The 2017 [2020] National Electrical Code is adopted with the
following limitations and exceptions:
(1) Aluminum
conductors or copper-clad aluminum conductors are not permitted to
be used except for service drop or service lateral.
(2) No
person shall hereafter install for residential purposes any service
entrance conductors with a rating of less than one hundred (100) amps.
(3) No
person shall install any electrical wiring of a smaller size wire
than no. 12.
(4) No
person shall install any electrical wiring on the outside surface
of any building within the city, including a private residence, without
placing such wiring in an approved and properly grounded metallic
conduit. P.V.C. may be used only on temporary power pole installations
on the load side.
(5) No
person shall install any service entrance switches or any service
equipment switches or any service equipment within a bathroom, heating
closet, cabinets or kitchens.
(6) No
person shall leave any unused electrical equipment within or upon
public or private buildings or premises, if, in the opinion of the
electrical inspector, the same constitutes a hazard or danger to life
or property, including unused electric range installations and unused
contractor meter loops.
(7) No
person shall cover up any electrical conduit or wiring in the process
of construction without inspection by an electrical inspector of the
city.
(8) All
service entrance conductors from the meter base to the panel shall
be installed in either of the following three (3) ways:
(A) The disconnect shall be located back of meter or under the meter
with a metallic conduit nipple.
(B) If the service entrance conductors are placed in metallic conduit
from the meter socket to the main panel, no main disconnect shall
be required at the meter, except in apartment complexes.
(C) A service disconnect shall be provided at the meter except in back
to back installations.
(9) The
minimum size of service disconnects shall be sixty (60) amps.
(A) Service panel breakers: All service panel breakers, known as piggyback,
tandems, twins, thins, or any other of this type disconnect above
thirty-amp capacity, are hereby prohibited on new installations.
(10) Section 110-14(b) of the NEC is hereby amended; electricians tape
alone will not be permitted as the sole insulation equivalent on splices
and joints.
(11) All electrical circuits shall have an equipment grounding conductor.
(12) All condensing units of air-conditioning and refrigeration shall
be connected to the final switch or disconnect with liquid-tight flexible
conduit approved for outside use.
(Ordinance 6340 adopted 12/7/20)
All electrical wiring for light, heat, power or other purposes
installed in the city, as respectively described in the following
subsections hereof, shall in all cases be contained and encased in
approved conduit:
(1) All
electrical wiring in buildings situated in the inner fire limits of
the city.
(2) All
commercial buildings, industrial buildings, educational and church
buildings.
(3) All
electrical wiring through metal studs.
(4) All
service entrance installations from entrance to meter sockets shall
be in metallic conduit. All meter sockets shall be grounded in an
approved manner. All meter sockets shall be located in accordance
with requirements of local power companies, and shall be located four
(4) to six (6) feet from the center of meter to grade level, except
meters located on pad transformers.
(5) All
supply wiring for electrical and neon signs when attached to a building.
(6) All
wiring installed underground, under buildings or in concrete slabs
or other masonry.
(7) Armored
cable, known to the electrical trade as BX or AC cable, will not be
approved for use as metallic conduit.
(Ordinance 5341 adopted 10/3/05)
Not more than ten (10) outlets shall be installed on any one
(1) circuit in a residence. Commercial buildings in the fire zone
shall have not more than six (6) wall outlets or six (6) fluorescent
light fixtures, but not more than four (4) bulb-type light fixtures,
per circuit.
(Ordinance 5341 adopted 10/3/05)
(a) Overhead
service/raceways shall be in approved metallic conduit. Underground
service/raceways between meter base and ground must be in approved
schedule 80 PVC conduit. No residential service conductor shall be
smaller than no. 4 copper or no. 2 aluminum. Except by special permission
of an electrical inspector, service entrance shall not be less than
twelve and one-half (12-1/2) feet or more than twenty-five (25) feet
from the ground level.
(b) Where
one (1) service is installed to supply several installations or customers
within the same building, the main service panel and disconnect must
be accessible at all times to each of the occupants or customers supplied
from such service.
(c) Whenever
the service to any commercial building is disconnected, the service
shall not again be connected to such building until the electrical
system has been approved by an electrical inspector and conforms to
the provisions of this article, and the metering requirements of the
local electrical power company. Any building regardless of occupancy,
not having the service conductors in approved metallic conduit, once
disconnected, shall not again be connected to the source of supply
until service and meter loop shall have been replaced and made to
conform to the standards of this article, and the metering requirements
of the local electrical power company. A disconnect shall be provided
at the meter except in back-to-back installations.
(Ordinance 5713 adopted 8/15/11)
(a) All
classes of electrical signs, whether of the gas tube, sign receptacle
or reflector type, including gas tube window signs and outside building
outlining shall be considered electric signs within the meaning of
this article. Portable inside displays or small signs using self-contained
transformers with current consumption not to exceed two hundred (200)
watts may be connected by attachment plug to present circuits providing
all other requirements of this article are complied with.
(b) All
signs must be on separate circuits in conduit from the distributing
panel and not more than one thousand three hundred twenty (1,320)
watts will be allowed on each circuit. All signs except portable signs
must be grounded directly to the conduit service.
(c) When
an electric sign is to be hung over the sidewalk there must be a clearance
of nine (9) feet from the sidewalk to the lowest point of the sign
and no sign shall extend to within two (2) feet of the curbline of
sidewalk, except by special permission of the director of the department
or his representative.
(Ordinance 5341 adopted 10/3/05)