Battery energy storage systems shall be subject to the following requirements:
A.
Battery energy storage systems must provide energy solely to the property on which the system is located.
B.
A building permit and an electrical permit shall be required for the installation of all battery energy storage systems.
C.
Building-mounted and ground-mounted Tier 1 battery energy storage systems shall be permitted in all zoning districts as an accessory use, subject to the Uniform Code, and exempt from site plan review.
D.
All battery energy storage systems shall be affixed with a sign clearly indicating the location of the power cut switch.
E.
Building mounted Tier 1 battery energy storage systems are subject to the following requirements:
(1)
Building-mounted Tier 1 battery energy storage systems shall not be located within any attic, basement, or living space. They are permitted within an attached or detached garage, or on an exterior wall.
(2)
Interior building-mounted Tier 1 battery energy storage systems shall be mounted on a wall with floor to ceiling fireproofing, such as sheetrock that has a minimum thickness of 5/8 inches.
(3)
Building-mounted Tier 1 battery energy storage systems shall be located within a water and fireproof container with ventilation.
(4)
The space in which the building-mounted Tier 1 battery energy storage system is located shall be serviced with a hard-wired smoke detector that is connected to a monitored alarm system.
F.
Ground-mounted Tier 1 battery energy storage systems are subject to the following requirements:
(1)
The height of the ground-mounted Tier 1 battery energy storage system and any mounts shall not exceed 15 feet.
(2)
The total footprint of the ground-mounted Tier 1 battery energy storage system shall not exceed 5% of the lot coverage.
(3)
Location in a front yard is prohibited. All systems must be located in a side or rear yard.
(4)
The ground-mounted Tier 1 battery energy storage system shall comply with the minimum setbacks for accessory structures applicable to the zoning district in which the system is sited.
(5)
The system shall be screened from adjacent residences through the use of architectural features, earth berms, landscaping, or other screening to limit visibility from off-site locations.
(6)
The ground-mounted Tier 1 battery energy storage system shall be located inside a fireproof metal cabinet that is situated a minimum of two feet from the nearest habitable structure and shall not be located under the eaves of any structures.
G.
Where site plan review is otherwise required, the site plan review shall include review of the adequacy, location, arrangement, size, design, and general site compatibility of any proposed ground-mounted Tier 1 battery energy storage system.