The National Electrical Code, 2020 edition, and all annexes thereto, as published by the National Fire Protection Association, Inc. is hereby adopted and made a part of this chapter, except as amended in section 6.02.462.
(Ordinance 2022-22 adopted 9/20/22)
The National Electrical Code, 2020 edition as adopted in section 6.02.461 is hereby amended as follows:
(1) 
Article 90.4 is hereby deleted and replaced with the following:
This Code is intended to be suitable for mandatory application by governmental bodies that exercise legal jurisdiction over electrical installations, including signaling and communications systems, and for use by insurance inspectors. The authority having jurisdiction for enforcement of the Code has the responsibility for making interpretations of the rules, for deciding on the approval of equipment and materials, and for granting the special permission contemplated in a number of the rules.
By special permission, the authority having jurisdiction may waive specific requirements in this Code or permit alternative methods where it is assured that equivalent objectives can be achieved by establishing and maintaining effective safety.
This Code may require new products, constructions, or materials that may not yet be available at the time the Code is adopted. In such event, the authority having jurisdiction may permit the use of the products, constructions, or materials that comply with the most recent previous edition of this Code adopted by the jurisdiction.
Permits; licensing.
(a) 
A person applying for an electrical permit shall be:
(1) 
A State of Texas licensed master electrician; or
(2) 
Exempt under state law from the licensing requirement.
(b) 
If applicable, a state licensed master electrician shall register with the City in accordance with the city’s registration policy and shall show proof of the license before any work is performed within the City.
(c) 
If a building owner is claiming an exemption under state law because they are planning to do the work themselves, then the owner shall provide proof to the building official stating they own the building as a homestead.
(d) 
The fees for work shall be as indicated in the schedule of fees adopted by the city council and attached to the Code of Ordinances as appendix A.
(e) 
No portion of any fee collected under this article shall be returned after a permit has been issued.
(f) 
Certificate of Occupancy
Permanent power shall not be released until a certificate of occupancy or temporary certificate of occupancy has been issued under the conditions as set forth in the City’s Unified Development Code.
Violations of State and Local Laws will be subject to the established fines of the State as outlined in Chapter 1305, Subchapter G, of the Texas Occupations Code (Texas Electrical Safety and Licensing Act).
(2) 
The exceptions set forth in 230.41 are hereby deleted.
(3) 
Section 230.43 is hereby deleted and replaced with the following:
230.43 Wiring methods for 600 volts, nominal, or less. Service-entrance conductors shall be installed in accordance with the applicable requirements of this code covering the type of wiring method used and shall be limited to the following methods:
(a) 
Rigid Metallic Conduit (RMC)
(b) 
Intermediate Metal Conduit (IMC)
(c) 
Electrical Metallic Tubing (EMT), or
(d) 
Rigid Nonmetallic Conduit (RNC) will be approved.
A service mast supporting the service drop must be a minimum of 2" diameter and shall be either rigid metallic conduit (RMC) or intermediate metal conduit (IMC). No couplings are to be installed above the roofline. The mast must penetrate a minimum of 18" above the high side of the roof deck. Any mast over 3' in length, measured from the high side of the roof deck, must be properly guyed to relieve the strain of the service drop.
(4) 
Section 230.70(A)(1) is hereby deleted and replaced with the following:
230.70(A)(1) Readily accessible location. The service disconnecting means shall be installed at a readily accessible location outside of a building or structure.
Exception: Services disconnecting means over 1200 amps shall be located a maximum of 25 ft. travel distance from the exterior entrance inside a commercial building. Disconnecting means shall be always accessible to the exterior of the building and shall not be located above the first floor of a multi-level building.
(5) 
Section 240.4(D) is hereby deleted and replaced with the following:
(d) 
Small Conductors.
Unless specifically permitted in 240.4 (E) or (G), the overcurrent protection shall not exceed that required by (D)(1) through (D)(7) after any correction factors for ambient temperature and number of conductors have been applied.
(1) 
18 AWG Copper.
7 amperes, provided all the following conditions are met:
(1) 
Continuous loads do not exceed 5.6 amperes.
(2) 
overcurrent protection is provided by one of the following:
a. 
Branch-circuit-rated circuit breakers listed and marked for use with 18 AWG copper wire .
b. 
Branch rated fuses listed and marked for use with 18 AWG copper wire.
c. 
Class CC, Class J, or Class T fuses.
(2) 
16 AWG Copper.
10 amperes, provides all the following conditions are met:
(1) 
Continuous loads do not exceed 8 amperes.
(2) 
Overcurrent protection is provided by one of the following:
a. 
Branch-circuit-rated circuit breakers listed and marked for use with 16 AWG copper wire.
b. 
Branch rated fuses listed and marked for use with 16 AWG copper wire.
c. 
Class CC, Class J, or Class T fuses.
(3) 
14 AWG Copper.
15 amperes.
(4) 
12 AWG copper.
20 amperes.
(5) 
10 AWG copper.
30 amperes.
(6) 
Section 320.108 is hereby deleted and replaced with the following:
320.108 Equipment grounding conductor. Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor. In addition, only type AC cable containing an insulated grounding conductor is authorized.
(7) 
Section 408.36, Exception 1, is hereby deleted and replaced with the following:
408.36 Overcurrent protection.
...
Exception No. 1: A main circuit breaker shall be required in all panelboards used as service equipment. This overcurrent protective device shall be located within or adjacent to the panelboard.
(Ordinance 2022-22 adopted 9/20/22)