A certain document, one (1) copy of which is on file in the office of the city secretary, being marked and designated as the International Residential Code, 2018 edition, as published by the International Code Council, be and is hereby adopted as the residential code of the city for regulating and governing the construction, alteration, movement, enlargement, replacement, repair, equipment, location, removal and demolition of detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories in height with separate means of egress as herein provided; providing for the issuance of permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions and terms of said residential code on file in the office of the city secretary are hereby referred to, adopted, and made a part hereof, as if fully set out in this division, with the additions, insertions, deletions and changes, if any, prescribed in section
4.02.052 of this division.
(Ordinance 2022-0322-01 adopted 3/22/22)
The following sections are hereby revised:
(1) Table
R301.2(1) of the International Residential Code, 2018 edition, adopted
by the city, is hereby amended to read as follows:
(2) Section
R303.4.1 of the International Residential Code, 2018 edition, adopted
by the city, is hereby added to read as follows:
R303.4.1 Laundry mechanical ventilation. Mechanical ventilation will be provided in laundry areas in accordance
with Table M1505.4.4 Bathrooms-Toilet Rooms.
(3) Section
R403.1.1 of the International Residential Code, 2018 edition, adopted
by the city, is hereby amended to read as follows:
R403.1.1 Minimum size. The minimum width,
W, and the minimum thickness, T, for concrete footings shall be in
accordance with Table R401.1(1) through R401.1(3) and Figure R403.1(1)
or 403.1.3, as applicable, but not less than 12 inches (305 mm) in
width, and 12 inches (305 mm) in depth….
(4) Section
R313.2 of the International Residential Code, 2018 edition, adopted
by the city is hereby amended to read as follows:
R313.2 One- and Two-family dwellings automatic sprinkler
systems. Section R313.2 of the International Residential
Code, 2018 edition, adopted by the city, is hereby deleted in its
entirety.
(5) Section
R602.3.1 of the International Residential Code, 2018 edition, adopted
by the city, is hereby amended to read as follows:
R602.3.1 Stud Size, height and spacing. The size, height and spacing of studs shall be in accordance with
Table R602.3(5). All wet walls, those containing DWV plumbing and
mechanical exhaust, shall be required to be 2 x 6 nominal lumber.
(6) Section
M1307.8 of the International Residential Code, 2018 edition, adopted
by the city, is hereby added to read as follows:
M1307.8 Water deflection. Outdoor unit
location must be far enough away from any structure to prevent excess
roof runoff water from pouring directly on the unit or protected in
a manner acceptable to the Building Official.
(7) Section
R1004 of the International Residential Code, 2018 edition, adopted
by the city, is hereby amended to add the following Section:
R1004.6 Factory built fireplace air spaces and chases. No electrical, mechanical, or plumbing, except for the combustion
air vent and gas line feed associated with the firebox, shall intrude
into the airspace enclosing the firebox or any chase for chimney components
associated with the fireplace.
(8) Section
G2517.4.1 (406.4.1) of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
G2417.4.1(406.4.1) Test pressure. The
test pressure to be used shall be not less than 10 psig irrespective
of design pressure. Where the test pressure exceeds 125 psig (862
kPa gauge), the test pressure shall not exceed a value that produces
a hoop stress in the piping greater than 50 percent of the specified
minimum yield strength of the pipe.
(9) Section
P2503.5.1 of the International Residential Code, 2018 edition, adopted
by the city, is hereby amended to read as follows:
P2503.5.1 Rough Plumbing. DWV systems
shall be tested on completion of the rough piping, and top out piping
installation by water or air with no evidence of leakage. Either test
shall be applied to the drainage system in its entirety or in sections
after rough piping and top out piping has been installed, as follows:
1. Water test.
Each section shall be filled with water
to a point not less than 5 feet above the highest fitting connection
in that section, or to the highest point in the completed system.
Water shall be held in the section under test for a period of 15 minutes.
The system shall prove leak free by visual inspection.
2. Air test.
The portion under test shall be maintained
at a gauge pressure of 5 pounds per square inch (psi) using a 0-15
psi air test gauge assembly with 1/10th lb. increments. This pressure
shall be held without introduction of additional air for a period
of 15 minutes.
(10) Section P2602.1 of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
P2602.1 General. … A building
having plumbing fixtures installed and intended for human habitation,
occupancy or use on the premises abutting on a street, alley or easement
in which there is a public sewer shall have a separate connection
to the sewer via individual building sewer. Where public sewer is
not available …
(11) Section P2706.1.2 of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
P2706.1.2 Standpipes. Standpipes shall
extend not less than 18 inches (457mm) and not greater than 42 inches
(1067mm) above their trap weir. Traps shall be installed not less
than 6 inches and not greater than 18 inches above grade.
(12) Section P2903.10 of the International Residential Code, 2018 edition,
adopted by the city, is hereby deleted in its entirety.
(13) Section P3008.1 of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
P3008.1 General. Fixtures on the first
floor of a foundation where the foundation is located at or below
the flood level rim of the next upstream manhole cover of the public
sewer shall be protected from backflow of sewage by installing an
approved backwater valve. Fixtures located on elevated floors of a
building above the flood level rim of the next upstream manhole shall
not discharge through the backwater valve. Backwater valves shall
be provided with access.
(14) Section P3103.1.3 of the International Residential Code, 2018 edition,
adopted by the city, is hereby deleted in its entirety.
(15) Section P3104.1 of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
P3104.1 Connection. All individual branch
and circuit vents shall connect to a vent stack, stack vent or extend
to the open air.
Exception: Individual, branch and circuit vents shall be permitted
to terminate to an air admittance valve upon approval by the Building
Official.
(16) Section P3201.6 of the International Residential Code, 2018 edition,
adopted by the city, is hereby amended to read as follows:
P3201.6 Number of Fixtures per Trap. Each
plumbing fixture shall be separately trapped by a water seal trap
placed as close as possible to the fixture outlet. The vertical distance
from the fixture outlet to the trap weir shall not exceed 24 inches.
The height of a clothes washer standpipe above a trap shall conform
to Section P2706.1.2. Fixtures shall not be double trapped.
(Ordinance 2022-0322-01 adopted 3/22/22)
Nothing in this division or in the residential code hereby adopted
shall be construed to affect any suit or proceeding impending in any
court, or any rights acquired, or liability incurred, or any cause
or causes of action acquired or existing, under any act or ordinance
repealed as provided in the ordinance from which this section derives;
nor shall any just or legal right or remedy of any character be lost,
impaired or affected by this division.
(Ordinance 2022-0322-01 adopted 3/22/22)
Any person who violates a provision of this code, or fails to
comply therewith, or with any of the requirements thereof, shall be
guilty of a misdemeanor, and subject to a fine of between $1.00 and
$2,000.00. Each day a violation occurs constitutes a separate offense.
(Ordinance 2022-0322-01 adopted 3/22/22)