publication date of August 2017.
a.
Section 105.2 Work exempt from permit delete item number 9 and include new item 9 as follows:
9. | Prefabricated swimming pools accessory to a Group R-3 occupancy that are less than twenty-four (24) inches (610mm) deep." |
b.
CHAPTER 13, ENERGY EFFICIENCY, SECTION 1301, GENERAL, [E] 1301.1 Scope and [E] 1301.1.1 Criteria shall be amended to read as follows:
"[E] 1301.1 Scope. This Chapter governs the design and construction of buildings for energy efficiency. |
[E] 1301.1.1 Criteria. Buildings may be designed and constructed in accordance with the International Energy Conservation Code." |
2.
International Fire Code 2018, with a publication date of August 2017, except for the following modifications.
a.
Section 503.1.1 Buildings And Facilities. Approved fire apparatus shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this Section and shall extend to within one hundred fifty (150) feet (45,720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. The approved apparatus access road will be designed to withstand the weight of a ninety thousand pounds (90,000) pound vehicle.
b.
Section 507.3 Fire-Flow. Fire-flow requirements for buildings or portions of buildings and facilities shall be determined by using the current adopted IFC code Appendix C.
c.
Section 507.5.1.2. Four (4) buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be six hundred (600) feet (183 m). The minimum number of hydrants shall be determined by using the current adopted IFC code Appendix C. Number of hydrants can be reduced by the Fire Code Official if deemed appropriate. Example: Building with automatic extinguishing system.
d.
Section 510.1.2 Emergency Responder Radio Coverage.
Any building meeting the following criteria will produce signal strength test as described in IFC 510: | |
1. | Any structure with an overall square footage of twelve thousand (12,000) square feet. |
2. | Any structure with a height of thirty (30) feet or more above grade level. |
3. | Any structure with a level below grade. |
4. | Any structure determined to be of concern of proper radio communication, Central Jackson County Fire Protection District can request a signal strength study to be completed. |
If a signal strength test is required it shall not be performed until all walls, roof, windows with glass, doors, and operational equipment has been completed and in place. | |
A field test will be performed by Central Jackson County Fire Protection District personnel at the time of Certificate of Occupancy utilizing Central Jackson County Fire Protection District portable two-way communications. If that test fails, a Temporary Certificate of Occupancy may be signed with an obligation to enhance the emergency radio communications coverage within six (6) months. | |
All other requirements for Emergency Responder Radio Coverage will follow IFC 510, NFPA 72, NFPA 1221, and UL 2425 as written in the current adopted code. | |
All BDA installations will include the following: | |
Cover 700 and 800 megahertz | |
Install an annunciator | |
Install a document box that contains installation plans, and pre- and post-survey test results | |
A field test will be performed by Central Jackson County Fire Protection District personnel at the time of Certificate of Occupancy utilizing Central Jackson County Fire Protection District portable two-way communications. If that test fails, a Temporary Certificate of Occupancy may be signed with an obligation to enhance the emergency radio communications coverage within six (6) months. | |
All other requirements for Emergency Responder Radio Coverage will follow IFC 510 and NFPA 72 as written in the current adopted code. | |
e.
Section 901.6.3.2 Records.
Contractors who perform inspection, testing and/or maintenance service on fire and life safety systems must submit those records of service to the Fire Code Official.
Records of all system inspections, tests, and maintenance (ITM) of the following must be submitted electronically through Central Jackson County Fire Protection District or the contractor it chooses to collect and maintain ITM reports and track compliancy of the Fire Code as it pertains to the following and the Compliance Engine Software used by Central Jackson County Fire Protection District or its contractor used to collect and maintain ITM reports and track compliancy of the Fire Code as it pertains to the following:
Automatic Sprinkler Systems |
Special Suppression Systems |
Fire Pumps |
Standpipes |
Paint Booths |
Hood and Ducts |
Cleaning of Hood and Ducts |
Commercial Fire Alarms |
Fire doors |
Emergency Responder Radio Coverage equipment |
f.
IFC Section 903.1 General. Automatic sprinkler systems shall comply with this Section. Any building requiring an automatic sprinkler system as required by IFC 903, which meets the following criteria, must install a separate water flow switch that is addressable through the fire alarm system.
1.
Any building that has an automatic sprinkler system with multiple addresses or suites that is greater than two (2).
2.
Any building requiring an automatic sprinkler system as required by IFC 903 shall have a permanent, maintained water source within one hundred (100) feet of the Fire Department connection.
g.
Section 903.2 Where Required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12. Any building requiring an automatic sprinkler system as required by IFC 903, which meets the following criteria, must install a separate water flow switch that is addressable through the fire alarm system.
1.
Any building that has an automatic sprinkler system with multiple addresses or suites that is greater than two (2).
2.
Any building requiring an automatic sprinkler system as required by IFC 903 shall have a permanent, maintained water source within one hundred (100) feet of the Fire Department connection.
h.
Section 903.4.2 Alarms. An approved audible and visual device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler systems shall actuate the building fire alarm system.
i.
Section 903.4.2.1 Notification Devices. Where an automatic extinguishing system is installed in a building, audible and visible notification appliances shall be installed throughout the building as follows:
1.
Audible notification appliances shall be installed so as to be audible at fifteen (15) dBa above average sound pressure level throughout the building.
2.
Visible notification appliances shall be installed in all public and common use areas, restrooms and corridors in accordance with the spacing requirements of NFPA 72.
3.
Visible notification devices can be eliminated in normally unoccupied portions of buildings where permitted by the Code Official.
Exception: The requirements of this Section do not apply to Group R-3 occupancies. |
j.
Section 904.5.1 System Test. Systems shall be inspected and tested for proper operation following the recommended schedule shown in NFPA 96. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed, and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer.
k.
Section 907.6 Installation And Monitoring. A fire alarm system shall be installed and monitored in accordance with Sections 907.6.1 through 907.6.6.2 and NFPA 72. Fire alarm systems required by the International Fire Code or by the International Building Code shall be monitored by a listed central station as defined in NFPA 72. A certificate or placard shall be issued by a recognizing organization that has listed the prime contractor for the newly installed fire alarm systems in commercial occupancies in accordance with NFPA 72. This regulation shall apply to all fire alarm systems that are newly installed in commercial occupancies that reside within Central Jackson County Fire Protection District boundaries on or after January 1, 2021. Any existing fire alarm system in a commercial occupancy wherein the fire alarm control panel and/or alarm system components are to be replaced shall be considered newly installed for the purpose of this Section. Also, where there is reasonable cause due to non-compliance or faulty conditions, the Fire Code Official may require an existing fire alarm system meet the same requirements as a newly installed system. Central station service in full compliance with the 2016 Edition of NFPA 72, Chapter 26, shall be maintained at the protected property, so long as the requirement for the fire alarm exists.
3.
ICC Electrical Code (Administrative Provisions) 2006, with a publication date of May 2009.
4.
National Electrical Code NFPA 70, 2017 Edition.
5.
International Plumbing Code 2018, with a publication date of August 2017, except for the following modification to Section 607.2 of the International Plumbing Code 2012:
a.
Section 607.2 Hot Or Tempered Water Supply To Fixtures. The developed length of hot or tempered water piping, from the source of hot water to the fixtures that require hot or tempered water, shall not exceed one hundred (100) feet (15,240 mm). Recirculating system piping and heat-traced piping shall be considered to be sources of hot or tempered water.
b.
Section 607.2.1 Delete.
6.
International Mechanical Code 2018, with a publication date of August 2017.
7.
International Fuel Gas Code 2018 with a publication date of August 2017.
8.
International Residential Code 2018 (for One- and Two- Family Dwellings) with a publication date of August 2017, except for the following modifications to the International Residential Code 2018:
a.
Table R301.2(1) Climatic and Geographic Design Criteria add the following items to this table.
Ground Snow Load | 20 |
Wind Speed (mph) | 115 |
Seismic Design Category | A |
Weathering | Severe |
Frost Line Depth | 36" |
Termite | M-H |
Winter Design Temp | 6° F. |
Ice Barrier Underlayment Required | Yes |
Air Freezing Index | 927 |
Mean Annual Temp | 55° F. |
b.
Section R303.7. Light Activation shall have added a new exception number 2; which shall read as follows:
"2. | Sunken or raised area with steps and only one (1) access direction to the space; lighting may be activated at only one (1) point in the access area to the steps and space." |
c.
Part IV — Energy Conservation, CHAPTER 11 [RE], ENERGY, EFFICIENCY, SECTION N1101, GENERAL, N1101.1 Scope is amended to read:
"N1101.1 Scope. This Chapter is adopted for reference purpose only, and compliance with this Chapter is not required but can be voluntarily partially or completely followed.
Note: The text of the following Sections N1101.2 through N1105 is extracted from the 2018 Edition of the International Energy Conservation Code — Residential Provisions and has been editorially revised to conform to the scope and application of this code. The Section numbers appearing in parenthesis after each Section number are the Section numbers of the corresponding text in the International Energy Conservation Code — Residential Provisions."
d.
Part IV — Energy Conservation, CHAPTER 11 [RE], ENERGY, EFFICIENCY, SECTION N1101, GENERAL, N1101.2 (R101.3) Intent is amended to read:
"N1101.2 (R101.3) Intent. This Chapter may regulate the design and construction of buildings for the effective use and conservation of energy over the useful life of each building. This Chapter is intended to provide flexibility to permit the use of innovative approaches and techniques to achieve this objective. This Chapter is not intended to abridge safety, health or environmental requirements contained in other applicable codes or ordinances."
e.
R317.1.1 Delete.
f.
R318.1.2 Delete.
g.
E3901.9 Basements, Garages And Accessory Buildings. Not less than one (1) receptacle outlet, in addition to any provided for specific equipment, shall be installed in each separate unfinished portion of a basement; in a vehicle bay not more than five and five-tenths (5.5) feet (1,676 mm) above the floor in attached garages; in a vehicle bay not more than five and five-tenths (5.5) feet (1,676 mm) above the floor in detached garages that are provided with electric power and in accessory buildings that are provided with electric power.
h.
E3902.2.1 Garage And Accessory Building Receptacles. 125-volt single-phase, 15- or 20-ampere receptacles installed in garages and grade-level portions of unfinished accessory buildings used for storage or work areas shall have ground-fault circuit-interrupter protection for personnel. With the exception of electrical receptacles dedicated to serve refrigerators, freezers, alarm, garage door openers, sump pumps, irrigation controls, to be non-GFCI.
i.
E3902.5 Exceptions: A receptacle supplying only a permanently installed fire alarm, burglar alarm, or sump pump system. Receptacles installed in accordance with this exception shall not be considered as meeting the requirement of Section E3901.9.
j.
E3902.10 Delete.
9.
Standard For Accessible And Usable Buildings And Facilities, ICC A117.1-2009.
10.
International Existing Building Code 2018, with a publication date of August 2017.
11.
2018 International Energy Conservation Code, with publication date of June 2018 is adopted for reference purposes only, and compliance with that code is not required but can be voluntarily partially or completely followed.