[Amended 1-23-1968 by Ord. No. 68-18; 6-27-1985 by Ord. No. 85-263; 2-14-2006 by Ord. No. 2006-22; 6-16-2009 by Ord. No. 2009-179]
The Commissioner of Neighborhood and Business
Development, as a condition to granting the said permit, may require
applicants to give him or her such information by statement, affidavit
or otherwise, as he or she may require, as to installation, use or
operation of the said heating apparatus.
Fuel used in heating apparatus, for the installation,
use or operation of which a permit is required by this chapter, shall
be such as does not emit a flammable vapor below a temperature of
100º F. when tested in a Pensky-Martens closed flash tester or
in a Tagliabue closed tester.
[Amended 5-24-1955; 1-23-1968 by Ord. No. 68-18; 2-10-1981 by Ord. No. 81-45; 2-14-2006 by Ord. No. 2006-22; 6-16-2009 by Ord. No. 2009-179]
A. The fuel used in the heating apparatus for which a
permit is required by this chapter shall be kept and stored in not
more than two tight metal or concrete tanks which shall be located
not less than five feet from the heating plant and the oil burner
and shall have a capacity of not more than 275 gallons each unless
buried below the level of the basement floor or completely surrounded
by a thickness of not less than one foot of earth, sand, concrete,
or similar heat-insulating materials. The Commissioner of Neighborhood
and Business Development may, however, grant permission to install
and maintain tanks outside of a building when in his or her opinion
no hazard will be created thereby and provided that such tanks are
installed and maintained under such conditions as he or she may impose.
B. The oil receptacles shall be so arranged as to prevent
gravity flow to the burners unless they are equipped with automatic
safety valves approved by the Commissioner of Neighborhood and Business
Development. When more than one tank is installed, connections between
tanks and the apparatus shall be made by means of three-way valves
approved by the Commissioner of Neighborhood and Business Development.
When the fuel mentioned in this chapter is stored
in a tank within the building, there shall be no artificial light
other than incandescent light in the room where and when such tank
is being filled.
[Amended 1-23-1968 by Ord. No. 68-18; 4-13-1971 by Ord. No. 71-206; 2-10-1981 by Ord. No. 81-45; 6-16-2009 by Ord. No. 2009-179]
The Commissioner of Neighborhood and Business
Development shall require the payment of the fee of $3 for the issuing
of the permits required by this chapter.
[Amended 9-28-1965; 7-22-1969 by Ord. No. 69-329]
Any person or corporation violating any of the
provisions of this chapter shall, upon conviction, be punishable by
a fine not exceeding $150 or by imprisonment not exceeding 15 days,
or by both such fine and imprisonment, or by a penalty of not less
than $25 nor more than $500 to be recovered by the City of Rochester
in a civil action.