The following rules and regulations shall govern
the installation of water distribution systems in the Town of Glenville.
As used in this article, the following terms
shall have the meanings indicated:
ENGINEER
The Town Engineer or the Town-designated engineer.
CONTRACTOR
The person, persons, copartnership, subcontractor or corporation
which has entered into contract to install a particular water distribution
system, according to plans and specifications as approved by the Town
of Glenville.
Whenever there shall be any excavation along
lands or under a pavement owned by Town, county or state government,
the Highway Superintendent or other official having control shall
be notified 24 hours in advance of said excavation.
The minimum width of replaced concrete pavements
shall be four feet at interiors and six feet at joints. Depths shall
be 1.3 times the original thickness. Existing pavement edges shall
be cut vertically. The minimum width of replaced bituminous shall
be three feet, with the base of same depth of original pavement; surface
course shall be cold-patch mixture. The existing pavement shall be
cut vertically and horizontally to a straight line. Edge of existing
pavement shall be painted with RC-3 or RC-4. The patch shall be rolled
in both directions with a five-ton roller.
The contractor shall clean up and dispose of
all excess material, trash and other debris.
[Amended 4-5-2006 by L.L.
No. 3-2006]
A. All pipe shall be cast in sand-lined molds and conform
to ASA specifications A21.8-1953 (or latest revision), thickness Class
22 and be cement-mortar lined in accordance with specifications A21.4-1953
(or latest revision). No pipe or fittings for water works service
shall be furnished without outside protective coating. Pipe shall
be designed for working pressures up to 350 psi; and tested to 500
psi hydrostatically before shipment by manufacturer.
B. Type of joint. The types of joint used may be: 1)
bell-and-spigot, 2) engineer-approved. The engineer shall approve
the type of pipe in advance.
[Amended 4-5-2006 by L.L.
No. 3-2006]
A. Pipe shall be laid parallel to tangent property line and as located by Chapter
238, Street Standards. Proper and suitable tools and equipment shall be used in handling pipe and special care shall be taken to prevent damage to pipe coating. All pipe lengths shall be carefully examined for defects and no pipe shall be laid which is known to be defective. If any defective pipe should be discovered after being laid, it shall be removed and replaced with sound material.
B. All pipe shall be thoroughly cleaned immediately before
laying and shall be kept clean until accepted in the complete work.
Whenever pipe laying is stopped, the end of the pipe shall be securely
closed to prevent entrance of water or other obstructions.
C. Pipe shall be carefully bedded to have uniform support
its entire length. All points of rock or other material which tend
to injure the pipe coating shall be removed. All pipe must be supported
on blocking and wedges to hold it in position as directed by the engineer.
After laying, the pipe shall be carefully bedded in earth and tamped
into place. All specials and valves shall be carefully supported on
blocking as directed by the engineer. Stones or other material tending
to injure the coating of the pipe shall not be placed within one foot
of same. No frozen earth shall be used in backfilling.
D. All slugs and bends shall be thoroughly braced with
concrete in such a manner as will permit removal if necessary. Concrete
braces at plugs shall be square and of side dimension not less than
the nominal diameter of the pipe, and shall be securely wedged between
the plug and substantial anchorage. At bends, concrete shall be placed
between the outside face of the bend and the trench wall. It shall
extend from the bottom of the trench to three inches above the center
line of bend and shall not be less than two feet wide. Concrete for
the above shall be clean rock and silica sand mixed in proportions
of one cement, 2 1/2 sand and five stone.
E. Where it is necessary to cut pipe or specials, the
cutting shall be done in such manner as will prevent cracking or breaking
of the pipe longitudinally. Roughness of the cross section shall be
ground to a smooth, even surface at right angles to the axis of the
pipe and shall be satisfactory to the engineer. All rejected pipe
shall be removed immediately from the work area.
F. The contractor shall use care not to damage or interfere
with the operation of any gas, sewer, other water mains, electrical
or telephone conduits. If any damage results to any main or conduit
the contractor must make immediate repairs. The contractor shall ascertain
from representatives of the gas company the location of any existing
gas mains and shall give the gas, electric and telephone companies
48 hours' notice in advance before uncovering any "active" mains.
[Added 7-19-2023 by L.L. No. 2-2023]
A. Notwithstanding the provisions of §
259-9A requiring ductile iron pipe and fittings, HDPE pipe may be used for water mains when approved by the Town on a case-by-case basis.
B. All buried HDPE pressurized pipe shall be manufactured in accordance
with AWWA C906.
C. All buried HDPE pressurized pipe and fittings shall be made of polyethylene
compounds which conform to the physical requirements of PE 4710 and
meet the ASTM D3350 cell classification of 445474C.
D. All buried HDPE pressurized pipe shall be DR-11 with a pressure rating
of 200 psi and have a nominal DIPS (ductile iron pipe size) outside
diameter. At the discretion of the Town, DR-9 (pressure rating of
250 psi) may be required.
E. HDPE pressure pipe for potable water shall meet the requirements
of NSF 61.
F. HDPE piping shall be provided with permanent identification by coextruding
identification, such as striping, into the pipe's outer surface.
Identification material shall be the same material as the pipe material,
except for color (blue). Identification printed or painted on the
pipe surface will not be acceptable.
G. HDPE pipe and fitting joints shall be butt fused by heat fusion in
accordance with ASTM D3261 and the manufacturer's recommendations.
H. HDPE pipe shall provide sufficient length of AWG No. 11 stainless
steel tracer wire with 30 mil thick blue HDPE insulation. Tracer wire
length shall be such that a continuous piece can be used for each
run of pipe. Splices in the tracer wire shall be made with split bolt
connectors. Wire nuts or clip-type connectors are not acceptable.
A waterproof connection is required to prevent corrosion. Wire shall
be terminated above grade at a hydrant or stubbed up inside a valve
box to end at an accessible location. Where horizontal directional
drilling is the method used for HDPE pipe installation, two separate
and independent tracer wires shall be installed side by side.
I. Water services connected to HDPE mains shall be through the use of
electrofusion transition saddles. Electrofusion saddle outlet material
shall be Brass 360 Alloy with 304 stainless steel compression ring.
J. Electrofusion transition saddles must be approved by the Department
of Public Works and shall be selected in accordance with the table
below. Strap-on saddles will not be allowed.
Main Size
(In)
|
Outlet Size
(In)
|
---|
8 DIPS
|
1 CORP
|
10 DIPS
|
1 CORP
|
12 DIPS
|
1 CORP
|
8 DIPS
|
1 1/2 CORP
|
10 DIPS
|
1 1/2 CORP
|
12 DIPS
|
1 1/2 CORP
|
8 DIPS
|
2 CORP
|
10 DIPS
|
2 CORP
|
12 DIPS
|
2 CORP
|
[Added 7-19-2023 by L.L. No. 2-2023]
Stiffening inserts (stiffeners) may be used in HDPE pipes subject
to compliance with all of the following:
A. Stiffeners shall be provided at each MJ adapter and coupling for
HDPE pipe.
B. Stiffening inserts shall be specially designed for use on the inside
of HDPE pipe in conjunction with AWWA C111 mechanical joints.
C. Stiffeners shall provide stainless steel per ASTM 240, type 304 or
316.
D. Stiffeners shall be manufactured within the pipe or MJ adapter by
the factory.
E. Field-installed stiffeners may be allowed upon prior approval of
the Town. Wedge-style stiffeners are allowed.
F. Inserts must be designed for underground pressurized fluid service
and are pressure rated to match the pipe DR pressure rating, derated
as appropriate for service temperature. Maximum test pressure limited
to pipe rated pressure.
Valve boxes shall consist of cast-iron base,
center section and top section with cover which shall be marked "Water."
The top section shall be adjustable for elevation and shall be set
to allow equal movement above and below finished grade. The base shall
be centered over the valve and shall rest on compacted backfill. The
top of the base section shall be approximately on line with nut at
top of valve stem and the entire assembly shall be plumb.
As water pipe is installed in the development
of Town highways, all laterals shall be laid to the front line of
each lot, before roadway pavement is constructed.
Materials may be used if accompanied by manufacturer's
certificate of compliance, pending any tests that may be made by the
engineer.
Any person violating any provision of this article
shall be punishable, upon conviction, by a fine of not more than $250
or by imprisonment for not more than 15 days, or by both such fine
and imprisonment.