Pursuant to Section 50022.2. of the Government Code of the state of California, there is hereby adopted by reference by the city council for the purpose of prescribing regulations for the erection, construction, improvement, removal, conversion, demolition, occupancy, equipment, use, height, area and maintenance of all detached one- and two-family dwellings and townhouses not more than three stories above grade plane in height with a separate means of egress in the city of Laguna Beach, that certain code known as the California Residential Code including Chapter 1, Div. II, Appendix O and V as published by the International Code Council, including the index thereto (2018 Edition) except those portions as are hereafter deleted, modified or amended, and this Code is adopted by reference and incorporated as though fully set forth herein and designated and referred to as the “Residential Code” of and for the City of Laguna Beach. Should there be a conflict between the California Residential Code as adopted and other municipal code requirements, the more restrictive shall govern.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R101.4 of the California Residential Code adopted in Section 14.52.010 is added to read as follows:
R101.4 Administrative Provisions. The provisions contained in Sections 101 through 116 of the California Building Code are applicable to the construction regulated by this code.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Table R301.2 (1) of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
-Image-7.tif
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R308.6.2 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R308.6.2 Permitted materials. The following types of glazing may be used:
1. 
Laminated glass with a minimum 0.015-inch polyvinyl butyral interlayer for glass panes 16 square feet or less in area located such that the highest point of the glass is not more than 12 feet above a walking surface or other accessible area; for higher or larger sizes, the minimum interlayer thickness shall be 0.030 inch.
2. 
Fully tempered glass.
3. 
Heat-strengthened glass.
4. 
Wire glass.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R313.1 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R313.1 Townhouse automatic sprinkler systems. An automatic residential fire sprinkler system shall be installed in townhouses and garages attached to townhouses. A garage is considered attached for the purposes of this subsection if it is within 10 feet of the townhouse. If the cumulative value of additions, alterations and repairs done to a townhouse and attached garage in any three-year period exceeds 50% of the valuation of the townhouse and attached garage prior to the additions, alterations, and repairs, the entire townhouse and attached garage must be sprinklered throughout. The valuation used for the existing building and for the additions, alterations, and repairs is the valuation established in the City’s resolution for computation of building permit fees. For the purposes of this subsection, each townhouse with its attached garage will be considered a separate building.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R313.2 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R313.2 One- and two- family dwellings automatic sprinkler systems. An automatic residential fire sprinkler system shall be installed in one- and two-family dwellings and garages attached to one- and two-family dwellings. A garage is considered attached for the purposes of this subsection if it is within 10 feet of the one- or two-family dwelling. If the cumulative value of additions, alterations and repairs done to a one- or two-family dwelling and attached garage in any three-year period exceeds 50% of the valuation of the one- or two-family dwelling and attached garage prior to the additions, alterations, and repairs, the entire one- or two-family dwelling and attached garage must be sprinklered throughout. The valuation used for the existing building and for the additions, alterations, and repairs is the valuation established in the City’s resolution for computation of building permit fees. For the purposes of this subsection, firewalls, fire barriers, or fire partitions shall not define separate buildings or fire areas.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R313.3 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R313.3 Dwelling unit fire sprinkler systems. Where installed, residential fire sprinkler systems, or portions thereof, shall be in accordance with the most current NFPA 13D standard for design and calculation. All residential fire sprinkler systems shall have a flow switch installed that activates an electric exterior alarm. The residential fire sprinkler flow switch shall also activate all interconnected interior smoke detectors.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsections R313.3.1 through R313.3.8.2 of the California Residential Code adopted in Section 14.52.010 are deleted in their entirety.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.1.1 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.1.1 Scope. This chapter applies to building materials, systems and/or assemblies used in the exterior design and construction of new buildings, additions, alterations, and repairs within the City.
Exception: With the approval of the Building Official minor repairs or replacement of exterior materials may be done with the same material as exists on the building.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.1.2 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.1.2 Purpose. The purpose of this Chapter is to establish minimum standards for the protection of life and property by increasing the ability of a building located within the City to resist the intrusion of flame or burning embers projected by a vegetation fire and contributes to a systematic reduction in conflagration losses.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.1.3 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.1.3 Outdoor fires. For regulations regarding outdoor fires, including fire pits, barbeques, and portable flame producing devices, see California Fire Code Section 323.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsections R337.1.3 through R337.1.5 of the California Residential Code adopted in Section 14.52.010 are deleted in their entirety.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.5.1 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.5.1 General. Roofs shall comply with the requirements of Sections R337 and R902. All new roof coverings and reroofs must be Class A assemblies. Roofs shall have roofing assemblies installed in accordance with their listings and manufacturer’s instructions.
Exception: With the approval of the Building Official small sections of a roof may be reroofed with the same material as exists on the roof.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.5.5 of the California Residential Code adopted in Section 14.52.010 is added to read as follows:
R337.5.5 Skylights and sloped glazing. Skylights and sloped glazing must comply with Section R308.6 and must be of glass. Plastic skylights and plastic sloped glazing are not allowed.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R327.6.2 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.6.2 Requirements. Ventilation openings for enclosed attics, enclosed eave soffit spaces, enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters, and underfloor ventilation openings shall be fully covered with metal wire mesh, vents, other materials or other devices that meet the following requirements:
1. 
The dimensions of the openings therein shall be a minimum of 1/16 inch and shall not exceed 1/8 inch.
2. 
The materials used shall be noncombustible.
Exception: Vents located under the roof covering, along the ridge of the roofs, with the exposed surface of the vent covered by noncombustible wire mesh, may be of combustible construction.
3. 
The materials used shall be corrosion resistant.
4. 
Each individual vent shall not exceed 144 square inches in area. Exterior openings into portions of the building noted in this section that exceed 144 square inches in area must be protected by a minimum 1 3/8 inch thick wooden door or equivalent
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.7.3 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
R337.7.3 Exterior walls. The exterior wall covering or wall assembly shall comply with one of the following requirements:
1. 
Noncombustible material.
2. 
Ignition-resistant material.
3. 
Heavy-timber exterior wall assembly.
4. 
Log wall construction assembly.
5. 
Fire rated assembly approved by the Building Official.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.8.2.1.1 of the California Residential Code adopted in Section 14.52.010 is added to read as follows:
R337.8.2.1.1 Vinyl frames. Glazing frames made of vinyl materials shall have welded corners and metal reinforcement in the interlock area.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection R337.10.1 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows.
R337.10.1 General. Accessory and miscellaneous structures that require a building permit shall be constructed to conform to the ignition resistance requirements of this section.
(Ord. 1536 § 2, 2010; Ord. 1581 § 2, 2013; Ord. 1620 § 2, 2016; Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)
Subsection AV100.2 (a) of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
Except as provided in Section AV100.5, when a building permit is issued for the construction of a new swimming pool or spa or the remodeling of an existing swimming pool or spa at a private single-family home, the respective swimming pool or spa shall be equipped with item #1 below AND at least one additional following seven drowning prevention features:
Subsection AV100.2 (a) #1 of the California Residential Code adopted in Section 14.52.010 is amended to read as follows:
1. 
An enclosure that meets the requirements of AV100.3 and isolates the swimming pool and spa from the private single-family home. Any walls of the residential structure or accessory structures used to complete the isolation enclosure must have door openings equipped with protection as required in AV100.2 (a) #4 or #5. Any such door protection device provided for this purpose may not be used to comply with the second drowning prevention feature requirement.
(Ord. 1641 § 2, 2019; Ord. 1681, § 2, 2023)