Note: Prior ordinance history: Ord. No. 1945CCS §
11, adopted 6/8/99.
Notwithstanding any provisions of the
California Building Code,
California Residential Code, California Fire Code, California Building
Standards Code, State Housing Law or other codes adopted by any Chapter
in Article VIII of the Municipal Code to the contrary, the following
local amendments shall apply.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2328CCS § 21,
adopted 11/9/10; Ord.
No. 2527CCS § 10, adopted 11/22/16; Ord. No. 2623CCS § 12,
adopted 10/22/19; Ord.
No. 2727CCS § 13, adopted 10/25/22)
The purpose of this Chapter is to promote public safety and
welfare by reducing the cumulative impact of certain individual construction
and building projects, each with an increased potential demand on
the rescue and fire suppression resources of the community. The City
Council establishes the policy of regulating both new and existing
buildings in this class by requiring approved automatic fire extinguishing
and detection systems, standpipes, fire resistive doors, and other
construction to be provided in these structures at the time of their
construction, conversion, alteration and maintenance so as to significantly
reduce the potential demand from simultaneous incidents on emergency
service resources.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
The provisions of this Chapter shall apply to all new and existing
buildings within the City, as indicated below. Structures for which
a building permit has been issued prior to November 1, 2002, shall
be considered as existing buildings.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
For purposes of this Chapter, the following definitions shall
apply:
"Automatic fire detection alarm system"
means a system that complies with Santa Monica Fire Department
requirements and is an approved arrangement of smoke, rate-of-rise,
fixed temperature, or any other detector, which is approved for the
use intended. The system shall alert all occupants of a building in
case of fire and, when required by the Fire Chief, notify the Fire
Department through Central Station Monitoring.
"Fire alarm system"
means a system or portion of a system consisting of components
and circuits arranged to monitor and annunciate the status of a fire
alarm or supervisory signal-initiating devices and to initiate the
appropriate response to those signals.
"False alarm"
means an activated fire alarm or fire alarm signal from any
fire alarm system which is responded to by the Santa Monica Fire Department
but for which no emergency situation exists or where there is no evidence
to indicate that there was an emergency situation as determined by
the responding officer. False fire alarms, that qualify under this
Section include:
(1)
Alarm caused by improper installation or maintenance of the
fire alarm system. This includes missing backup batteries, loose connections;
poorly installed or mounted smoke detectors near air vent or otherwise
overly sensitive detection devices;
(2)
Alarm caused by construction and/or demolition to the fire alarm
system;
(3)
Alarm caused by construction-related activities such as dust
or painting operation;
(4)
Alarms caused by problematic or out-of-service fire alarm systems;
(5)
Alarms caused by failure of providing proper notification to
the responsible parties (alarm company and fire dispatch) of a fire
alarm system in repair, test;
(6)
Alarms caused by occupant or owner conducting a fire drill;
(7)
Alarm caused by a burglar alarm reported as a fire alarm by
an alarm company;
(8)
Alarm for which there is no explanation. If a cause for the
alarm cannot be identified—no pull station activated, smoke
was not present, etc.—the alarm system will be assumed to have
malfunctioned.
"Fiscal year"
means the period from and including July 1st of any year
to and including June 30th of the following year.
"Owner"
means any person who owns the premises in which a fire alarm
system is installed or the person or persons, who lease, operate,
occupy or manage the premises. The owner shall be responsible for
the activation of a fire alarm system. This includes all occupancy
classification as defined in the California Building and Fire Codes
as adopted by the City of Santa Monica.
"Person"
means any individual, or entity, as defined in Section
1.12.150 of this Code.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2233CCS § 1, adopted 5/22/07; Ord. No. 2244CCS § 11,
adopted 11/27/07; Ord.
No. 2527CCS § 10, adopted 11/22/16; Ord. No. 2623CCS § 12,
adopted 10/22/19; Ord.
No. 2727CCS § 13, adopted 10/25/22)
(a) When Required. An approved automatic fire sprinkler system
shall be installed as set forth in this Chapter under the following
conditions:
(1) In all newly constructed buildings, without regard to floor area
or area separation walls except detached one-story two-car residential
garages (including minor accessory uses such as laundry areas or bathrooms
under one hundred square feet) provided that the new garage is located
a minimum of six feet away from any other building on the same lot.
(2) Throughout any existing building, when there is a change in occupancy
classification to a more hazardous division, as shown in Table 8.44-A
or as determined by the Fire Chief or the Fire Marshal.
TABLE 8.44-Al DEGREE OF OCCUPANCY
HAZARD
|
---|
Rank
|
Occupancy Class
|
---|
1
|
Groups E and I
|
2
|
Groups A, Divisions 1, 2, 4 and 5
|
3
|
Group R, Divisions 1 and 2 and Group A, Division 3
|
4
|
Group H, Divisions 1, 2 and 5
|
5
|
Group H, Divisions 3 and 4, Group L, Group F
|
6
|
Groups B and M; Group S, Divisions 1 and 2
|
7
|
Group R, Division 3
|
8
|
Group U, Division 1
|
1
|
To use the table - Step 1. Find the existing occupancy classification
or division in the occupancy class column. Step 2. If the new occupancy
classification or division is ranked above the existing class, then
the entire building requires a full automatic fire sprinkler system.
|
(3) Throughout any existing building greater than one thousand square
feet, whenever more than fifty percent cumulative, of the existing
floor area, including mezzanines, is added to within three calendar
years.
(4) Throughout any existing building one thousand square feet or less,
whenever more than seventy-five percent cumulative, of the existing
floor area, including mezzanines, is added within three calendar years.
(5) Throughout any existing building greater than one thousand square
feet, whenever more than a cumulative fifty percent of the interior
walls and/or ceilings are exposed.
(6) Throughout any existing building one thousand square feet or less,
whenever more than a cumulative seventy-five percent of the interior
walls and/or ceilings are exposed.
(7) Throughout any existing building other than a single-family dwelling,
whenever an additional story is added.
(8) Throughout any single-family dwelling greater than one thousand square
feet, whenever an additional story is added and the new floor area
for the additional story increases the existing floor area by more
than thirty-three and one-third percent.
(9) Throughout any single-family dwelling one thousand square feet or
less, whenever an additional story is added and the new floor area
for the additional story increases the existing floor area by more
than fifty percent.
(10) Throughout any existing building or structure determined to be used
primarily for public assembly more than five thousand square feet
in total floor area. This subsection shall not apply to buildings
or structures with an approved full automatic fire sprinkler system
or to churches and theaters with fixed seating.
(11) Throughout the entire floor of any existing building equipped with
a partial fire sprinkler system whenever more than fifty percent of
the floor space is altered or reconfigured.
(12) In a newly constructed ADU attached or detached, when the single
family dwelling has an existing residential automatic fire sprinkler
system.
(13) Throughout any existing single family dwelling less than one thousand
square feet with an attached ADU that adds seventy-five percent to
the original home floor area.
(14) Throughout any existing single family dwelling greater than one thousand
square feet with an attached ADU that adds fifty percent to the original
home floor area.
(15) When a newly constructed ADU is greater than one hundred fifty feet
from the primary street access and has no rear alley access.
(b) Exceptions. The requirements of subsection
(a) of this Section shall not apply to:
(2) Buildings such as power plants, lookout towers, steeples, grain houses,
and similar structures with noncontinuous human occupancy only when
so determined by the Fire Chief;
(c) When
a fire sprinkler system is required in any building that does not
have a designated occupant and use at the time fire sprinkler plans
are submitted for approval, the system shall be designed and installed
to deliver a minimum density of not less than that required for Ordinary
Hazard, Group 2, with a minimum design area of not less than three
thousand square feet.
When a subsequent change in occupancy classification requires
the fire sprinkler system to deliver a higher minimum density, it
shall be the responsibility of the building owner to upgrade the system
to the required density for the new use.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2165CCS § 1, adopted 8/9/05; Ord. No. 2244CCS § 11,
adopted 11/27/07; Ord.
No. 2328CCS § 22, adopted 11/9/10; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
The Fire Chief and Building Officer are jointly authorized to promulgate standards regarding the installation and type of automatic fire sprinkler systems required by Section
8.44.050 of the Municipal Code.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
New buildings or structures housing any occupancy classification
having floors used for human occupancy more than fifty-five feet above
the lowest level of Fire Department vehicle access shall be defined
as a high-rise building or structure. Such high-rise buildings or
structures shall comply with the high-rise building requirements contained
in Section 403 of the
California Building Code unless modified through
modifications and/or alternate materials and methods approved by the
Fire Marshal and the Building Officer.
These requirements shall not apply to:
(2) Buildings
used exclusively as open parking garages;
(3) Buildings
such as power plants, lookout towers, steeples, grain houses and similar
structures with noncontinuous human occupancy only when so determined
by the Fire Chief.
Any full automatic fire sprinkler system installed in any high-rise
building shall have two connections with control valves to independent
risers on each floor level, with each riser being of the size necessary
to supply the required water supply.
|
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2445CCS § 35,
adopted 11/12/13; Ord.
No. 2527CCS § 10, adopted 11/22/16; Ord. No. 2623CCS § 12,
adopted 10/22/19; Ord.
No. 2727CCS § 13, adopted 10/25/22)
(a) General. In every existing apartment, dwelling unit, guestroom,
one- or two-family dwelling or condominium, hotel or motel room, smoke
detectors shall be installed in accordance with the provisions of
this Section.
(b) Existing Group R Occupancies. On or before July 1, 2001 approved
and listed smoke detectors, which may be battery-powered, shall be
installed and located in accordance with the California Fire Code.
(c) Residential Occupancy Remodels. Approved and listed smoke
detectors, which meet the provisions of the
California Building Code,
shall be installed when any of the following occurs:
(1) Addition of a story which increases total floor area by more thirty-three
and one-third percent; or
(2) More than fifty percent of the existing roof structure is removed;
or
(3) The floor area of an existing residence with a floor area of one
thousand square feet or less increases more than seventy-five percent;
or
(4) The floor area of an existing residence with a floor area of more
than one thousand square feet increases more than fifty percent.
(d) Transfer of Property. Prior to the sale or exchange of residential buildings subject to Chapter
9.08 of this Municipal Code, the seller shall certify, on the report of residential building record, that approved and listed smoke detectors have been installed. Smoke detectors, which may be battery-powered, shall be installed and located in accordance with California Fire Code.
(e) Maintenance. Smoke detectors shall be maintained in an operable
condition at all times. Detectors shall be tested, maintained and
cleaned at least annually by the building owner. Proof of maintenance
and cleaning shall be maintained by the building owner for a minimum
of five years. New batteries shall be installed in smoke detectors
annually or in accordance with the manufacturer's instructions. When
it is determined that any installed smoke detector was manufactured
more than ten years prior to the effective date of this Chapter, it
shall be replaced.
Exception: Single-family dwellings, which are owner
occupied, do not need to maintain a written record of proof of maintenance
and cleaning.
(f) Service. Smoke detectors shall be tested, cleaned, serviced,
and replaced as needed every five years by a licensed C-10 electrical/fire
alarm contractor. Written record of the service for each detector
shall be maintained by the building owner and shall be made available
for review by the Fire Department upon request. Written certification
of the required five-year service shall be submitted to the Fire Prevention
Division of the Fire Department.
Exception: Single-family dwellings, which are owner
occupied, do not need to maintain a written record.
(g) Hearing Impaired Occupants. In a dwelling unit occupied by
one or more hearing impaired persons, each smoke detector shall cause
the operation of approved notification appliances for the hearing
impaired. Visible notification appliances used in rooms where hearing
impaired persons sleep shall have a minimum rating of one hundred
seventy-seven candela for a maximum room size of fourteen feet by
sixteen feet. For larger rooms, the notification appliance shall be
located within sixteen feet of where the pillow is normally located.
Wall mounted visual notification appliances which are part of a smoke
detector shall be located between four and twelve inches below the
ceiling measured to the top of the smoke detector. Visual notification
appliances in non-sleeping areas shall have a minimum rating of fifteen
candela.
Exception: Where a visual notification appliance
in a sleeping room is mounted more than twenty-four inches below the
ceiling, a minimum rating of one hundred ten candela shall be permitted.
Since hearing deficits are often not readily apparent, the responsibility
to advise the property owner or manager shall rest with the hearing
impaired party. The responsibility for compliance shall rest with
the property owner or manager.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
(a) General. Fire protection systems shall conform to the standards adopted by Chapter
8.40 of the Municipal Code and to supplemental requirements of the Fire Chief.
(b) System Monitoring. Alarm systems, required by Chapter
8.40 of the Municipal Code shall be monitored by an approved and listed central station. Exception: Fire sprinkler systems containing less than six heads may be provided with a local alarm.
(c) Annunciation and Control. Extinguishing systems shall include
control valves and signaling devices to control and indicate system
operation by floors or other approved subdivisions. An approved annunciator
panel shall be provided in an approved location near the principal
entrance.
(d) Fire Department Connections and System Zones. Systems shall
be provided with listed Fire Department connections at approved locations
on public street frontages. Multiple exterior connections and system
zones shall be interconnected.
(e) Design, Approval, Acceptance, Testing and Maintenance. Fire
alarm systems shall be maintained in an operable condition at all
times. When required by the Fire Chief, an approved fire watch shall
be provided and maintained while a fire and life safety system is
inoperative or impaired. The fire watch shall be maintained until
the inoperative or impaired system is restored a fully operational
condition and a test is approved by the Fire Department.
(f) Approval, Acceptance, Testing of New Fire Alarm Systems. New
fire alarm systems shall be designed, installed, tested and maintained
in accordance with the provisions of the National Fire Alarm Code
published by the National Fire Protection Association.
(g) Existing Fire Alarm Systems. Existing fire alarm systems shall
be tested and maintained in accordance with the provisions of the
National Fire Alarm Code.
(h) Notification Devices. All one- and two-family dwellings having
a fire sprinkler system installed in compliance with NFPA 13-D, NFPA
13D, NFPA 13R and NFPA 13 systems shall have a weather-proof horn/strobe
installed on the address side of the building or as approved by the
Fire Marshal.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2328CCS § 24,
adopted 11/9/10; Ord.
No. 2527CCS § 10, adopted 11/22/16; Ord. No. 2623CCS § 12,
adopted 10/22/19; Ord.
No. 2727CCS § 13, adopted 10/25/22)
(a) General. This Section shall be applicable to all existing
automatic fire sprinkler systems installed prior to January 1, 1996.
At the time of required five-year service, the seismic protection
of all automatic fire sprinkler systems shall be inspected in accordance
with this Section. The C-16 contractor performing the inspection shall
prepare a written notice of system deficiencies, which shall be submitted
to the Fire Prevention Division.
(b) Standard. Seismic protection shall comply with the 1996 Edition
of NFPA 13, Standard for the Installation of Automatic Fire Sprinkler
Systems.
(c) Restricted Fasteners. Through bolts with washers and nuts
shall be used to secure earthquake bracing in wood members. Lag screws
shall not be used to secure longitudinal bracing in wood members.
Powder-driven studs shall not be used to secure earthquake bracing
in concrete or masonry members. When it is determined that powder-driven
studs have been used, they shall be replaced with an approved fastener.
(d) Suspended Ceilings. Ceilings shall be braced with splayed
seismic bracing wire.
(e) Unsupported Sprinklers. Sprinkler drops longer than eight
feet shall be braced with splayed seismic bracing wire.
(f) Armovers. Armovers used to position sprinkler heads in ceilings
shall be braced with splayed seismic bracing wire.
(g) Branch Lines. A listed wrap-around hanger shall be installed
on all branch lines within eighteen inches of the end.
(h) Unlisted Mechanical Couplings. All unlisted mechanical couplings
shall be replaced with approved and listed mechanical couplings.
(i) Unbraced Systems. Listed bracing shall be installed in accordance
with NFPA 13, 1996 Edition.
(j) Threaded Pipe. All sprinkler systems shall use shop-welded
branch lines. The branch lines shall be secured to cross-mains by
approved grooved mechanical fittings. Longitudinal and lateral bracing
shall be installed on feed mains, cross-mains and branch lines larger
than two and one-half inches. Bracing shall be installed on smaller
branch lines that could strike light fixtures, building system components,
and building structural members.
(k) Threaded Pipe Sway Bracing. No thin wall pipe shall be used
for sway bracing. Pipe used shall be minimum Schedule 40.
(l) Retaining Straps. All C-clamp type hangers shall be equipped
with retaining straps.
(m) Notification and Enforcement. Notification, enforcement and
compliance shall be in accordance with Sections 8.44.060 and 8.44.070
of the Municipal Code. When it is determined that an existing automatic
fire sprinkler system does not meet the minimum standard, the building
owner shall be notified in accordance with this subsection.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
Prior to installation of any automatic fire extinguishing, life
safety or fire protection system required by this Chapter, the Fire
Chief shall approve the plans and specifications for the system.
(Added by Ord. No. 2054CCS §
11, adopted 10/8/02; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
(a) False Alarm Reports Required. A report shall be generated
by the Santa Monica Fire Department responding fire companies as deemed
necessary by the Fire Marshal. The report shall include whether or
not the alarm was a "false alarm" as defined in Section 8.44.040(d)
of this Code.
(b) Fire Alarm Requirements.
(1) Every person owning or maintaining a fire alarm system shall post
a notice containing the name and telephone number of the persons at
which they may be reached at any time of the day or night to be notified
to render repairs or services when the fire alarm is activated. Such
notice shall be posted near the fire alarm panel and or the remote
annunciator panel in such a position so as to be legible.
(2) The owner or the owners' representative of any fire alarm system
shall be responsible for deactivating any alarm within one hour after
notification or after reasonable efforts have been made to notify
the owner or owners' representative that such alarm has been activated
and is ringing. The ringing of an alarm for a period in excess of
one hour after such notification or efforts of notification have been
made is hereby declared to be a public nuisance and subject to misdemeanor
prosecution or summary abatement.
(Added by Ord. No. 2233CCS §
2, adopted 5/22/07; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
The following response fees shall be levied and paid by the responsible party (owner or lessee) of a location that includes a fire alarm system. The fees are based on the total number of false alarms, as defined in Section
8.44.040, which generate a fire company's response to the location during the same fiscal year.
No response fees shall be charged for the first and second false
alarm responses to a location during the same fiscal year. Based on
the costs associated with the Fire Department's emergency response
to a false alarm, a fee set by resolution of the City Council shall
be charged for the third false alarm response and each subsequent
false alarm response made to a location during the same fiscal year.
The Fire Chief shall cause to be issued a monthly bill for the unpaid
service charges accrued during the billing period and any prior periods.
Such bill shall be due and payable within fifteen days after the billing
date.
All remedies shall be cumulative, and the use of one or more
remedies by the City shall not bar the use of any other remedy for
the purpose of enforcing the provisions of this Chapter. The amount
of any service charge shall be deemed a debt to the City. An action
may be commenced in the name of the City in any court of competent
jurisdiction for the amount of any delinquent debt thirty days after
it becomes due and payable. Payment of any service charge shall not
prohibit criminal prosecution for the violation of any of the provisions
of this Chapter.
A location with a fire alarm system that generates more than five false alarm responses during a single fiscal year may be declared a public nuisance and the owners as defined in Section
8.44.040 shall be prosecuted.
(Added by Ord. No. 2233CCS §
3, adopted 5/22/07; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)
A penalty of ten percent shall be added to the fees required by Section
8.44.150 in connection with any fees that are not paid in the time and manner required by Section
8.44.150.
(Added by Ord. No. 2233CCS §
4, adopted 5/22/07; amended by Ord. No. 2244CCS § 11, adopted 11/27/07; Ord. No. 2527CCS § 10,
adopted 11/22/16; Ord.
No. 2623CCS § 12, adopted 10/22/19; Ord. No. 2727CCS § 13,
adopted 10/25/22)