The storage, handling, installation, use and transfer of liquefied
natural gas shall be in accordance with NFPA 59A, except that more
restrictive requirements as specified in this article shall take precedence
over any NFPA requirements.
All equipment shall be installed and maintained in conformity
with the rules and regulations of the Chief Fire Marshal of the Town
of Brookhaven and the appropriate standards of the NFPA. It shall
be unlawful to install, service, handle or offer for sale, in any
form, liquefied natural gas and related equipment that does not conform
to the rules and regulations of the Chief Fire Marshal of the Town
of Brookhaven and the appropriate standards of the NFPA.
Any incident involving liquefied natural gas, including but
not limited to leaks, fires, explosions or any other accidental discharge
into the atmosphere in excess of 8.5 cubic feet, must be reported
to the Chief Fire Marshal by the responsible party or his representative.
The initial report may be made by telephone and followed by a written
report. Under no circumstances shall a report be filed later than
24 hours after the incident.