BOARD OF APPEALS — Code Hearing Board.
| |
BUILDING OFFICIAL — Code Enforcement Officer.
| |
CORPORATION COUNSEL — Solicitor of the township.
| |
DEPARTMENT OF BUILDING INSPECTION — Office of Code Enforcement.
| |
NAME OF JURISDICTION — The Township of Marple.
|
All dwellings hereafter constructed in the Township of Marple shall
provide a minimum of one off-street paved parking space per dwelling unit,
except as otherwise required by the Zoning Ordinance. Said off-street paved
parking space may be provided in a garage with a paved drive leading from
the street to the garage or on a paved pad with a minimum dimension of 10
feet by 20 feet. Driveways leading to the garage or paved parking pad must
be a minimum of eight feet wide. All drives and off-street paved parking spaces
in residential districts shall be constructed of a minimum of four inches
of compacted crushed stone base on a thoroughly compacted subgrade with a
minimum of two inches of ID-2 wearing course or six inches of reinforced concrete
or seven inches of unreinforced concrete. Concrete shall have a certified
minimum compressive strength of 3,500 pounds per square inch. Drives and off-street
paved parking spaces in all districts other than residential shall be designed
by a registered engineer to withstand the anticipated loads but shall, at
a minimum, have a base course of six inches of crushed stone compacted over
a thoroughly compacted subgrade with 2 1/2 inches of ID-2 placed as 1 1/2
inches of binder course and one inch of wearing course. Off-street parking
pads shall not be permitted within the street right-of-way. Every application
for a permit to construct or alter a building requiring off-street parking
under the terms of the provisions hereinbefore set forth shall have indicated
on it, and in the plans and specifications which accompany it, sufficient
information regarding the off-street parking which it is proposed to provide
so as to enable the Building Official to determine that the requirements with
respect to off-street parking are being complied with. Every building permit
issued pursuant to an application and plans which include off-street parking
shall be deemed to be a permit onditioned upon the completion of the required
off-street parking facilities. Failure to complete the required off-street
facilities shall be a violation of the terms of the permit and shall constitute
a violation of this article. No certificate of occupancy shall be issued until
the required off-street parking facilities have been completed.
| |
Driveways.
| |
Location. Driveways shall be so located as to provide reasonable sight
distance at intersection with streets and not closer than five feet from side
lot lines. A stopping area measured 20 feet behind the right-of-way line shall
be provided not to exceed a four-percent grade.
| |
Intersections. Driveways shall be located not less than 40 feet from
the street intersection and shall provide access to the street of a lesser
classification when there are streets of different classes involved.
| |
Pavement widths and grade. Driveway paving widths and grade shall be
as follows:
|
Land Use
|
Minimum
Paving
Width
(feet)
|
Maximum
Curb Cut
(feet)
|
Maximum
Grade
|
Maximum
Change of
Grade per
10 Feet
|
---|---|---|---|---|
Single-family
|
8
|
15
|
14%
|
10%
|
residential
| ||||
Multifamily
|
12
|
23
|
8%
|
10%
|
residential
|
(one-way)
| |||
24
|
35
|
8%
|
10%
| |
(two-way)
| ||||
Commercial,
|
12
|
23
|
5%
|
7%
|
industrial
|
(one-way)
| |||
and
|
24
|
35
|
5%
|
7%
|
institutional
|
(two-way)
|
All driveways shall be located, designed and constructed in such a manner
as not to interfere or be inconsistent with the design maintenance and drainage
of the highway.
| |
Frontage of 50 feet or less shall be limited to one driveway. Normally
not more than two driveways need to be provided to any single property, tract
or business establishment. Exceptions may be made where the frontage exceeds
300 feet in length.
| |
Driveway cut at curb area shall be independent from the apron. The sidewalk
area under the driveway shall have a minimum thickness of six inches of concrete.
The concrete apron including the sidewalk area in the driveway shall be reinforced
with wire, six inches by six inches, number 9 wire (minimum). Two layers of
this wire shall be utilized with a minimum of two-inch spacing between layers.
The wire shall be installed so that it is not closer than 1/2 inch from the
top or bottom surfaces of the driveway.
| |
All concrete used in the construction of improvements shall be certified
to develop a compressive stress of at least 3,500 pounds per square inch air
entrained at 28 days with certification of the mix furnished to the Township
Engineer or the Township Director of Code Enforcement.
| |
A one-half-inch premolded expansion joint shall be placed between all
joints where concrete sidewalk abuts a concrete curb.
|
All gates must be self-latching and self-closing with latches placed
four feet above the underlying ground or otherwise made inaccessible from
the outside to small children. All gates must be kept closed except during
ingress and egress.
|
SECTION 1002.0 FIRE SUPPRESSION SYSTEMS
| ||
1002.1 Where required: Fire suppression systems shall be
installed and maintained in full operating condition, as specified by this
code, in the locations indicated in Sections 1002.2 through 1002.23.
| ||
1002.2 Use Group A-1: In all buildings or structures or
portions thereof when more than 1,500 square feet.
| ||
1002.3 Use Group A-2: In all buildings or structures or
portions thereof of Use Group A-2:
| ||
1.
|
When more than 1,500 square feet (1,116 square meters) in area.
| |
1002.4 Use Group A-3: In all buildings or structures or
portions thereof of Use Group A-3 when more than 1,500 square feet (1,116
square meters) in area.
| ||
1002.5 Stages and enclosed platforms: Stages under the
roof and gridiron, in the tie and fly galleries, and in all places behind
the proscenium wall of the stage; over and within enclosed platforms in excess
of 500 square feet (465 square meters) in area; and in dressing rooms, lounges,
workshops and storerooms accessory to such stages or enclosed platforms.
| ||
Exceptions
| ||
1.
|
Stages or enclosed platforms open to the auditorium room on three or
more sides.
| |
2.
|
Altars, pulpits or similar platforms and their accessory rooms.
| |
3.
|
Stage gridirons when sidewall sprinklers with one-hundred--thirty-five-degree-Fahrenheit
(fifty--seven-degree-Celsius) rated heads with heat-baffle plates are installed
around the perimeter of the stage except for the proscenium opening at points
not more than 30 inches (762 millimeters) below the gridiron nor more than
six inches (152 millimeters) below the baffle plate.
| |
4.
|
Under stage or under enclosed platform areas less than four feet (1219
millimeters) in clear height used exclusively for chair or table storage and
lined on the inside with materials approved for one-hour-fire-resistance-rated
construction.
| |
1002.6 Use Group B; R-1, R-2, R-3 and R-4: In all buildings
or structures or portions thereof when more than 1,500 square feet.
| ||
1002.7 Use Group E: In all buildings or structures or portions
thereof when more than 1,500 square feet.
| ||
1002.8 Use Group H: In all buildings or structures or portions
thereof of Use Group H.
| ||
1002.9 Use Group I: In all buildings or structures or portions
thereof when more than 1,500 square feet.
| ||
1002.10 Use Groups M, S-2, F and U: In all buildings or
structures or portions thereof when more than 1,500 square feet.
| ||
1002.11 Public garages (Groups 1 and 2): In all public
garages when more than 1,500 square feet. Exception: open parking structure
as defined in Section 607.1.
| ||
1002.12 All use groups: An automatic suppression system
shall be installed in any portion of a structure below a residential occupancy,
regardless of floor area.
| ||
1002.13 Bus garages: In all bus garages:
| ||
1.
|
When required by Section 1002.10.
| |
2.
|
When used as passenger terminals for four or more buses.
| |
3.
|
When used for storage or loading of four or more buses.
| |
1002.14 Unlimited area buildings: In unlimited area buildings
as required by Section 504.0.
| ||
1002.15 Storage and workshop areas: In all portions of
Use Groups A, B, E, I, R-1 and R-2 occupied for storage, workshop or similar
purposes and as provided in Sections 610.2 and 611.7 for Use Groups I-2 and
I-3, respectively.
| ||
1002.16 All use groups: An automatic suppression system
shall be installed in any below-grade area of 1,500 square feet or more.
| ||
1002.17 Painting rooms: In spray-painting rooms or shops
where painting, brushing, dipping or mixing is regularly conducted using flammable
materials.
| ||
1002.18 Trash rooms and chutes: In rooms or areas used
for incineration, trash and laundry collection and similar uses and at alternate
floor levels and at the top of all chutes used in conjunction with these rooms
or areas.
| ||
1002.19 Furnace rooms: In furnace rooms, boiler rooms and
rooms for similar uses.
| ||
1002.20 Unenclosed vertical openings: In unenclosed vertical
openings between floors as required by Section 606.3.
| ||
1002.21 Kitchen exhaust systems: In commercial exhaust
systems when such systems are required by the Mechanical Code listed in Appendix
A.
| ||
1002.22 Hazardous exhaust systems: In duct systems exhausting
hazardous materials in accordance with the Mechanical Code listed in Appendix
A.
| ||
1002.23 Alternate protection: In special use areas of buildings
or structures, an automatic fire alarm system may be installed in lieu of
a fire suppression when approved by the code official and Chief Fire Official
and when such fire suppression system installation would be detrimental or
dangerous to the specific use or occupancy.
|