Pursuant to Section 50022.2 of the
Government Code of the state of California, there is hereby adopted by reference by the city council for the purpose of prescribing regulations for the erection, construction, improvement, removal, conversion, demolition, occupancy, equipment, use, height, area and maintenance of all buildings and structures in the city of Laguna Beach, (except those buildings that are required to be constructed in compliance with the California Residential Code adopted in Section
14.52.010) that certain code known as the
California Building Code including Chapter 1, Division II and Appendix Chapters G, H and J as published by the International Code Council, including the index thereto (2022 Edition) except those portions as are hereafter deleted, modified or amended, and this Code is adopted by reference and incorporated as though fully set forth herein and designated and referred to as the “Building Code” of and for the city of Laguna Beach. Should there be a conflict between the
California Building Code as adopted and other municipal code requirements, the more restrictive shall govern.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019;Ord. 1681 § 1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023; Ord. 1681, §
1, 2023)
109.7 Reinspection fees. A reinspection fee may
be assessed for each inspection or reinspection when such portion
of work for which inspection is called is not complete or when corrections
called for are not made. This subsection is not to be interpreted
as requiring reinspection for failure to comply with the requirements
of the technical codes, but as controlling the practice of calling
for inspections before the project is ready for such inspection or
reinspection. Reinspection fees may be assessed when the permit card
is not properly posted on the work site; the approved plans are not
readily available to the inspector; for failure to provide access
on the date for which the inspection is requested; or for deviating
from the plans requiring the approval of the Building Official. To
obtain a reinspection, the applicant shall pay the reinspection fee
in accordance with a fee schedule adopted by resolution of the City
Council.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
113.1 General. In order to hear and decide appeals
of orders, decisions or determinations made by the building official
relative to the application and interpretation of this code, there
shall be and is hereby created a Board of Appeals. This Board is likewise
known as the Planning Commission of the City of Laguna Beach. The
Planning Commission, serving as the Board of Appeals, shall render
all decisions in writing to the building official with a duplicate
copy to the appellant, and recommend to the City Council such new
legislation as is consistent therewith.
Fees for a hearing before the Planning Commission serving as
Board of Appeals are to be established by resolution of the City Council,
and are payable at the time the applicant submits a request for a
hearing.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
114.4 Violation penalties. Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the building official, or of a permit or certificate issued under provisions of this code, shall be guilty of a misdemeanor and/or subject to an administrative citation pursuant to Chapter
1.15 of the Municipal Code, and each such person shall be deemed guilty of a separate offense for each and every day or portion thereof during which any violation of any provisions of this code is committed, continued or allowed to be continued.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
115.3 Unlawful continuance. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be guilty of a misdemeanor and/or subject to an administrative citation pursuant to Chapter
1.15 of the Municipal Code, and each such person shall be deemed guilty of a separate offense for each and every day or portion thereof during which any violation of any provisions of this code is committed, continued or allowed to be continued.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
403.1 Applicability. New high-rise buildings and
new Group I-2 occupancies having occupied floors located more than
55 feet above the lowest level of fire department access shall comply
with Sections with Sections 403.2 through 403.6.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
404.3 Automatic sprinkler protection. An approved
automatic sprinkler system shall be installed throughout the entire
building.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
410.6 Automatic sprinkler system. Stages shall
be equipped with an automatic fire-extinguishing system in accordance
with Chapter 9.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
701A.1 Scope. This chapter applies to building
materials, systems and/or assemblies used in the exterior design and
construction of new buildings, additions, alterations, and repairs
within a Fire Hazard Severity Zone within the City of Laguna Beach.
Exception: With the approval of the building official
minor repairs or replacement of exterior materials may be done with
the same materials as exists on the building.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
New buildings located in any Fire Hazard Severity Zone or any
Wildland Interface Fire Area designated by the City of Laguna Beach
shall comply with this chapter. For regulations regarding outdoor
fires, including fire pits, barbeques, and portable flame producing
devices, see California Fire Code Section 323
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023; Ord. 1681, §
1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
705A.1 General. Roofs shall comply with the requirements
of Chapter 7A and Chapter 15. All new roof coverings and assemblies
and all reroofs must be Class A. Roofs shall have roofing assembly
installed in accordance with its listing and the manufacturer’s
installation instructions.
Exception: With the approval of the building official
small sections of a roof may be reroofed with the same material as
exists on the roof.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
706A.4 Vent size. Each individual ventilation opening
into enclosed attics, enclosed eave soffit spaces, enclosed rafter
spaces formed where ceilings are applied directly to the underside
of roof rafters, and underfloor spaces shall not exceed 144 square
inches in area. Openings exceeding 144 square inches in area shall
be protected by a minimum 1 3/8 inch thick solid core wooden door
or equivalent.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
707A.3 Exterior wall coverings. The exterior wall
covering, or wall assembly, including insulation shall comply with
one of the following requirements:
2. Ignition-resistant
material.
3. Heavy
timber exterior wall assembly.
4. Log
wall construction assembly.
5. Fire
rated assembly approved by the Building Official.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
707A.4 Exterior wall assemblies. Wall assemblies
of buildings or structures shall be constructed using one or more
of the following methods, unless they are covered by an exterior wall
covering complying with Section 707A.3:
1. Assembly
of sawn lumber or glue-laminated wood with the smallest minimum nominal
dimension of four inches (102 mm). Sawn or glue-laminated planks splined,
tongue-and-grove, or set close together and well spiked.
2. Log
wall construction assembly.
3. Assembly
that has been tested in accordance with the test procedures for a
ten-minute direct flame contact exposure test set forth in ASTM E2707
with the conditions of acceptance shown in Section 707A.4.1.
4. Assembly
that meets the performance criteria in accordance with the test procedures
for a ten-minute direct flame contact exposure test set forth in SFM
Standard 12-7A-1.
5. Assembly
suitable for exterior fire exposure with a one-hour fire-resistance
rating, rated from the exterior side, as tested in accordance with
ASTM E119 or UL 263.
6. Assembly
suitable for exterior fire exposure containing one layer of 5/8-inch
(15.9 mm) Type X gypsum sheathing applied behind the exterior wall
covering or cladding on the exterior side of the framing.
7. Assembly
suitable for exterior fire exposure containing any of the gypsum panel
and sheathing products listed in the Gypsum Association Fire Resistance
Design Manual as complying with a one-hour fire-resistance rating,
as tested in accordance with ASTM E119 or UL 263.
(Ord. 1681, §
1, 2023)
708A.2.1.1 Vinyl windows. Glazing frames made of
vinyl materials shall have welded corners and metal reinforcing in
the interlock area.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
904.3.5 Monitoring. Where a building fire alarm
or monitoring system is installed, automatic fire-extinguishing systems
shall be monitored by the building fire alarm or monitoring system
in accordance with NFPA 72.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the
following locations:
1. In
every required stairway, a hose connection shall be provided for each
floor level above or below grade. Hose connections shall be located
at an intermediate floor level landing between floors, unless otherwise
approved by the fire code official. See Section 909.20.3.2 for additional
provisions in smoke proof enclosures.
2. On
each side of the wall adjacent to the exit opening of a horizontal
exit.
Exception: Where floor areas adjacent to a horizontal
exit are reachable from exit stairway hose connections by a nozzle
attached to 100 feet of hose, as measured along the path of travel,
a hose connection shall not be required at the horizontal exit
3. In
every exit passageway, at the entrance from the exit passageway to
other areas of a building.
Exception: Where floor areas adjacent to an exit
passageway are reachable from exit stairway hose connections by a
thirty-foot hose stream from a nozzle attached to 100 feet of hose,
a hose connection shall not be required at the entrance from the exit
passageway to other areas of the building.
4. In
covered mall buildings, adjacent to each exterior public entrance
to the mall and adjacent to each entrance from an exit passageway
or exit corridor to the mall.
5. Where
the roof has a slope less than four units vertical in 12 units horizontal,
each standpipe shall be provided with a hose connection located either
on the roof or at the highest landing of a stairway with stair access
to the roof. An additional hose connection shall be provided at the
top of the most hydraulically remote standpipe for testing purposes.
6. Where
the most remote portion of nonsprinklered floor or story is more than
150 feet from a hose connection or the most remote portion of a sprinklered
floor or story is more than 150 feet from a hose connection, the building
or fire official is authorized to require that additional hose connections
be provided in approved locations. The distance from a hose connection
shall be measured along the path of travel.
7. The
centerline of the 2.5 inch outlet shall be no less than 18 inches
above and no more 24 inches above the finished floor.
8. Every
new building with any horizontal dimensions greater than 300 feet
shall be provided with either access doors or a 2.5 inch outlet so
that all portions of the building can be reached with 150 feet of
hose from an access door or hose outlet. Required access doors shall
be located in the exterior of the building and shall be accessible
without the use of a ladder. The door dimensions shall be not less
than three feet in width, and not less than six feet eight inches
in height. These doors are for fire department access only.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
907.3.1 Duct smoke detectors. Smoke detectors installed
in ducts shall be listed for the air velocity, temperature and humidity
present in the duct. Duct smoke detectors shall be connected to the
building’s fire alarm control unit when a fire alarm system
is installed. Activation of a smoke detector shall initiate a visible
and audible supervisory signal at a constantly attended location and
shall perform the intended fire safety function in accordance with
this code and the California Mechanical Code. Duct smoke detectors
shall not be used as a substitute for required open area detection.
Exception: In occupancies not required to be equipped
with a fire alarm system, actuation of a smoke detector shall activate
a visible and an audible signal in an approved location. Smoke detector
trouble conditions shall activate a visible or audible signal in an
approved location and shall be identified as air duct detector trouble.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
909.20.4.3.2 Standby power. Mechanical vestibule
and stair shaft ventilation systems and automatic fire detection systems
shall be powered by an approved emergency power system per section
403.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
910.3 Sprinklered buildings. Where installed in
buildings equipped with an approved automatic sprinkler system, smoke
and heat vents shall be designed to operate automatically by actuation
of a heat-responsive device rated at least 100° F. above the operating
temperature of the sprinkler, unless otherwise approved.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
1406.1 General. The requirements of Chapter 7A
are applicable for all buildings located in Fire Hazard Zones. Section
1406 shall apply to exterior wall coverings; balconies and similar
projections; and oriel and bay windows constructed of combustible
materials. The most restrictive requirements of Section 1406 and Chapter
7A shall govern.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
1406.3 Balconies and similar projections. Balconies
and similar projections of combustible construction other than fire-retardant-treated
wood shall be fire-resistance rated in accordance with Table 601 for
floor construction or shall be of Type IV construction in accordance
with Section 602.4. The aggregate length shall not exceed 50% of the
buildings perimeter on each floor.
Exceptions:
1. On
buildings of Type I and II construction, three stories or less above
grade plane, fire-retardant-treated wood shall be permitted for balconies,
porches, decks and exterior stairways not used as required exits.
2. Balconies
and similar projections on buildings of Type III, IV and V construction
shall be permitted to be of Type V construction but must comply with
the provisions of Section 707A.
3. Where
sprinkler protection is extended to the balcony areas, the aggregate
length of the balcony on each floor shall not be limited.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
SECTION 1505
FIRE CLASSIFICATION
|
1505.1 General. Roof assemblies shall be divided
into the classes defined below. Class A, B, and C roof assemblies
and roof coverings required to be listed by this section shall be
tested in accordance with ASTM E 108 or UL 790. In addition, fire-retardant
wood roof coverings shall be tested in accordance with ASTM D 2898.
A Class A roof assembly or roof covering is the minimum class of roofing
that can be applied on any building in the City for either new roofing
or reroofing. Roofing and reroofing must also comply with Section
705A.
Exceptions:
|
1.
|
Skylights and sloped glazing that comply with Chapter 24.
|
2.
|
With the approval of the building official, reroofing of small
portions of a roof may done with the same material as exists on the
roof.
|
1505.1.1 Roof coverings when 50% or more of roof covering
is replaced. The entire roof covering of every existing structure
where more than 50% of the total roof area is replaced within any
one-year period shall be at least Class A.
1505.2 Class A roof assemblies. Class A roof assemblies
are those that are effective against severe fire test exposure. Class
A roof assemblies and roof coverings shall be listed and identified
as Class A by an approved testing agency. Class A roof assemblies
shall be permitted for use in buildings or structures of all types
of construction.
Exceptions:
|
1.
|
Class A roof assemblies include those with coverings of brick,
masonry or an exposed concrete roof deck.
|
2.
|
Class A roof assemblies also include ferrous or copper shingles
or sheets, metal sheets and shingles, clay or concrete roof tile or
slate installed on noncombustible decks or ferrous, copper or metal
sheets installed without a roof deck on noncombustible framing.
|
(Balance of Section remains unchanged.)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
104.8.2 Design and construction of retaining walls that
support public improvements. Retaining walls that provide lateral
support for public improvements such as streets, storm drains and
sanitary sewers shall be constructed entirely of concrete with a maximum
water-cement ratio of 0.40. Such walls shall be damp proofed or waterproofed
as required for walls enclosing interior habitable spaces per Section
1805.
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)
Subsection 3109.2 is amended to read as follows:
3109.2 Construction permit; safety features required. New or remodel pools or spas, at a private single-family home, shall
have an enclosure complying with the amended California Residential
Code Appendix V.
(Ord. 1641 § 1, 2019; Ord. 1681, §
1, 2023)
(Ord. 1536 § 1, 2010; Ord. 1581 § 1, 2013; Ord. 1620 § 1, 2016; Ord. 1641 § 1, 2019; Ord. 1681, § 1, 2023)